160 kVA Inu Gbẹ Iru Amunawa-10 / 0.4 kV|Georgia ọdun 2025
Agbara: 160kVA
Foliteji: 10/0.4kV
Ẹya: pẹlu apade

Pipe fun Awọn ohun elo inu ile & Awọn ohun elo pataki - Ko si Epo, Ko si Ewu!
01 Gbogbogbo
1.1 Project Apejuwe
160 kVA resin simẹnti gbẹ iru transformer ti a jišẹ si Georgia ni 2025. Awọn won won agbara ti awọn transformer jẹ 160 kVA pẹlu ONAN itutu. Foliteji akọkọ jẹ 10 kV pẹlu ± 2 * 2.5% ibiti o tẹ ni kia kia (NLTC), foliteji keji jẹ 0.4 kV, wọn ṣẹda ẹgbẹ fekito ti Dyn11.
Simẹnti resini iru ayirapada jẹ aṣoju ailewu, eco{0}}ore, ati giga{1} yiyan išẹ si epo ibile{2}awọn transformers ti o kun, ti o nfihan resini iposii{3} ti o ni awọn iyipo ti o ṣe imukuro awọn ewu ina ati awọn iwulo itọju. Awọn oluyipada wọnyi kii ṣe ina - (pade awọn ilana IEC 60076-11), tako ọrinrin, eruku, ati ipata kemikali, wọn si ṣiṣẹ ni ipalọlọ (<55 dB) with minimal cooling requirements. Ideal for indoor, urban, and sensitive environments-such as hospitals, data centers, and renewable energy plants-they offer high efficiency (up to 99%), low partial discharge, and a 30+ year lifespan. Their compact, oil-free design ensures easy installation in harsh conditions (coastal, industrial, or offshore), while compliance with IEC, IEEE, and UL standards guarantees reliability.
Pẹlu awọn agbara abojuto IoT{0} ati awọn eewu ayika odo, awọn oluyipada resini simẹnti jẹ yiyan ode oni fun alagbero ati pinpin agbara ailewu.
1.2 Imọ pato
160 kVA resini simẹnti gbẹ iru transformer sipesifikesonu ati data dì
|
Jišẹ si
Ilọsiwaju agbara, Ṣiṣeto Ọjọ iwaju.
|
|
Odun
2025
|
|
Iru
Resini simẹnti gbẹ iru transformer
|
|
Ohun elo mojuto
Ọkà Oorun ohun alumọni, irin dì
|
|
Standard
IEC60076-11, EN50541-1, ISO9001, ISO14001
|
|
Ti won won Agbara
160kVA
|
|
Igbohunsafẹfẹ
50HZ
|
|
Ẹgbẹ Vector
Dyn11
|
|
Ipele
3
|
|
Itutu agbaiye
ONAN
|
|
Primary Foliteji
10 kV
|
|
Secondary Foliteji
0.4 kV
|
|
Ohun elo Yiyi
Aluminiomu
|
|
Ipalara
6%
|
|
Tẹ Ayipada
NLTC
|
|
Ibiti titẹ ni kia kia
± 2 * 2.5% @ ẹgbẹ akọkọ
|
|
Ko si Ipadanu Ẹru
0,55 kW
|
|
Lori Ipadanu Fifuye
2.4 kW
|
|
Ipele idabobo
F
|
1.3 Yiya
160 kVA resini simẹnti gbẹ iru transformer iyaworan aworan ati iwọn.
![]() |
![]() |
02 iṣelọpọ
2.1 mojuto
Simẹnti resini gbẹ - Iru transformer core nlo giga{1}} irin CRGO silikoni irin (0.23{4}}0.30mm) pẹlu iwọn 45 ni kikun{5}}igbesẹ{7}} awọn isẹpo mitered itan ati annealing hydrogen (800-850 iwọn kekere tabi iwọn kekere) lati ṣaṣeyọri 1.0W/kg), iṣẹ idakẹjẹ (<55dB), and high efficiency (IE4 class) at 1.6-1.7T flux density, while C6-class insulation coating and elastic spacers ensure thermal stability, complying with IEC 60076-11 standards.

2.2 Yiyi

Resini ti o gbẹ -iru onipo transformer n ṣe igbale-awọn wiwu bàbà ti a fi sinu akopo (HV: precision-waya ọgbẹ, LV: waya/foil) ninu resini iposii ti ko kun, ti o n ṣe ọna ẹrọ iyipo ti o lagbara pẹlu agbara itusilẹ apa kan (Kere tabi dogba si 10pC). Awọn ipele resini tinrin rẹ jẹ ki itutu agba AN daradara ṣiṣẹ nigba ti o pese ọrinrin -ẹri (agbara 100% RH), ina-idaduro, ati bugbamu-awọn ohun-ini ẹri.
Apẹrẹ n pese agbara dielectric giga (iduro monomono 75kV), kukuru -idaabobo ayika, ati itọju{2}}ọfẹ ni wiwapọ, idii iwuwo fẹẹrẹ dara fun fifuye{3}} fifi sori aarin.
1. Apejọ ara akọkọ
• Kokoro ati okun ti wa ni apejọ pẹlu ẹya atilẹyin rirọ, pẹlu aafo imugboroja 5-8mm ni ipamọ
Ṣeto awọn fẹlẹfẹlẹ pupọ ti idabobo oofa lati dinku awọn adanu ti o yapa nipasẹ 15-20%
2. Itanna Awọn isopọ
• Ẹgbẹ HV: Iyẹwu USB tabi awọn ohun elo bushing
• LV ẹgbẹ: Ejò busbar tabi USB ebute oko
3. Idaabobo Idaabobo
• Ipade IP20 (irin alagbara tabi Al{1}} awọn aṣayan irin ti a bo)
Awọn ikanni iderun titẹ (titẹ ti nwaye Ti o tobi ju tabi dogba si 0.5MPa)

03 Idanwo
|
Rara. |
Nkan Idanwo |
Ẹyọ |
Awọn iye gbigba |
Iwọn Iwọn |
Ipari |
|
|
1 |
Idiwon ti yikaka resistance |
/ |
Iwọn aidogba resistance ti o pọju Idaabobo laini: Kere tabi dogba si 2% |
HV (ila) |
LV (ila) |
Kọja |
|
0.33% |
1.68% |
|||||
|
2 |
Iwọn iwọn foliteji ati ṣayẹwo ti iṣipopada alakoso |
/ |
Ifarada ti ipin foliteji lori titẹ ni akọkọ: ± 1/10 Asopọmọra aami: Dyn11 |
0.00% ~ 0.13% Dyn11 |
Kọja |
|
|
3 |
Idiwon ti Kukuru -Imudanu ayika ati Pipadanu Ẹru |
/ kW kW |
t:120 iwọn Z%: iye iwọn Pk: iye iwọn Pt: iye iwọn |
3.90% 1.402 1.943 |
Kọja |
|
|
4 |
Wiwọn ti Bẹẹkọ -Padanu ati lọwọlọwọ ni 90% ati 110% ti foliteji ti a ṣe ayẹwo |
/ kW |
I0 :: pese iye iwọn P0: pese iye iwọn |
90% Ur |
0.81 0.450 |
Kọja |
|
100% Ur |
0.90 0.501 |
|||||
|
110% Ur |
0.99 0.551 |
|||||
|
5 |
Applied Foliteji Igbeyewo |
/ |
HV: 28kV 60s LV: 3kV 60s |
Ko si iparun ti foliteji idanwo waye |
Kọja |
|
|
6 |
Induced Foliteji withstand Igbeyewo |
/ |
Foliteji ti a lo (KV): 2 Úrì Foliteji ti o ni ilọsiwaju (KV): 0.8 Iye akoko:40 Igbohunsafẹfẹ (HZ): 150 |
Ko si iparun ti foliteji idanwo waye |
Kọja |
|
|
7 |
Idanwo Sisọjade Apa kan |
pC |
Ipele ti o pọju ti awọn idasilẹ apakan yoo jẹ 10 pC |
<10 |
Kọja |
|


04 Iṣakojọpọ ati Sowo
4.1 Iṣakojọpọ
• Logan Onigi Crating
Fireemu ipilẹ ti a ṣe pẹlu igilile (Ti o tobi ju tabi dogba si sisanra 50mm)
Àmúró inu lati ṣe idiwọ gbigbe lakoko gbigbe
• Oju ojo Idaabobo
Ṣiṣu film murasilẹ (IP65-ti won won) fun ọrinrin / ekuru resistance
Awọn baagi desiccant (jeli siliki) inu apoti lati ṣakoso ọriniinitutu
• Gbigbọn mọnamọna
Giga - fifẹ foomu iwuwo ni awọn igun ati awọn paati ipalara
Ikun irin (Ti o tobi ju tabi dogba si iwọn 10mm) fun didi to ni aabo

4.2 Gbigbe

• Ojuse Olupese
Pese ẹrọ oluyipada daradara si Port Shanghai (ebute adehun).
Pese iwe-ipamọ okeere pipe (Atokọ Iṣakojọpọ, Invoice Iṣowo, Ijẹrisi IEC, ati bẹbẹ lọ).
Rii daju pe ẹru ti kojọpọ ni aabo sori ọkọ oju omi (ṣugbọn awọn gbigbe eewu si olura lori ikojọpọ).
05 Ojula ati Lakotan
Resini simẹnti wa gbẹ-iru awọn oluyipada ti n ṣojuuṣe idapọ pipe ti isọdọtun, ṣiṣe, ati imuduro. Ti a ṣe pẹlu idabobo ti o ga julọ, ipadanu agbara diẹ, ati itọju{2}}ọfẹ, wọn jẹ yiyan ti o dara julọ fun ile-iṣẹ, iṣowo, agbara isọdọtun, ati awọn ohun elo ayika ti o nbeere. Pẹlu idojukọ to lagbara lori ailewu ati igbẹkẹle, a ṣe jiṣẹ agbara{4}} fifipamọ, kekere{5} awọn ojutu itujade ti o ṣe atilẹyin awọn amayederun agbara alawọ ewe.
Ilọsiwaju agbara, Ṣiṣeto Ọjọ iwaju.

Awọn afiwe Gbona: Oluyipada iru gbigbẹ inu ile, olupese, olupese, idiyele, idiyele
You Might Also Like
400 kVA Gbẹ Iru Itanna Ayirapada-0.55 / 0,46 kV|Salv...
3 MVA Gbẹ Iru Ayirapada-13.8 / 0,48 kV|Ilu Jamaa ni ...
630 kVA 3 Ipele Gbẹ Iru Amunawa-6.6 / 0.55 kV|South ...
2100 kVA Gbẹ Iru Pipin Amunawa-13.8 / 0.46 kV|South ...
630 kVA Mẹta Ipele Gbẹ Iru Amunawa-10 / 0,4 kV|Georg...
630 kVA Simẹnti Resini Gbẹ Iru Amunawa-66.6 / 0.55 k...
Fi ibere ranṣẹ