250 KVA KVA Kekere paadi Amunawa-13.8 / 0.22 KV|Guyana 2025

250 KVA KVA Kekere paadi Amunawa-13.8 / 0.22 KV|Guyana 2025

Orilẹ-ede: Guyana 2024
Agbara: 250 kVA
Foliteji: 13.8-0.22y / 0.127 kV
Ẹya: pẹlu OCTC
Fi ibere ranṣẹ

 

image001

Amunawa ti a gbe paadi: Ilọsiwaju Alagbara, Ni aabo ati idakẹjẹ.

 

 

01 Gbogbogbo

1.1 Project Apejuwe

250 kVA mẹta alakoso pad agesin transformer ti a jišẹ si Guyana ni 2024. Awọn won won agbara ti awọn transformer jẹ 250 kVA pẹlu ONAN itutu. Iwọn giga jẹ 13.8 kV pẹlu ± 2 * 2.5% ibiti o tẹ ni kia kia (NLTC), foliteji kekere jẹ 0.22y / 0.127 kV, wọn ṣẹda ẹgbẹ fekito ti Dyn11.

AwọnPaadi -Ayipada ti a gbe sokejẹ okuta igun-ile ti igbalode, ailewu, ati igbẹkẹle pinpin itanna ipamo. Ti a ṣe ẹrọ fun iṣẹ ṣiṣe ati aabo gbogbo eniyan, iwapọ yii, ilẹ - ipele ipele jẹ apẹrẹ lati lọ silẹ giga{2} ina foliteji si awọn ipele iwulo ti o nilo nipasẹ awọn agbegbe ibugbe, awọn ile-iṣẹ iṣowo, ati awọn ohun elo ile-iṣẹ. Ko dabi ọpá ibile- awọn oluyipada ti a gbe soke, ti paade rẹ ni kikun, tamper - ile irin ti o ni aabo ni aabo ni gbogbo awọn paati laaye, ṣiṣe ni yiyan pipe fun awọn agbegbe nibiti iraye si gbogbo eniyan jẹ ibakcdun. Apẹrẹ ti o lagbara ṣe aabo fun awọn eroja ayika, iparun, ati olubasọrọ lairotẹlẹ, ni idaniloju iṣẹ ti ko ni idilọwọ ati aabo imudara fun agbegbe.

Anfani bọtini kan ti Paadi-Ayipada ti a gbe soke ni ipasẹ to kere julọ ati irọrun ẹwa. O ti wa ni laye ti fi sori ẹrọ lori paadi nja ni ipele ilẹ, ni irọrun dapọ si agbegbe rẹ tabi ti wa ni iboju pẹlu fifi ilẹ. Apẹrẹ yii kii ṣe itọju ifamọra wiwo ti agbegbe nikan ṣugbọn o tun gba awọn atukọ ohun elo laaye lailewu ati irọrun wiwọle fun itọju ati iṣakoso fifuye.

Lati fi agbara mu awọn ilu ti o ni oye pọ si iṣakojọpọ awọn orisun agbara isọdọtun, Paadi{0}Mounted Transformer duro bi olutọpa ipalọlọ, igbẹkẹle, ati alabojuto imunadoko agbara grid, fifi ina mọnamọna han nibiti o nilo{1} ni aabo ati lainidi.

 

 

 

1.2 Imọ pato

250 kVA paadi agesin transformer ni pato iru ati data dì

Jišẹ si
Guyana
Odun
2024
Iru
Paadi agesin transformer
Standard
IEEE Std C57.12.34
Ti won won Agbara
250 kVA
Igbohunsafẹfẹ
60HZ
Ipele
3
Ifunni
Loop
Iwaju
Òkú
Itutu agbaiye
ONAN
Primary Foliteji
13.8kV
Secondary Foliteji
0.22ọdun / 0.127 kV
Ohun elo Yiyi
Ejò
Ẹgbẹ Vector
Dyn11
Ipalara
4%
Iṣẹ ṣiṣe
98.94%
Tẹ Ayipada
NLTC
Ibiti titẹ ni kia kia
±2*2.5%
Ko si Ipadanu Ẹru
0,535 kW
Lori Ipadanu Fifuye
3.56 kW

 

1.3 Yiya

250 kVA paadi agesin transformer aworan atọka yiya ati iwọn.

image003 image005

 

 

02 iṣelọpọ

2.1 mojuto

image007

Paadi yii - transformer ti a fi sori ẹrọ jẹ ẹya iwapọ mẹta{1}} ipele, ipilẹ ẹsẹ mẹta{2} ti a ṣe ti irin silikoni ti a ti lami. Apẹrẹ naa n pese ọna oofa ti o munadoko fun ṣiṣan akọkọ lakoko gbigba odo{4}} ṣiṣan-tẹle lati pada nipasẹ afẹfẹ, ti o fa abajade to lagbara ati aaye-ipo fifipamọ.

 

2.2 Yiyi

Awọn yiyi nlo Ejò fun awọn mejeeji kekere {{0}foliteji ati giga{1} awọn apakan foliteji. Yiyi kekere -foliteji jẹ ti ikole bankanje, pese ipese kukuru axial to dara julọ-agbara iyika ati itujade ooru to munadoko. Lọna miiran, giga -foliteji yiyi n gba apẹrẹ ọgbẹ kan{{7} oniru ọgbẹ pẹlu waya oofa onigun onigun, ti o funni ni ifarada foliteji to ṣe pataki ati irọrun ni iṣeto titan. Àkópọ̀ foil àti Layer -Ọ̀nà ọ̀gbẹ́ yìí máa ń yọrí sí ìsokọ́ra alágbára, dídìpọ̀, tí ó sì ní ìgbẹ́kẹ̀lé gíga.

image009

 

2.3 ojò

image011

Oko ti transformer ti wa ni itumọ ti lati ìwọnba irin, pese a logan ati iye owo{0}}ipade ti o munadoko. O jẹ edidi hermetically lati rii daju pe epo idabobo inu wa ni iyasọtọ lati ọrinrin ati awọn idoti. Apo ita gbangba ti o tọ ni a lo lati koju awọn ipo ayika ti o le, ti o jẹ ki o yẹ fun iṣẹ ita gbangba pipẹ-.

 

2.4 ik Apejọ

Ipejọ ti o kẹhin ṣepọ mojuto {{0} ati - ẹyọ okun sinu ojò irin kekere, eyi ti o kun fun epo dielectric ti a sọ di mimọ. Gbogbo awọn asopọ inu ti wa ni ifipamo, ati awọn paati ita gẹgẹbi iyẹwu ile-iwe keji ti o ni ipin, awọn ifopinsi akọkọ (gẹgẹbi awọn igbonwo tabi awọn igbo), ẹrọ iderun titẹ, ati awọn lugs ti ilẹ ti fi sori ẹrọ. Ojò ti wa ni edidi hermetically, ati pe gbogbo ẹyọ naa ni idanwo to muna lati rii daju iduroṣinṣin iṣiṣẹ, ailewu, ati igbẹkẹle ṣaaju ki o to fọwọsi fun iṣẹ.

image013

 

 

03 Idanwo

Awọn idanwo naa pẹlu awọn nkan ti o ṣe deede: wiwọn resistance yikaka (oṣuwọn aiṣedeede ti o pọju 1.57%), idanwo ipin (iyapa -0.07% si -0.05%), idanwo ibatan-ipin (ti n jẹrisi Dyn11), awọn adanu fifuye ko si ati wiwọn lọwọlọwọ (0.450kW, 0.76%), awọn ipadanu foliteji ati ipadanu agbara 4. 3.93% ikọjujasi, 99.04% ṣiṣe), gbẹyin foliteji igbeyewo (34kV fun HV, 10kV fun LV, 60s kọọkan pẹlu ko si foliteji Collapse), induced foliteji withstand igbeyewo (27.6kV, 150Hz, 48s, ko si foliteji Collapse), jo igbeyewo (20kPa fun 12h resistance) (55.13kV). Gbogbo awọn iye wiwọn pade awọn ibeere gbigba, ti o yori si ipari “Pass” kan. Ijabọ naa wulo nikan pẹlu awọn ibuwọlu ti oludanwo, oludaniloju, ati alakosile; atako gbọdọ wa ni silẹ laarin 7 ọjọ ti ọjà, ati didakọ ti wa ni ko gba ọ laaye lai Scotech ká kọ aiye.

Rara.

Nkan Idanwo

Ẹyọ

Gbigba

Awọn iye

Awọn iye Diwọn

Ipari

1

Awọn wiwọn Resistance

%

Oṣuwọn aibojumu resistance ti o pọju Kere tabi dọgba si 5%

1.57

Kọja

2

Awọn idanwo ipin

%

Iyapa ti ipin foliteji lori titẹ ni akọkọ: Kere tabi dọgba si 0.5%

Asopọmọra aami: Dyn11

-0.07%-0.05%

Kọja

3

ipele{0}}awọn idanwo ibatan

/

Dyn1

Dyn1

Kọja

4

Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun

/

I0 :: pese iye iwọn

0.76%

Kọja

P0: pese iye iwọn (t: 20 iwọn)

0.450kW

Ifarada fun ko si pipadanu ẹru jẹ +10%

/

5

Fifuye adanu impedance foliteji ati ṣiṣe

/

t:85 iwọn

ifarada fun ikọjujasi jẹ ± 7.5%

ifarada fun pipadanu fifuye lapapọ jẹ +6%

/

Kọja

Z%: iye iwọn

3.93%

Pk: iye iwọn

3.354kW

Pt: iye iwọn

3.804 kW

Ṣiṣe ko kere ju 98.94%

99.04%

6

Applied Foliteji Igbeyewo

kV

HV: 34kV 60s

LV: 10kV 60s

Ko si iparun ti foliteji idanwo waye

Kọja

7

Induced Foliteji withstand Igbeyewo

kV

Foliteji ti a lo (KV):2Ur

Ko si iparun ti foliteji idanwo waye

Kọja

Foliteji ti o ni ilọsiwaju (KV): 27.6

Duration(s):48

Igbohunsafẹfẹ (HZ): 150

8

Idanwo jijo

kPa

Ipa titẹ: 20kPA

Ko si jijo ati ki o ko

Bibajẹ

Kọja

Iye akoko: 12h

9

Idiwon Resistance idabobo

GΩ

HV{0}LV si Ilẹ:

46.0

/

LV-HV si Ilẹ:

109.6

HV&LV si Ilẹ:

42.6

10

Idanwo Dielectric Epo

kV

Ti o tobi ju tabi dọgba si 45

55.13

Kọja

 

image015
image017

 

 

04 Iṣakojọpọ ati Sowo

4.1 Iṣakojọpọ

image019

Gbe apo bankanje tin kan sori atẹ rẹ lati bo transformer, fi ohun mimu kun, fi aaye silẹ fun igbale, lẹhinna di apo naa. Nigbamii, dada awọn aabo igun (foomu, ṣiṣu tabi paali ti a tẹ) ni ayika rẹ ki o fi ipari si pẹlu fiimu aabo. Nikẹhin, ṣajọ rẹ sinu apoti onigi kan, eyiti a fun pẹlu orita ati aarin{2}}ti{3}} awọn ami gbigbẹ.

 

4.2 Gbigbe

Oluyipada kikun ti o pejọ ati idanwo ti pese sile fun gbigbe si ibudo ti nlo, Georgetown, Guyana. Gbogbo awọn itagbangba ita ni aabo, ati pe ẹyọ naa wa pẹlu awọn iwe aṣẹ gbigbe to wulo, pẹlu awọn atokọ iṣakojọpọ alaye ati awọn ilana imọ-ẹrọ, lati dẹrọ imukuro aṣa ati ifijiṣẹ ikẹhin.

image021

 

 

05 Ojula ati Lakotan

Ni akojọpọ, paadi yii{0} ti a gbe sori ẹrọ oluyipada n pese ojutu pinpin agbara ti o lagbara ati igbẹkẹle, ti a ṣe fun igbesi aye gigun ati ailewu. Apẹrẹ iṣapeye rẹ, apapọ mojuto oofa ti o munadoko, awọn iyipo bàbà ti o tọ, ati ojò irin ti a fi edidi, ṣe idaniloju iṣẹ ṣiṣe deede ni wiwa awọn agbegbe ita gbangba. A ni igboya pe ẹyọ yii yoo pese awọn ọdun ti wahala-iṣẹ ọfẹ, ṣiṣe ni igbẹkẹle ati dukia ti o niyelori fun awọn amayederun itanna rẹ.

image023

 

Awọn afiwe Gbona: kekere pad agesin transformer, olupese, olupese, owo, iye owo

Fi ibere ranṣẹ