630 kVA Simẹnti Coil Amunawa-6.6 / 0,55 kV|South Africa 2025

630 kVA Simẹnti Coil Amunawa-6.6 / 0,55 kV|South Africa 2025

Orilẹ-ede: South Africa 2025
Agbara: 630 kVA
Foliteji: 6.6 / 0.55 kV
Ẹya: pẹlu oluṣakoso iwọn otutu ati awọn onijakidijagan
Fi ibere ranṣẹ

 

 

630 kVA cast coil transformer

Simẹnti Resini Iru Ayipada – Ina -Atako, Solusan Agbara ipalọlọ!

 

 

01 Gbogbogbo

1.1 Project Apejuwe

630 kVA gbẹ iru transformer ti a fi jišẹ si South Africa ni 2025. Awọn won won agbara ti awọn transformer jẹ 630 kVA pẹlu ONAN/ONAF itutu. Foliteji akọkọ jẹ 6.6 kV pẹlu ± 2 * 2.5% ibiti o tẹ (NLTC), foliteji keji jẹ 0.55 kV, wọn ṣẹda ẹgbẹ fekito ti Dyn11.

Amupada Iru Gbẹ Cast Resini jẹ gige - ojutu itanna eti ti a ṣe apẹrẹ fun aabo ti o ga julọ, ṣiṣe, ati igbẹkẹle. Ko dabi epo ibile - awọn transformer ti o kun, o nlo ina - resini epoxy retardant lati bo awọn yiyi pada, imukuro ewu ti epo n jo, ina, ati awọn eewu ayika.

Ti o dara julọ fun awọn fifi sori inu ile, awọn oluyipada wọnyi nṣiṣẹ ni idakẹjẹ, nilo itọju to kere, ati pe o ni itara pupọ si ọrinrin, eruku, ati awọn agbegbe ibajẹ.

Pẹlu imuduro igbona to dara to dara julọ ati awọn ohun-ini imukuro ara ẹni{{0}, wọn rii daju pe agbara ainidilọwọ ni awọn ohun elo to ṣe pataki gẹgẹbi awọn ile iṣowo, awọn ile-iwosan, awọn ile-iṣẹ data, ati awọn ile-iṣẹ iṣelọpọ. Yiyan Cast Resini Dry Type Transformer tumọ si idoko-owo ni mimọ, eco -ore, ati eto pinpin agbara pipẹ{3} ti o ṣe pataki aabo ati iṣẹ.

 

 

 

1.2 Imọ pato

630 kVA iru gbẹ iru transformer sipesifikesonu ati data dì

Jišẹ si
gusu Afrika
Odun
2025
Iru
Amunawa iru gbigbẹ
Ohun elo mojuto
Ọkà Oorun ohun alumọni, irin dì
Standard
IEC60076
Ti won won Agbara
630kVA
Igbohunsafẹfẹ
50HZ
Ẹgbẹ Vector
Dyn11
Ipele
3
Itutu agbaiye
ONAN/ONAF
Primary Foliteji
6.6kV
Secondary Foliteji
0.55kV
Ohun elo Yiyi
Aluminiomu
Ipalara
6%
Tẹ Ayipada
NLTC
Ibiti titẹ ni kia kia
± 2 * 2.5% @ ẹgbẹ akọkọ
Ko si Ipadanu Ẹru
1.3KW
Lori Ipadanu Fifuye
6.5KW

 

 

1.3 Yiya

630 kVA simẹnti resini gbẹ iru transformer iyaworan ati iwọn.

630 kVA cast resin dry type transformer drawing

 

 

02 iṣelọpọ

2.1 mojuto

Ayipada iru mojuto ti a ṣe pẹlu giga -tutu tutu{1}} ti yiyi silikoni irin laminations ni igbesẹ kan{2}} iṣeto ni ipele ipele lati dinku isunmọ ati awọn adanu lọwọlọwọ. Ipilẹ Iru Core ṣe idaniloju pinpin pipinka ati imudara ooru ti o ni ilọsiwaju. Pẹlu atako - idabobo idabobo, o nfi iṣẹ ṣiṣe dakẹ, dide ni iwọn otutu kekere, ati imudara agbara ṣiṣe fun iṣẹ ṣiṣe igbẹkẹle.

630 kVA cast coil transformer iron core

 

2.2 Yiyi

epoxy resin windings

Awọn ẹya ara ẹrọ transformer iposii resini windings, aridaju superior idabobo ati darí agbara. Awọn iyipo HV / LV jẹ ti awọn olutọpa aluminiomu pẹlu idabobo interlayer fun imudara agbara dielectric. Awọn igbo ninu ẹrọ oluyipada ti fi sori ẹrọ ni awọn ebute iyipo fun awọn asopọ itanna to ni aabo ati itọju irọrun. Awọn yiyi jẹ ọrinrin -ẹri ati eruku{4}}, o dara fun awọn agbegbe lile.

 

2.3 ik Apejọ

Ayipada yi gba oniru to ti ni ilọsiwaju, ti o nfihan iposii{0}}awọn yiyi simẹnti resini ati igbesẹ{1}}awọn ohun kohun ti o ṣopọ pẹlu awọn biraketi idabobo transformer. Ẹka naa ṣepọ oluṣakoso iwọn otutu ti oye ati awọn onijakidijagan itutu agbaiye ti o ṣatunṣe ṣiṣan afẹfẹ laifọwọyi da lori awọn ipo fifuye. Pẹlu idayatọ ni kikun, ipata - awọn bushings sooro ati awọn ebute, ṣiṣi - ọna fireemu rẹ pẹlu awọn ikanni iṣapeye ṣiṣan afẹfẹ n ṣe idaniloju itusilẹ ooru to munadoko fun ṣiṣe igbẹkẹle labẹ awọn ipo ẹru pupọ.

630 kVA cast coil transformer assembly

 

 

03 Idanwo

Rara.

Nkan Idanwo

Ẹyọ

Awọn iye gbigba

Awọn iye Diwọn

Ipari

1

Idiwon ti yikaka resistance

/

Iwọn aidogba resistance ti o pọju

Idaabobo laini: Kere tabi dogba si 2%

HV (ila)

LV (ila)

Kọja

0.06%

0.61%

2

Iwọn iwọn foliteji ati ṣayẹwo ti iṣipopada alakoso

/

Ifarada ti ipin foliteji lori titẹ ni akọkọ: ± 1/10

Asopọmọra aami: Dyn11

-0.02% ~ 0.16%

Dyn11

Kọja

3

Idiwon ti Kukuru -Imudanu ayika ati Pipadanu Ẹru

/

kW

kW

t:120 iwọn

Z%: iye iwọn

Pk: iye iwọn

Pt: iye iwọn

6.02%

4.55

6.28

Kọja

4

Wiwọn ti Bẹẹkọ -Padanu ati lọwọlọwọ ni 90% ati 110% ti foliteji ti a ṣe ayẹwo

/

kW

I0:: pese iye iwọn

P0: pese iye iwọn

90% Ur

0.414

0.985

Kọja

100% Ur

0.46

1.095

110% Ur

0.506

1.204

5

Applied Foliteji Igbeyewo

/

HV: 20kV 60s

LV: 3kV 60s

Ko si iparun ti foliteji idanwo waye

Kọja

6

Induced Foliteji withstand Igbeyewo

/

Foliteji ti a lo (KV):

2 Úrì

Foliteji ti o ni ilọsiwaju (KV): 1.1

Iye akoko:40

Igbohunsafẹfẹ (HZ): 150

Ko si iparun ti foliteji idanwo waye

Kọja

7

Idanwo Sisọjade Apa kan

pC

Ipele ti o pọju ti awọn idasilẹ apakan yoo jẹ 10 pC

<10

Kọja

 

630 kVA cast coil transformer testing
630 kVA cast coil transformer test

 

 

04 Iṣakojọpọ ati Sowo

4.1 Iṣakojọpọ

Ayipada Simẹnti Resini Gbẹ Iru ti wa ni aabo ni aabo ni erupẹ -awọn apoti plywood iṣẹ, ti n pese aabo to lagbara lakoko gbigbe ati ibi ipamọ.

Irin{0}}awọn egbegbe ti a fi agbara mulẹ jẹki idakokoro ipa, lakoko ti itusilẹ aṣa ṣe aabo fun koko ati awọn yiyi. Awọn aami ita (aarin ti walẹ, awọn ikilọ ọrinrin, awọn aaye gbigbe) ni ibamu pẹlu awọn iṣedede eekaderi agbaye.

630 kVA cast coil transformer packing

 

4.2 Gbigbe

630 kVA cast coil transformer shippment

Oluyipada naa ti wa ni gbigbe labẹ awọn ofin CIF (Iye owo, Iṣeduro & Ẹru) nipasẹ okun lati awọn ebute oko oju omi China si Durban, South Africa. Gbigbe ẹrọ oluyipada pẹlu iṣeduro okun kikun ti o bo iye ẹru lapapọ. Awọn iṣẹ gbigbe ẹru alamọdaju ni a pese fun idasilẹ kọsitọmu ati ayewo ni ibudo ibi-ajo.

Gbigbe ni kiakia nigbati o ba de ni a gbaniyanju lati yago fun awọn idiyele demurrage.

 

 

05 Ojula ati Lakotan

Gẹgẹbi ojutu ti o gbẹkẹle fun awọn ọna ṣiṣe agbara, Cast Resini Dry Type Transformer duro jade pẹlu epo rẹ {{0} apẹrẹ ọfẹ, aabo ina, aabo ọrinrin, ati itọju{1}}ọfẹ, ti o jẹ ki o dara julọ fun awọn ile iṣowo, awọn ohun ọgbin ile-iṣẹ, ati awọn ohun elo agbara isọdọtun. Pẹlu imọ-ẹrọ konge ati iṣakoso didara ti o muna, gbogbo ẹyọkan n funni ni ṣiṣe giga, ailewu, ati agbara.

Nipa yiyan wa, kii ṣe ọja ti o ga julọ nikan ni o jere ṣugbọn atilẹyin imọ-ẹrọ alamọja ati okeerẹ lẹhin iṣẹ tita{{0}. Fun awọn alaye imọ-ẹrọ tabi awọn solusan adani, kan si ẹgbẹ imọ-ẹrọ wa loni!

630 kVA cast coil transformer with temperature controller and fans

 

Awọn afiwe Gbona: olupilẹṣẹ okun simẹnti, olupilẹṣẹ, olupese, idiyele, idiyele

Fi ibere ranṣẹ