Pole Mounted Transformer Installation and Operation Guide

Itọsọna yii ni wiwa fifi sori ẹrọ, iṣẹ ṣiṣe, ati itọju awọn oluyipada pipinka ti a fi sori ẹrọ ti epo-ipele kan ṣoṣo. O da lori awọn itọnisọna imọ ẹrọ ẹrọ ati awọn iṣedede ile-iṣẹ bii IEEE C57.12.00. Fifi sori ẹrọ ti o tọ, iṣẹ ṣiṣe ti o tọ, ati itọju deede jẹ pataki fun ailewu ati iṣẹ oluyipada igbẹkẹle. Itọsọna yii pẹlu gbigba ati mimu, iṣagbesori, awọn asopọ itanna, ilẹ ilẹ, iṣaaju-ati awọn sọwedowo agbara-lẹhin, iṣẹ ẹrọ aabo, awọn ayewo igbagbogbo, ati mimu omi mimu.

Ohun elo ti a bo: Awọn ayirapada pinpin kaakiri lori epo-ipele kanṣoṣo (ilana aṣa)
Awọn ajohunše to wulo: IEEE C57.12.00, IEEE C57.12.90, NEMA TR1, NFPA 70E
 


 

 

 

1. Gbogbogbo Abo

 

 

 

1.1 Awọn asọye ipele ewu

Ọrọ ifihan agbara

Itumo

IJAMBA

Ipo ti o lewu laipẹ eyiti, ti ko ba yago fun, yoo ja si iku, ipalara nla tabi ibajẹ ohun elo.

IKILO

Ipo ti o lewu eyiti, ti ko ba yago fun, o le ja si iku, ipalara nla tabi ibajẹ ohun elo.

Ṣọra

Ipo eewu ti o lewu eyiti, ti ko ba yago fun, le ja si ipalara kekere/iwọntunwọnsi tabi ibajẹ ohun elo.

 

1.2 Gbogbogbo aabo awọn ibeere

Nikanoṣiṣẹ eniyan(oṣiṣẹ ni fifi sori ẹrọ ohun elo foliteji giga, itọju, iṣiṣẹ, lilo PPE to dara, ati iranlọwọ akọkọ) le ṣiṣẹ lori ohun elo yii.

Ṣaaju eyikeyi itọju tabi ayewo:

  • Yọ ẹrọ oluyipada lati alatọna ipo.
  • Lo aṣawari foliteji ti o yẹ lati jẹrisifoliteji odo lori gbogbo awọn giga-foliteji ati kekere-foliteji bushings.
  • Daradara ilẹ gbogbo awọn ebute(mejeeji akọkọ ati keji).
  • Ro ṣee ṣe backfeed (fun apẹẹrẹ imurasilẹ monomono).

Maṣe gbarale yiyọkuro fiusi nikan tabi yi ipo pada bi ẹri ti agbara-agbara.

Wọ PPE ti o yẹ (awọn ibọwọ idabobo, aabo oju, aṣọ arc-flash) bi NFPA 70E ti beere fun.

Maṣe ṣiṣẹ awọn ẹrọ iyipada ti omi-omi nigbati iwọn otutu omi idabobo wa ni isalẹ:

  • Epo nkan ti o wa ni erupe ile aṣa tabi omi silikoni: -20 iwọn
  • R-omi otutu: 0 iwọn
  • FR3™ omi ester adayeba: -10 iwọn

 


 

 

 

2. Gbigba, Mimu ati Ibi ipamọ

 

 

2.1 Gbigba ayewo (ṣaaju gbigba silẹ)

Nkan

Iṣe

Awo oruko

Daju nọmba ni tẹlentẹle, kVA, HV/LV-wonsi, impedance, ito iru baramu ibere.

Ita bibajẹ

Ṣayẹwo fun dents, scratches, dibajẹ radiators, kun bibajẹ.

N jo

Ṣayẹwo awọn welds, bushings, awọn iwọn, awọn falifu fun awọn abawọn epo.

Awọn ẹya ẹrọ

Jẹrisi iwọn titẹ / igbale, iwọn ipele epo, thermometer, àtọwọdá sisan, awọn imuni, awọn fiusi, awọn iwe afọwọkọ, awọn aami ikilọ wa.

Iwọn titẹ-igbale

Kika yẹ ki o yatọ pẹlu iwọn otutu ibaramu. Odo igbagbogbo le ṣe afihan jijo kan.

Ti a ba rii ibajẹ tabi aito,akiyesi lori owo gbigba, ya awọn fọto, faili kan nipe pẹlu awọn ti ngbe, ki o si fi to olupese.

 

2.2 Gbigbe ati mimu

Kireni / gbígbé soke:

  • Lonikan ni pese gbígbé lugs. Maṣe gbe soke lati awọn igbo, awọn imooru tabi awọn ihò di isalẹ.
  • Awọn ohun elo gbigbe (awọn kio, awọn slings, ọpa ti ntan) gbọdọ jẹ iwọn fun iwuwo lapapọ (wo apẹrẹ orukọ).
  • Lo ọpa ti ntan kaakiri lati tọju awọn slings sunmọ inaro (igun Ti o kere ju tabi dọgba si iwọn 20 lati inaro).
  • Titẹ ti o pọju lakoko gbigbe:15 ìyí lati inaro.
  • Nigbati iwọn otutu ibaramu ba wa ni isalẹ -20 iwọn, mu pẹlu itọju afikun lati yago fun ibajẹ brittle.

Mimu Forklift:

  • Nikan fun awọn oluyipada ti a gbe ni aabo lori pallet gbigbe.
  • Forks gbọdọ fa patapata labẹ pallet.
  • Kògbe transformer unpalletised pẹlu kan forklift.

 

2.3 Ibi ipamọ

Igba kukuru: Tọju ni iṣakojọpọ atilẹba ni agbegbe mimọ, gbigbẹ, ti ko ni ibajẹ.

Long‑term (>osu 3):

  • Itaja lori kan duro, ipele dada. Lo awọn agbeko ipamọ.
  • Maṣe ṣe akopọAyirapada – ewu ti ojò ati bushing bibajẹ.
  • Ṣayẹwo ni gbogbo oṣu mẹta: iwọn titẹ, ipele epo, n jo, ipata.
  • Ti iwọn titẹ ba ka odo tabi ipele epo ṣubu, ṣe iwadii ati tunse awọn n jo.
  • Ṣe itọju titẹ rere diẹ (3-4 PSIG) pẹlu afẹfẹ gbigbẹ tabi nitrogen ti o ba ṣeeṣe.

 


 

 

 

3. Fifi sori Igbesẹ

 

 

 

3.1 Aṣayan ipo

Ni ibamu pẹlu IEEE C57.12.00 "Awọn ipo Iṣẹ deede":

  • Giga Kere ju tabi dọgba si 1000 m
  • otutu ibaramu – iwọn 25 si iwọn +40
  • Ko si eruku ti o pọ ju, awọn gaasi ipata, gbigbọn, tabi eewu iṣan omi.

Fi sori ẹrọ ni ipo ti o wa si awọn oṣiṣẹ ti a fun ni aṣẹ nikan (fun apẹẹrẹ apade titiipa tabi ọpa).

Jeki awọn radiators (ti o ba wa) laisi awọn idena.

 

3.2 polu iṣagbesori

Lo awọn biraketi hanger ti a pese fun iṣagbesori ọpá taara.

Agbara ọpá gbọdọ ṣe atilẹyin iwuwo lapapọ ti oluyipada (wo apẹrẹ orukọ).

Lẹhin iṣagbesori, tẹ si eyikeyi itọsọnako yẹ ki o kọja iwọn 3. Ilọju pupọ le:

  • Din insulating ito agbegbe ti ifiwe awọn ẹya ara.
  • Irẹwẹsi itutu agbaiye.
  • Fun awọn kika ipele epo eke.

 

3.3 Ilẹ-ilẹ

Lo awọnigbẹhin grounding pad tabi nutlori ojò.

Adaorin ilẹ (paapaa bàbà, Ti o tobi ju tabi dọgba si 16 mm²) gbọdọ ni ibamu pẹlu awọn koodu agbegbe.

Idaduro ilẹ yẹ ki o jẹ kekere bi o ti nilo nipasẹ awọn ilana agbegbe (nigbagbogbo Kere ju tabi dogba si 10 Ω).

Kòlo awọn biraketi hanger, awọn igbo tabi awọn ẹya miiran ti kii ṣe ilẹ fun didasilẹ.

So gbogbo awọn didoju to wa si didoju eto.

 

3.4 HV ati LV awọn isopọ

Nu ati ki o dan gbogbo ibarasun asopọ roboto ṣaaju ki asopọ.

Tẹle apẹrẹ asopọ lori apẹrẹ orukọ.

Mu awọn boluti pọ si awọn iye iyipo ti a fun ni Table 3 (wo Abala 8).

Yago fun awọn ẹru cantilever pupọ lori awọn igbo (maṣe fa awọn olutọpa ṣinṣin ju) – bibẹẹkọ bushing tabi bibajẹ gasiketi le ṣẹlẹ.

Awọn bọtini ebute idayatọ iyan ni ẹgbẹ HV ṣe iranlọwọ lati yago fun olubasọrọ ẹranko.

 

3.5 Atunto awọn asopọ LV inu (ti o ba nilo)

IpoAyipada pẹlu awọn igbo LV mẹta, ile-iṣelọpọ-ṣeto fun E/2E (fun apẹẹrẹ{2}}/240 V), ṣugbọn nilo foliteji E (fun apẹẹrẹ . 120 V).

Ilana:

  • De-agbara, ilẹ, tu silẹ titẹ (ṣiṣẹ PRV).
  • Yọ ideri transformer kuro tabi ideri imudani (wo Abala 8.7).
  • Tun LV nyorisi lati jara si afiwe bi o ṣe han lori aworan atọka orukọ.
  • Rii daju pe gbogbo awọn asopọ ti wa ni ṣinṣin (lo tabili iyipo), awọn itọsọna jẹ idabobo daradara, ati maṣe fi ọwọ kan ojò tabi ara wọn.
  • Tun ideri sori ẹrọ, ṣatunkun si ipele to dara, gba laaye wakati 24 lati yanju, lẹhinna ṣe idanwo ipin kan lati rii daju.

Kan si olupese ti ko ba ni idaniloju.

pole mounted transformer on a pole
polu agesin transformer
pole mounted transformer installation
polu agesin transformer fifi sori

 

 


 

 

 

4. Ṣiṣayẹwo Agbara-iṣaaju ati Awọn Idanwo

 

 

 

Ayipada ko gbọdọ ni agbara titi gbogbo awọn sọwedowo ati awọn idanwo wọnyi yoo pari ni aṣeyọri.

Rara.

Idanwo / Ṣayẹwo

Awọn alaye

Ilana gbigba

1

Idanwo ipin (TTR)

Lo oluyẹwo ipin titan transformer lori gbogbo awọn ipo tẹ ni kia kia

Kere ju tabi dọgba si ± 0.5%

2

Idaabobo idabobo

1000 V megger; yiyi-yika ati yikaka-ilẹ

Ti o tobi ju tabi dọgba si 1.0 GΩ (mimọ/gbẹ)

3

Ipo iyipada pupọ-foliteji

Ṣeto bi fun orukọplate, titiipa dabaru išẹ

Ipo ti o tọ

4

Fọwọ ba ipo yipada

Ṣeto si foliteji ti a ṣe iwọn (nigbagbogbo tẹ ni kia kia aarin)

Ipo ti o tọ

5

Ilẹ-ilẹ

Visual + wiwọn resistance ilẹ

Ni aabo, laarin opin agbegbe

6

Bolted awọn isopọ

Ayẹwo Torque fun Awọn tabili 1-4

Laarin iyipo iyipo

7

Ipele omi

Iwọn ipele tabi plug oju

Laarin "Ga" ati "Low"

8

Iwọn otutu omi

Ka thermometer

Ko si ni isalẹ laaye kere (wo isalẹ)

9

Oluwari Aṣiṣe Inu (IFD)

Yọ titiipa sowo osan kuro

Tipa kuro

10

Awọn oluyipada lọwọlọwọ (CTs)

Ti ko ba sopọ si fifuye, awọn itọsọna gbọdọ wa ni kuru ati ilẹ

Ko si Circuit ṣiṣi

11

Ẹya ẹrọ onirin

Iṣakoso, awọn iyika itaniji – ko si awọn asopọ alaimuṣinṣin tabi idabobo ti o bajẹ

Ipo ti o dara

12

Ipari ojò

Kun - ko si bibajẹ, ipata

Itewogba

 

Iwọn otutu ito ti o kere julọ ṣaaju gbigba agbara:

  • Epo ohun alumọni / silikoni: -20 iwọn
  • R-Iwọn otutu: 0 iwọn
  • FR3: -10 iwọn

Ti omi tutu ba tutu, gbona ni diẹdiẹ (fun apẹẹrẹ pẹlu awọn ibora alapapo) ṣaaju ki o to fi agbara mu.

The pole-mounted transformer is undergoing testing
Opó - ti a gbe sori ẹrọ ni idanwo
pole mounted transformer test
polu agesin transformer igbeyewo

 

 


 

 

 

5. Awọn sọwedowo Igbala lẹhin

 

 

Lẹhin agbara akọkọ (daradara lati ipo jijin), ṣe:

  • Daju secondary foliteji- Yẹ ki o wa laarin ± 5% ti iye iyasọtọ orukọ.
  • Ṣayẹwo fun awọn n jo- Ṣayẹwo awọn welds, bushings, falifu, awọn wiwọn fun eyikeyi oju epo.
  • Ṣe akiyesi iṣẹ ṣiṣe- Ko si gbigbọn ajeji, ẹfin, didan, tabi ariwo dani.
  • Ṣayẹwo awọn wiwọn- Ipele epo yẹ ki o dide (bi iwọn otutu ṣe n pọ si), iwọn otutu yẹ ki o pọ si laiyara, iwọn titẹ-igbale yẹ ki o ṣafihan titẹ rere.
  • Ohun afetigbọ- Deede jẹ “hum” ti o duro (magnetostriction).

Cracking / yiyo aarin → ṣee ṣe idasilẹ dada lori awọn igbo.

Buzzing pẹlu ohun arcing → asopọ alaimuṣinṣin inu tabi ọran pataki.

Npariwo pupọ → lori ‑ excitation tabi overvoltage.

  • Thermography infurarẹẹdi (aṣayan)- Ṣayẹwo awọn asopọ ebute fun awọn aaye to gbona.

 

 


 

 

 

6. Isẹ ti Yipada ati Awọn ẹrọ Idaabobo

 

 

 

6.1 Gbogbogbo ofin

  • Lo aOhun elo laini laaye (ọpá gbigbona tabi ọpá ibọn)fun awọn ẹrọ apẹrẹ fun iru isẹ. Maṣe ṣiṣẹ pẹlu ọwọ.
  • Yọọ agbara nigbagbogbo ati ilẹ ṣaaju ṣiṣiṣẹ eyikeyi iyipada tabi rọpo awọn fiusi.

 

tap changer of pole mounted transformer

6.2 Iyipada titẹ tẹ ni kia kia

Ṣiṣẹ nikan nigbati a ti mu ẹrọ iyipada kuro.

Ilana:

  • De-agbara ati ilẹ.
  • Disengage titiipa dabaru (ti o ba pese).
  • Yi mimu mimu pada si ipo ti o fẹ (tọka si awo orukọ ati titẹ).
  • Tun-ṣe adaṣe titiipa dabaru.

Eto ile-iṣẹ jẹ deede ipo foliteji ti a ṣe iwọn.

 

6.3 Multiple-foliteji yipada

  • Paapaa iṣẹ-ṣiṣe ti ko ni agbara nikan.
  • Eto ile-iṣẹ nigbagbogbo jẹ ipo foliteji ti o ga julọ.
  • Ti awọn mejeeji tẹ ni kia kia ati ọpọ-foliteji windings wa, rii daju pe iyipada tẹ ni kia kia wa ni ipo ti o han lori apẹrẹ orukọ nigbati iyipada-pupọ-foliteji wa ni ipo afiwera.

 

6.4 Kekere-foliteji Circuit fifọ

  • Be lori ojò ẹgbẹ, ṣiṣẹ pẹlu kan gbona stick.
  • Mu awọn ipo:O= ŠI,C= TIDE,RTuntun =
  • Lẹhin irin ajo: yipada siR, lẹhinna siC.
  • Iyan lefa apọju pajawiri: yi si “EO” fun agbara apọju igba diẹ (≈30% loke iwọn). Gbe lilo rẹ silẹ lati yago fun igbesi aye oluyipada ti o dinku.
  • Imọlẹ ifihan agbara (aṣayan): tan imọlẹ lẹhin apọju iwuwo; tunto nigbati mimu ba wa ni titan siR.

IKILO: Paapaa pẹlu ṣiṣi fifọ, sisọpọ agbara le fa eewu mọnamọna ni awọn ebute ile-iwe giga ti ko ni ilẹ. Nigbagbogbo ilẹ awọn ebute Atẹle ṣaaju ṣiṣe.

circuit breaker of pole mounted transformer

 

6,5 Magnex interrupter

Ti inu epo-immersed overcurrent ati ohun elo iwọn otutu fun ẹgbẹ HV.

Ṣiṣẹ pẹlu ọpá gbigbona:

  • Ṣii: yi mimu mimu si oke (loju aago-aago) si ŠI ipo.
  • Sunmọ: yiyi mimu sisale (ni ọna aago) ni iduroṣinṣin lodi si iduro ni ipo pipade.
  • Tun lẹhin irin ajo: akọkọ lati ŠI, lẹhinna lati PA.

Apọju pajawiri iyan (EO): ni ipo OPEN, tan EO lefa counter-ni ọna aago si EO, lẹhinna sunmọ.

Atọka irin ajo iyan: lẹnsi osan yoo han nigbati o ba ja.

 

6.6 Fuses

Fiusi asopọ alailagbara: agesin ni HV bushing mimọ tabi lori yipada; ṣe aabo lodi si awọn ẹru apọju ati awọn aṣiṣe inu.

Fiusi aropin apa kan-ibiti o lọwọlọwọ: ni jara pẹlu alailagbara-ọna asopọ; fi opin si agbara fun awọn aṣiṣe inu lọwọlọwọ lọwọlọwọ.

Rọpo:

  • Ṣe idanimọ ati ṣatunṣe idi ti iṣiṣẹ ṣaaju ki o to rọpo.
  • Lo iwọn kanna ati awọn abuda.
  • Mu agbara kuro, ilẹ, ojò ṣiṣi (wo Abala 8.7) lati wọle si.

 

Surge arrester of pole mounted transformer

 

6.7 gbaradi arrester

  • Olumudani ita: ṣiṣayẹwo laini-asiwaju ati awọn asopọ ilẹ ti ṣoro (Table torque 3).
  • Amudani MOV inu (aṣayan): epo-immersed; Iwọn otutu omi aropin ko yẹ ki o kọja iwọn 90, iwọn 125 ti o pọju.
  • Ṣaaju ṣiṣe itara tabi awọn idanwo agbara ti o fa, ge asopọ imuni(mejeeji ita ati inu). Atunkun lẹhin idanwo.

 


 

 

 

7. Isẹ ti Bushings, Gauges ati Awọn ẹya ẹrọ

 

 

Ẹrọ

Itọkasi deede / lilo

Aiṣedeede / iṣe

Iwọn titẹ-igbale

Yatọ pẹlu fifuye ati iwọn otutu; rere nigbati o gbona, o le jẹ odi nigbati tutu

Odo igbagbogbo → ṣee ṣe jo, ṣe iwadii

Iwọn ipele epo

Ni iwọn 25, itọka laarin "H" ati "L"; ga soke pẹlu iwọn otutu

Ni isalẹ "L" → fi omi kun ati ṣayẹwo fun awọn n jo

thermometer epo

Oke epo otutu deede Kere ju tabi dogba si iwọn 85; pupa fa ọwọ igbasilẹ max

>Iwọn 95 → ṣayẹwo fifuye, itutu agbaiye, ipo ito

Sisan àtọwọdá / iṣapẹẹrẹ ẹrọ

Sisan tabi ya awọn ayẹwo lati isalẹ ti ojò

Njo → rọpo gasiketi tabi àtọwọdá

Àtọwọdá iderun titẹ aladaaṣe (PRV)

Ṣii nigbati titẹ inu ba kọja aaye ti a ṣeto, lẹhinna tun ṣe

Lẹhin isẹ, ṣe iwadii idi

Oluwari Aṣiṣe Inu (IFD)

Ṣe agbejade asia osan ti kii ṣe atunto nigbati asise arcing inu ba waye

Asia osan ti o han → transformer jẹ aṣiṣe,maṣe fun agbara

IFD ìkìlọ: IFD jẹ afihan wiwo nikan, kii ṣe asopọ itanna kan. Paapa ti IFD ko ba ṣiṣẹ, ẹrọ iyipada le tun jẹ aṣiṣe. Maṣe gbarale rẹ bi ohun elo ilọkuro aabo.

 

Pressure‑vacuum gauge

Iwọn titẹ-igbale

Oil level gauge

Iwọn ipele epo

Oil thermometer

thermometer epo

Drain valve / sampling device

Sisan àtọwọdá / iṣapẹẹrẹ ẹrọ

Radiator

Radiator

IFD

Oluwari Aṣiṣe Inu (IFD)

 

 

 

 


 

 

 

8. Itọju ati Titunṣe

 

 

8.1 Niyanju itọju awọn aaye arin

Àárín

Iṣẹ-ṣiṣe

Oṣooṣu (ojuse wuwo tabi agbegbe lile)

Ayẹwo jijo wiwo, ipele epo, ohun dani, IR thermography

Ni gbogbo oṣu 6

Ayewo kikun, awọn boluti retiighten, awọn imooru mimọ

Lododun

Iṣapẹẹrẹ epo (agbara dielectric, akoonu omi, acidity, DGA)

Ni gbogbo ọdun 3

Idaabobo idabobo, idanwo ipin, idanwo ifosiwewe agbara

Lẹhin aṣiṣe tabi aiṣedeede

Itupalẹ epo lẹsẹkẹsẹ ati awọn idanwo itanna

 

8.2 Ita kun pari

Ti alakoko tabi irin igboro ba farahan, tunṣe lẹsẹkẹsẹ lati yago fun ipata:

  • Iyanrin agbegbe lati yọ ipata ati awọ alaimuṣinṣin.
  • Mọ pẹlu epo (yọ epo, girisi).
  • Waye alakoko egboogi-ipata.
  • Wa awọn ẹwu oke meji (lo awọ ifọwọkan ti olupese ti o ba wa).

 

8.3 Atunṣe ṣiṣan omi

Ijeri jo:

  • Mọ agbegbe ifura, lo talc tabi omi wiwa jo.
  • Ojò titẹ pẹlu afẹfẹ gbigbẹ tabi nitrogen si 3-4 PSIG, duro 1-2 wakati, ṣayẹwo.

Awọn ọna atunṣe:

  • Pinhole tabi weld pelu jo lori ojò: de-energise, sisan, weld (olumulo alurinmorin).
  • Radiator jo: ma ṣe weld (ohun elo tinrin); ropo tabi lo iposii titunṣe ohun elo.
  • Bushing jo: gbiyanju tightening dimole boluti (torque Table 2); ti o ba kuna, ropo gasiketi.
  • Àtọwọdá tabi won jo: ropo gasiketi tabi odidi paati.

 

8.4 Insulating ito itọju

Ilana iṣapẹẹrẹ:

  • De-agbara ati ilẹ.
  • Fi omi ṣan àtọwọdá pẹlu kekere iye ti epo.
  • Ya awọn ayẹwo ni mimọ, eiyan gbẹ, yago fun orun.
  • Pa lẹsẹkẹsẹ ki o firanṣẹ fun itupalẹ.

Awọn ilana gbigba deede (epo erupẹ):

Paramita

Iye itẹwọgba

Dielectric agbara

Ti o tobi ju tabi dogba si 26 kV

Omi akoonu

Kere ju tabi dogba si 35 ppm

Akitiyan

Kere tabi dogba si 0.1 mg KOH/g

Agbara ifosiwewe @ 25 ìyí

Kere ju tabi dọgba si 0.5%

Sisẹ:

  • Lo ẹrọ titẹ àlẹmọ titi agbara dielectric Ti o tobi ju tabi dogba si 26 kV.
  • Maṣe dapọ awọn iru omi inu; titẹ àlẹmọ gbọdọ jẹ ofe ni idoti lati inu omi miiran.

Atunkun:

  • Lo iru kanna ati ami iyasọtọ ti ito.
  • Fa fifa soke laiyara lati isalẹ ti ojò lati yago fun air nyoju.
  • Fọwọsi si laini ti o samisi inu ojò, lẹhinna gba wakati 24 fun afẹfẹ lati sa fun agbara.

 

8.5 Awọn idanwo itanna (igbakọọkan tabi iwadii aisan)

Idanwo

Ọna

Gbigba

Idaabobo idabobo

1000 V tabi 2500 V megger

Ti o tobi ju tabi dọgba si 1 GΩ (gbẹ)

Ipin (TTR)

oluyẹwo TTR

±0.5%

ifosiwewe agbara idabobo

2,5 kV tabi 10 kV Afara

Kere ju tabi dogba si 0.5% @20 ìyí

Yiyi DC resistance

Micro-ohmmeter

Iyapa Kere tabi dogba si 2% laarin awọn ipele

 

8.6 Torque itọnisọna

Table 1 - Ita fasteners

Fastener iru

Yiyipo orukọ (ni-lbs)

Iwọn iyipo (ni-lbs)

3/8 ″ boluti

240

220‑260

Handhole ideri ẹdun

144

129‑158

Boluti band

180

170‑185

gbaradi arrester iṣagbesori ẹdun

420

372‑468

Table 2 - Ita bushing iṣagbesori hardware

Bushing iru

Yiyipo orukọ (ni-lbs)

Torque ibiti o

LV di Mẹta-dimole (ko si oruka dimole), okunrinlada 3/8 ″

60

40‑80

LV mọ (pẹlu oruka dimole), okunrinlada 3/8 inch

120

90‑150

Tanganran LV (pẹlu oruka dimole), okunrinlada 1/2 inch

80

70‑90

Dimole Mẹta ti a mọ HV, okunrinlada 3/8 ″

60

40‑80

HV mọ (pẹlu oruka dimole), okunrinlada 3/8 inch

120

90‑150

HV tanganran

80

70‑90

Table 3 - Ita ebute awọn isopọ

Iru ebute

Yiyipo orukọ (ni-lbs)

Torque ibiti o

HV tanganran bushing oju-boluti

210

180‑240

HV tanganran bushing opin fila

168

156‑180

LV bushing 5/8 ″ Jam nut

600

480‑720

LV bushing 1 ″ Jam nut

600

480‑720

LV bushing 1‑ 1/4 ″ Jam nut

720

600‑840

Ita arrester ila asiwaju

180

162‑198

Ita arrester ilẹ asiwaju

180

162‑198

Table 4 - Awọn ẹya ẹrọ

Ẹya ara ẹrọ

Yiyipo orukọ (ni-lbs)

Torque ibiti o

Awọn boluti fiusi ọna asopọ alailagbara ti o gbe igbo

85

80‑90

Omi ipele plug oju

960

900‑1020

Kun plug

960

900‑1020

Sisan plug

960

900‑1020

Sisan àtọwọdá

600

480‑720

PRV 1/4 ″ NPT

180

160‑200

PRV 1/2 ″ NPT

360

324‑396

Didẹmọ okun didoju (ni paadi ilẹ)

160

140‑180

Tẹ ni kia kia yipada nut iṣagbesori

120

96‑144

Nitori isinmi gasiketi, iyipo wiwọn le jẹ kekere ju ipin lọ. Ma ṣe di pupọju - eewu ti fifọ tabi funmorawon ju.

 

8.7 Nsii awọn ojò transformer

Nikan nigbati Egba pataki(fun apẹẹrẹ ti abẹnu fiusi rirọpo, LV atunto, ti abẹnu yipada titunṣe).

Ilana:

  • De-agbara, ilẹ, yọkuro titẹ (ṣiṣẹ PRV pẹlu ọpá gbigbona – ṣọra fun omi gbona).
  • Mọ agbegbe ni ayika ideri tabi imudani lati ṣe idiwọ titẹsi idoti.
  • Yọ boluti, fara gbe ideri (dabobo gasiketi).
  • Ti omi ba gbọdọ wa ni isalẹ, fifa sinu mimọ, awọn apoti gbigbẹ (maṣe jẹ ki omi kekere silẹ ni isalẹ mojuto/apọn dimole pan – awọn coils gbọdọ wa ni bo).
  • Lakoko iṣẹ: lo mimọ, awọn ideri laisi lint; di awọn irinṣẹ pẹlu awọn okun ailewu lati ṣe idiwọ sisọ silẹ sinu ojò.
  • Maṣe fi ojò silẹ ni ṣiṣi fun diẹ ẹ sii ju wakati 2 lọ.Ti o ba ni idilọwọ, tun di ati kun pẹlu afẹfẹ gbigbẹ tabi nitrogen.
  • Ṣaaju fifi sori ẹrọ ideri, rọpo gasiketi ti bajẹ. Mu boluti to Table 1 iyipo.
  • Ṣatunkun laiyara, gba laaye fun wakati 24, lẹhinna ṣe idanwo idabobo ṣaaju agbara.

 

 


 

 

 

9. Laasigbotitusita Guide

 

 

 

Aisan

Owun to le fa

Iṣe

Atẹle foliteji ti ko tọ

Ipo titẹ ti ko tọ, asopọ HV ti ko tọ, fiusi ti o fẹ

Mu agbara kuro, ṣayẹwo iyipada tẹ ni kia kia, wiwu, rọpo fiusi

Gbigbona pupọ

Apọju, awọn radiators dina, ipele epo kekere, aṣiṣe inu

Din fifuye, awọn radiators mimọ, fi epo kun, epo ayẹwo

PRV ṣiṣẹ

Aaki ti inu, apọju pupọ, iran gaasi

Mu agbara kuro, ṣayẹwo IFD, ṣe DGA – maṣe tun-agbara ni afọju

IFD osan flag han

Ti abẹnu arcing ẹbi

Ayirapada jẹ aṣiṣe – rọpo ẹyọkan

Low idabobo resistance

Ọrinrin ninu epo, idọti bushings, ti ogbo idabobo

Mọ bushings, àlẹmọ tabi ropo epo, gbẹ jade

Ariwo ajeji (kii ṣe deede hum)

Kokoro alaimuṣinṣin, gbigbe yikaka, ayọ ju

Mu agbara kuro, ipin ayẹwo ati lọwọlọwọ ko si fifuye

Epo ipele laiyara silẹ

Jo

Wa ki o tun jo, gbe soke

Iwọn titẹ-igbale nigbagbogbo odo

Igbẹhin ojò ti sọnu

Idanwo jo, tunše, lẹhinna yọ kuro ki o ṣatunkun

 

 


 

 

 

 

 

10. Fifi sori ẹrọ Amunawa ti o jọmọ & Awọn Itọsọna Iṣẹ

 

 

 

Awọn ayirapada ti a fi sori ọpa ṣe iranṣẹ awọn laini pinpin oke, ṣugbọn ọpọlọpọ awọn ohun elo agbara nilo awọn aza iṣagbesori miiran tabi awọn iru apade. Fun eto pipe ti fifi sori ẹrọ iyipada ati awọn iṣe ṣiṣe, wo awọn itọsọna afikun atẹle wọnyi.

 

 

 


 

 

 

11. apoju Parts, Atilẹyin ọja ati nu

 

 

10.1 Ibere ​​apoju awọn ẹya ara

Pesetransformer nọmba ni tẹlentẹle(lori apẹrẹ orukọ), apejuwe apakan, ati opoiye.

Kan si tita olupese tabi iṣẹ imọ ẹrọ.

 

10.2 atilẹyin ọja

Ṣe akiyesi olupese lẹsẹkẹsẹ ti awọn iṣoro ba waye lakoko akoko atilẹyin ọja.

Gbogbo awọn atunṣe atilẹyin ọja gbọdọ jẹ ifọwọsi tabi ṣe nipasẹ olupese.

 

10.3 Idasonu

Sisan gbogbo omi idabobo ṣaaju ki o to yọ oluyipada kuro.

Sọ omi bibajẹ ni ibamu siawọn ilana ayika agbegbe(maṣe tú jade).

Ojò irin, mojuto ati Ejò windings le ti wa ni tunlo.

Omi lati awọn oluyipada atijọ (tẹlẹ-1970s) le ni awọn PCB ninu – mimu bi egbin eewu.

 

 