2000/2300kVA Electrical Substation Transformer-13.8 / 0.48 kV|AMẸRIKA 2025
Agbara: 2000/2300 kVA
Foliteji: 13.8-0.48GrdY / 0.277kV
Ẹya: pẹlu FR3 epo ati CT

Awọn ilu ti n ṣe agbara, Awọn ile-iṣẹ & Ni ikọja – Ga-Awọn Ayirapada Ibusọ Imudara ṣiṣe fun Akoj Smarter.
01 Gbogbogbo
1.1 Project Apejuwe
2000/2300 kVA substation transformer ti a jišẹ si America ni 2025. Awọn won won agbara ti awọn transformer jẹ 2000/2300 kVA pẹlu KNAN/KNAF itutu. Foliteji akọkọ jẹ 13.8 kV pẹlu ± 2 * 2.5% ibiti o tẹ ni kia kia (NLTC), foliteji keji jẹ 0.48GrdY / 0.277 kV, wọn ṣẹda ẹgbẹ fekito ti Dyn1.
Ṣafihan transformer substation 2000/2300 kVA - ojutu agbara to lagbara ti a ṣe atunṣe fun awọn ohun elo ti n beere ni Iṣakoso Agbara Aifọwọyi (APC), Awọn ohun elo Afẹfẹ giga (HAF), Giga- Awọn ohun elo Fifuye (HLSB), ati Awọn ọna ikojọpọ Wagon. Oluyipada išẹ giga yii - ṣe ẹya 5A olutako ilẹ didoju fun imudara idabobo aiṣedeede, alayipada 5:5 ipin deede fun ibojuwo deede, ati iwọn kukuru C10{10} lati koju awọn aapọn itanna to gaju.
Ti a ṣe apẹrẹ fun igbẹkẹle ninu awọn amayederun to ṣe pataki, o funni ni pinpin agbara iduroṣinṣin fun awọn eto iṣakoso aladaaṣe, giga{0}awọn agbegbe itutu agbaiye, eru{1} awọn ile-iṣẹ fifuye, ati awọn iṣẹ eekaderi oju-irin. Pẹlu ikole gaungaun rẹ ati awọn ẹya aabo to ti ni ilọsiwaju, pẹlu iṣapeye aropin lọwọlọwọ lọwọlọwọ ati kukuru kukuru -Ayika ti o duro ni agbara, transformer yii ṣe idaniloju iṣẹ ṣiṣe ti ko ni idilọwọ nibiti didara agbara ati aabo eto ṣe pataki julọ. Awọn atunto aṣayan pẹlu awọn agbara ibojuwo latọna jijin ati awọn solusan itutu agbaiye lati pade awọn ibeere iṣẹ ṣiṣe kan pato.
1.2 Imọ pato
2000/2300 kVA substation transformer ni pato iru ati data dì
|
Jišẹ si
America
|
|
Odun
2025
|
|
Iru
Amunawa substation
|
|
Standard
ANSI / IEEE C57.12.00
|
|
Ti won won Agbara
2000/2300 kVA
|
|
Igbohunsafẹfẹ
60HZ
|
|
Ipele
3
|
|
Itutu agbaiye
KNAN/KNAF
|
|
Primary Foliteji
13.8kV
|
|
Secondary Foliteji
0,48GrdY / 0,277 kV
|
|
Ohun elo Yiyi
Ejò
|
|
Angular nipo
Dyn1
|
|
Ipalara
6%
|
|
Tẹ Ayipada
NLTC
|
|
Ibiti titẹ ni kia kia
±2*2.5%
|
|
Ko si Ipadanu Ẹru
Kere ju tabi dogba si 2.36kW
|
|
Lori Ipadanu Fifuye
Kere ju tabi dogba si 17kW
|
1.3 Yiya
2000/2300 kVA substation transformer aworan atọka iyaworan ati iwọn.
![]() |
![]() |
02 iṣelọpọ
2.1 mojuto
Ipilẹ laminated jẹ ẹya paati pataki ti - ipele mẹta,{1}mẹta{1} alayipada alapapọ ẹsẹ ẹsẹ, ti n pese ọna kekere{2} fun ṣiṣan oofa lakoko ti o dinku awọn adanu lọwọlọwọ eddy. Ti a ṣe lati awọn ohun elo irin silikoni tolera, mojuto n ṣe ẹya apẹrẹ iwe mẹta{4}} ti o mu ki pinpin ṣiṣan oofa pọ si fun iṣiṣẹ iwọntunwọnsi mẹta{5}. Ilana ti o lagbara ni idaniloju ṣiṣe giga, idinku ko si - adanu fifuye, ati ṣiṣe igbẹkẹle labẹ awọn ipo ẹru oriṣiriṣi. Apẹrẹ ti a fi sita tun nmu iduroṣinṣin igbona pọ si ati agbara ẹrọ, ti o jẹ ki o dara julọ fun awọn ohun elo idasile agbara giga-.
2.2 Yiyi

LV Yiyi:Ti a ṣe ti bankanje bàbà, ti o funni ni awọn ipele iwapọ, itutu agbapada aṣọ ile, ati agbara kukuru kukuru{{0}.
HV Yiyi:Olona-afẹfẹ helical Layer pẹlu idabobo ti a fikun, iṣapeye aarin{1}}apaacitance fun iduroṣinṣin giga{2}foliteji.
2.3 ojò
Tanki transformer n ṣiṣẹ bi ibi aabo fun oluyipada akọkọ, ti a ṣe pẹlu awọn apẹrẹ irin welded didara{0} ni apẹrẹ edidi ni kikun. Ojò naa gba awọn idanwo titẹ lile lati rii daju iṣẹ igbẹkẹle labẹ awọn iyatọ titẹ epo iṣẹ ati awọn ipo aṣiṣe inu. Ọpọlọpọ awọn ṣiṣii flanged ni a pese fun awọn igbo, awọn afihan ipele epo, ati awọn ẹrọ ibojuwo. Awọn oju inu inu gba itọju ipata - ati pẹlu idabobo oofa lati dinku awọn adanu ti o yapa. Awọn aṣayan aṣa pẹlu atako - awọn ideri ipata tabi ikole irin alagbara fun awọn agbegbe ti o nbeere.

2.4 ik Apejọ

Apejọ oluyipada substation jẹ akopọ mojuto, fifi sori ẹrọ yikaka (bankanje LV + waya HV), titunṣe apakan ti nṣiṣe lọwọ, asopọ ebute, lilẹ ojò, ati iṣagbesori ẹya ẹrọ, pẹlu kikun epo iyipada igbale ati awọn idanwo ile-iṣẹ (ipin, impedance, dide otutu, bbl) lati rii daju ibamu. Apẹrẹ apọjuwọn jẹ ki gbigbe gbigbe ati itọju rọrun.
03 Idanwo
|
Rara. |
Nkan Idanwo |
Ẹyọ |
Awọn iye gbigba |
Iwọn Iwọn |
Ipari |
|
1 |
Awọn wiwọn Resistance |
% |
Iwọn aidogba resistance ti o pọju |
4.55 |
Kọja |
|
2 |
Awọn idanwo ipin |
% |
Iyapa ti ipin foliteji lori titẹ ni akọkọ: Kere tabi dọgba si 0.5% |
-0.07~0.12 |
Kọja |
|
3 |
Ipele{0}} igbeyewo ibatan |
/ |
Dyn1 |
Dyn1 |
Kọja |
|
4 |
Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun |
% |
I0 :: pese iye iwọn |
0.35 |
Kọja |
|
kW |
P0: pese iye iwọn |
2.096 |
|||
|
/ |
Ifarada fun ko si pipadanu ẹru jẹ +0% |
/ |
|||
|
5 |
Awọn adanu fifuye, foliteji ikọlu, awọn adanu lapapọ ati ṣiṣe |
/ |
t:85 iwọn ifarada fun ikọlura jẹ +7.5% ifarada fun pipadanu fifuye lapapọ jẹ +0% |
/ |
Kọja |
|
% |
Z%: iye iwọn |
6.38 |
|||
|
kW |
Pk: iye iwọn |
16.642 |
|||
|
kW |
Pt: iye iwọn |
18.738 |
|||
|
% |
Ṣiṣe ko kere ju 99.27% |
99.30 |
|||
|
6 |
Applied Foliteji Igbeyewo |
/ |
HV: 34kV 60s LV: 10kV 60s |
Ko si iparun ti foliteji idanwo waye |
Kọja |
|
7 |
Induced Foliteji withstand Igbeyewo |
/ |
Foliteji ti a lo (kV): 0.96 |
Ko si iparun ti foliteji idanwo waye |
Kọja |
|
Iye akoko:40 |
|||||
|
Igbohunsafẹfẹ (HZ): 180 |
|||||
|
8 |
Idiwon Resistance idabobo |
GΩ |
HV{0}LV si Ilẹ: |
6.50 |
/ |
|
LV-HV si Ilẹ: |
7.12 |
||||
|
HV&LV si Ilẹ: |
5.05 |
||||
|
9 |
Idanwo jijo |
/ |
Ipa titẹ: 50kPA |
Ko si jijo ati ki o ko Bibajẹ |
Kọja |
|
Iye akoko: 12h |
|||||
|
10 |
Idanwo epo |
kV |
Dielectric Agbara |
51.6 |
Kọja |
|
mg/kg |
Ọrinrin akoonu |
176.8 |
|||
|
% |
Okunfa ifasilẹ |
3.205 |
|||
|
mg/kg |
Furan Analysis |
/ |
|||
|
/ |
Gaasi Chromatography Analysis |
/ |


04 Iṣakojọpọ ati Sowo
4.1 Iṣakojọpọ
Oluyipada ile-iṣẹ gba irin ti o wa ni kikun{0}} iṣakojọpọ igi. Férémù àkọ́kọ́ ni a ṣe pẹ̀lú ọ̀nà gíga - irin ìkanni tí a fi agbára welded, ní ìpèsè pẹ̀lú àwọn àtìlẹ́yìn atako- inú. Àpótí náà ṣe àkópọ̀ àwọn ọ̀rọ̀ gbígbé sókè fún àbójútó àìléwu pẹ̀lú àwọn kọ̀rọ̀ tàbí fọ́nfọ́, ó sì jẹ́ àmì ní kedere pẹ̀lú àwọn ìkìlọ̀ (fun apẹẹrẹ, “Ẹgẹ́,” “Jeki Gbẹ́”). Awọn iwe aṣẹ pataki (akojọ iṣakojọpọ, awọn ijabọ idanwo iyipada) ti wa ni ipamọ ninu apo kekere ti ko ni omi inu apoti.
4.2 Gbigbe
A ti gbe transformer lọ si ibudo lori ọkọ ayọkẹlẹ tirela - ti o wuwo, ti o so ni aabo lati dena iyipada. Ni ibudo, o ti kojọpọ sinu apoti kan, pẹlu àmúró to dara ati aabo ọrinrin. Ohun elo edidi naa jẹ gbigbe nipasẹ ọkọ oju-omi okun pẹlu itọpa akoko gidi{{3}. Awọn iwe aṣẹ kọsitọmu ti pese tẹlẹ fun imukuro didan.
05 Ojula ati Lakotan
Gẹgẹbi paati pataki ninu awọn amayederun agbara, awọn oluyipada ipapopada wa n pese iṣẹ ṣiṣe ti o gbẹkẹle, iṣẹ ṣiṣe to lagbara, ati agbara{0}} iṣẹ ṣiṣe daradara. Imọ-ẹrọ lati pade awọn iṣedede agbaye, wọn rii daju gbigbe ina mọnamọna iduroṣinṣin fun ile-iṣẹ, iṣowo, ati awọn ohun elo IwUlO. Pẹlu awọn aṣayan isọdi ati iṣakoso didara lile, a pese awọn ojutu ti a ṣe deede si awọn ibeere akoj rẹ. Kan si wa lati fi agbara si awọn iṣẹ akanṣe rẹ pẹlu igboiya.

Awọn afiwe Gbona: olupilẹṣẹ ile-iṣẹ itanna, olupilẹṣẹ, olupese, idiyele, idiyele
You Might Also Like
100 kVA Pole Amunawa Amunawa-7.97 / 0.12 * 0.24 kV|C...
300 kVA paadi-Ayipada-34.5/0.208 kV|AMẸRIKA 2024
3750/4250 kVA Substation Amunawa-13.8 / 0.48 kV|AMẸR...
2000 kVA Distribution Substation Amunawa-44 / 0,48 k...
3000 kVA Electrical Substation-44 / 0,6 kV|Canada 2025
1000/1150 kVA Distribution Transformer Substation-13...
Fi ibere ranṣẹ