500 kVA paadi Amunawa-13.2 / 0.48 kV|AMẸRIKA 2025
Agbara: 500kVA
Foliteji: 13200GrdY / 7620-480V
Ẹya: DOE 2016

500 kVA paadi ti a gbe sori ẹrọ iyipada{1}} n pese ailewu, mimọ, ati agbara to munadoko pẹlu awọn iṣedede iṣẹ ṣiṣe DOE 2016
01 Gbogbogbo
1.1 Project abẹlẹ
Ise agbese yii jẹ pẹlu ipese 500 kVA mẹta{1} paadi alakoso{2} ti a fi sori ẹrọ transformer pinpin, ti a ṣe apẹrẹ fun awọn ọna ṣiṣe 60 Hz pẹlu foliteji akọkọ ti 13.2 kV GrdY / 7620 V ati foliteji keji ti 480 V. Oluyipada naa ṣe ẹya ONAN (Epo Adayeba Afẹfẹ Adayeba) itutu agbaiye, iṣẹ ifunni lupu ati iṣeto ni aabo ailewu. O ti wa ni itumọ ti pẹlu ẹgbẹ fekito YNd1 ati pe o ni idiwọ ti 5.75%.
Ti ṣelọpọ ni ibamu pẹlu awọn iṣedede ṣiṣe agbara agbara DOE 2016, 500 kva pad mounted transformer n pese iṣẹ giga pẹlu awọn adanu agbara kekere{3}}5.75 kW pipadanu fifuye ati pipadanu fifuye 0.65 kW ni agbara idiyele.
Yi 500 kVA 13.2 kV / 480 V mẹta{3}}paadi alakoso- transformer ti a gbe soke jẹ apẹrẹ fun alabọde{5}}voltage si kekere-pinpin foliteji ni ilu ati igberiko. Awọn ohun elo deede pẹlu:
• Awọn agbegbe ibugbe, ipese agbara fun ina, HVAC, ati awọn ohun elo ile
• Awọn ile-iṣẹ iṣowo gẹgẹbi awọn ọfiisi, awọn ile itaja nla, ati awọn papa itura soobu
• Awọn ohun elo ile-iṣẹ ina, ti nmu agbara kekere si aarin{0}} awọn ohun elo ati ẹrọ
• Awọn ile-iṣẹ bii awọn ile-iwe ati awọn ile-iwosan nilo agbara igbẹkẹle ati ailewu
• Awọn ọna pinpin ipamo, ti a lo ninu awọn nẹtiwọọki kikọ sii loop fun imudara igbẹkẹle ati ailewu
Paadi rẹ- ti a gbe, loop{1} ifunni, ati okú{2} oniru iwaju jẹ ki o dara fun ita gbangba tabi ilẹ{3}} awọn fifi sori ẹrọ ipele nibiti aaye, ailewu, ati iraye si jẹ bọtini.
1.2 Imọ pato
500kVA mẹta paadi paadi agesin transformer sipesifikesonu ati data dì
|
Jišẹ si
America
|
|
Odun
2025
|
|
Iru
Meta alakoso paadi òke transformer
|
|
Standard
IEEE Std C57.12.34-2022
|
|
Ti won won Agbara
500KVA
|
|
Igbohunsafẹfẹ
60HZ
|
|
Ifunni
Loop
|
|
Iwaju
Òkú
|
|
Ipele
Mẹta
|
|
Itutu agbaiye
ONAN
|
|
Primary Foliteji
13,2 kV
|
|
Secondary Foliteji
0,48 kV
|
|
Ẹgbẹ Vector
YNd1
|
|
Ohun elo Yiyi
Aluminiomu
|
|
Ipalara
5.75%
|
|
Ṣiṣe ati awọn adanu
Ọdun 2016
|
|
Tẹ Ayipada
NLTC
|
|
Ibiti titẹ ni kia kia
±2*2.5%
|
|
Ko si Ipadanu Ẹru
5.75 W
|
|
Lori Ipadanu Fifuye
0.65 W
|
|
Awọn ẹya ẹrọ
Standard iṣeto ni
|
1.3 Yiya
500 kva paadi agesin transformer sipesifikesonu ati data dì
![]() |
![]() |
02 iṣelọpọ
2.1 mojuto
Apẹrẹ koko ẹsẹ marun - ṣe idaniloju awọn ọna ṣiṣan oofa fun gbogbo awọn ipele mẹta. Paapaa labẹ odo -awọn ṣiṣan ti o tẹle{3} gẹgẹbi awọn ti o ṣẹlẹ nipasẹ -ila-si{6}}awọn abawọn ilẹ{7} tabi nigba awọn ipo ikojọpọ ti ko ni iwọntunwọnsi, ṣiṣan oofa le ṣàn laisiyonu nipasẹ awọn ẹsẹ ita meji. Eyi dinku aifẹ oofa, dinku iwọn otutu, ati dinku gbigbọn.
Eto ipilẹ yii jẹ anfani ni pataki fun awọn oluyipada ẹgbẹ YNd, bi o ṣe n pese ọna ti o han gbangba fun odo-isun-tẹle nigba ti irawọ{1}} ti o ga ju{2}} didoju ẹgbẹ foliteji ba wa ni ilẹ, nitorinaa nmu iduroṣinṣin itanna ati igbẹkẹle eto ga.
2.2 Yiyi

Yiyi giga {{0}foliteji n lo asopọ irawọ (Y) pẹlu nọmba awọn iyipo ti o ga julọ lati rii daju pinpin foliteji aṣọ ati iṣẹ idabobo to dara julọ. Yiyi kekere -foliteji ti wa ni asopọ ni iṣeto delta (D), ti a ṣe apẹrẹ fun lọwọlọwọ ti o ga ati awọn iyipada diẹ, ni igbagbogbo ni lilo ọna ẹrọ yipo foil fun imudara agbara ẹrọ ati lọwọlọwọ-agbara gbigbe.
Ẹgbẹ fekito YNd1 jẹ lilo wọpọ ni awọn ọna ṣiṣe agbara North America to nilo giga{1}} ati kekere{2}ipinya foliteji, idinku irẹpọ, ati awọn agbara ilẹ.
2.3 ojò
Eleyi 500 kva pad agesin transformer ẹya kan edidi ìwọnba, irin epo ojò pẹlu kan bolted ideri, laimu lagbara darí iyege ati ipata resistance. O kọja idanwo jijo titẹ fun IEC 60076-1 lati rii daju pe iṣẹ ṣiṣe ti epo.
Eto ti awọn imooru ti a fi paadi ti wa ni gbigbe si ẹhin, ti a fi edidi{0}} welded si ojò lati mu itutu afẹfẹ sii lasiko ti o nṣii ṣiṣiṣẹ -ọfẹ. Apẹrẹ iwapọ yii ṣe atilẹyin iṣẹ ṣiṣe igbona iduroṣinṣin ati igbẹkẹle igba pipẹ{3} ni awọn ohun elo agbara mimọ.

2.4 ik Apejọ

Lakoko apejọ ikẹhin, awọn paati bọtini ti wa ni fifi sori ẹrọ lati rii daju iṣẹ ailewu ati igbẹkẹle ti paadi 500 kVA{1}} ẹrọ oluyipada.
Apa giga {{0}foliteji pẹlu 200A mẹfa ti o ya sọtọ igbo ti o ya sọtọ ati igbẹgbẹ didoju H0 kan fun didasilẹ. Apa kekere{4}}faliteji n ṣe ẹya resini meji{5}simẹnti spade{6}iru bushings pẹlu awọn ebute iho mẹfa{{7} fun awọn asopọ okun to ni aabo.
Awọn ohun elo idabobo pẹlu awọn fiusi bayonet mẹta ati lọwọlọwọ -awọn fuses diwọn (CLF) fun iyasọtọ aṣiṣe, pẹlu awọn imuniṣẹ abẹ akọkọ mẹta lati daabobo lodi si awọn iṣẹlẹ apọju.
Awọn paadi ilẹ pẹlu - awọn isopọ iho kan ni a pese ni ẹgbẹ HV ati LV mejeeji lati ṣe atilẹyin didasilẹ aaye ailewu. Gbogbo awọn paati ni a fi sori ẹrọ ni deede lati pade awọn iwulo ati awọn iṣedede iṣẹ.
03 Idanwo

Igbeyewo baraku ati Standard Igbeyewo
1. Idiwọn Resistance Insulation: IEEE C57.12.90-2021 Abala 10.11
2. Awọn idanwo ipin: IEEE C57.12.90-2021 Abala 7; IEEE C57.12.00-2021 Abala 9.1
3. Idanwo Ibaṣepọ Alakoso: IEEE C57.12.90-2021 Abala 6
4. Awọn wiwọn Resistance: IEEE C57.12.90-2021 Abala 5
5. Ko si Awọn ipadanu fifuye ati Ko si fifuye lọwọlọwọ: IEEE C57.12.90-2021 Abala 8, IEEE C57.12.00-2021 Abala 9.3
6. Igbeyewo Idaduro Foliteji ti a fa: IEEE C57.12.90-2021 Abala 10.7
7. Awọn ipadanu fifuye, Foliteji Impedance ati ṣiṣe: IEEE C57.12.90-2021 Abala 9; IEEE C57.12.00-2021 Abala 9.2
8. Ohun elo Foliteji Idanwo: IEEE C57.12.90-2021 Abala 10.6
9. Idanwo Leak Pẹlu Ipa Fun Liquid{1}}Awọn Ayirapada Immersed: IEC60076-1
Awọn abajade Idanwo
|
Rara. |
Nkan Idanwo |
Ẹyọ |
Awọn iye gbigba |
Awọn iye Diwọn |
Ipari |
|
1 |
Awọn wiwọn Resistance |
% |
Iwọn aidogba resistance ti o pọju |
2.29 |
Kọja |
|
2 |
Awọn idanwo ipin |
% |
Iyapa ti ipin foliteji lori titẹ ni akọkọ: Kere tabi dọgba si 0.5% Aami asopọ: YNd1 |
-0.05% ~ -0.03% |
Kọja |
|
3 |
Ipele{0}} igbeyewo ibatan |
/ |
YNd1 |
YNd1 |
Kọja |
|
4 |
Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun |
/ |
I0 :: pese iye iwọn |
0.27% |
Kọja |
|
P0: pese iye iwọn (t: 20 iwọn) |
0.577kW |
||||
|
Ifarada fun ko si pipadanu ẹru jẹ +10% |
/ |
||||
|
5 |
Fifuye adanu impedance foliteji ati ṣiṣe |
/ |
t:85 iwọn ifarada fun ikọjujasi jẹ ± 7.5% ifarada fun pipadanu fifuye lapapọ jẹ +6% |
/ |
Kọja |
|
Z%: iye iwọn |
5.67% |
||||
|
Pk: iye iwọn |
4.032kW |
||||
|
Pt: iye iwọn |
4.609kW |
||||
|
Ṣiṣe ko kere ju 99.35% |
99.41% |
||||
|
6 |
Applied Foliteji Igbeyewo |
kV |
HV: 34kV 60s LV: 10kV 60s |
Ko si iparun ti foliteji idanwo waye |
Kọja |
|
7 |
Induced Foliteji withstand Igbeyewo |
kV |
Foliteji ti a lo (KV):2Ur |
Ko si iparun ti foliteji idanwo waye |
Kọja |
|
Duration(s):48 |
|||||
|
Igbohunsafẹfẹ (HZ): 150 |
|||||
|
8 |
Idanwo jijo |
kPa |
Ipa titẹ: 20kPA |
Ko si jijo ati ki o ko Bibajẹ |
Kọja |
|
Iye akoko: 12h |
|||||
|
9 |
Idiwon Resistance idabobo |
GΩ |
HV{0}LV si Ilẹ: |
21.5 |
/ |
|
LV-HV si Ilẹ: |
51.6 |
||||
|
HV&LV si Ilẹ |
21.2 |
04 Iṣakojọpọ ati Sowo
4.1 Iṣakojọpọ

4.2 Gbigbe
Ṣaaju ki o to ikojọpọ, wọn iwọn ati iwuwo ti transformer, ki o gbero ipa-ọna ti o yago fun awọn ihamọ iga, iwọn ati iwuwo. Lo ibusun kekere{1} tabi awọn oko nla pataki pẹlu agbara to peye.
Mö awọn transformer ká aarin ti walẹ pẹlu awọn ọkọ. Lo irin ikanni ati awọn ọna fifẹ to dara lati ni aabo ipilẹ si oko nla, ti o ba gba laaye. Ṣe aabo ẹrọ oluyipada pẹlu awọn slings tabi awọn ẹwọn nipasẹ awọn ihò gbigbe ti a yan, yago fun awọn paati ẹlẹgẹ gẹgẹbi awọn imooru ati awọn igbo. Tii awọn paati inu ati ki o di gbogbo awọn ilẹkun.
Jeki iyara Kere ju tabi dogba si 60 km / h ati tẹ Kere ju tabi dogba si iwọn 15 lakoko gbigbe. Yago fun awọn gbigbe lojiji ati awọn gbigbọn ti o lagbara. Sọtọ awọn alabobo lati ṣayẹwo isomọ ati da gbigbe duro ni oju ojo lile.
Nigbati o ba gbe soke, tọju awọn igun okun Kere ju tabi dọgba si iwọn 60. Lo awọn ifi kaakiri ti o ba nilo. Nigbagbogbo gbe soke, ati fun awọn sipo laisi awọn lugs oke, lo awọn ọpa gbigbe isalẹ.
05 Ojula ati Lakotan
500 kVA yii, 13.2 kV/480V mẹta{3}}paadi alakoso-iyipada pinpin kaakiri jẹ ẹya ẹya YNd1 ẹgbẹ fekito kan, ti o funni ni alabọde to dara julọ-si{7}} ipinya foliteji kekere ati awọn agbara ilẹ ti a ṣe deede fun awọn eto agbara North America. Apẹrẹ koko ẹsẹ marun-un - n dinku ṣiṣan odo - lẹsẹsẹ, imudara iduroṣinṣin iṣẹ ati idinku gbigbọn.
Ti ni ipese pẹlu ojò epo irin kekere ti o ni edidi ati lẹhin- awọn radiators ti a gbe soke, o pese itutu agbaiye to munadoko (ONAN) ati igbẹkẹle igba pipẹ{{1}. Òkú - Apẹrẹ iwaju ṣe idaniloju ailewu ati itọju to rọrun. Apa giga -ẹgbe foliteji pẹlu 200A mẹfa ti o ya sọtọ bushings ati iyasọtọ H0 didoju bushing, lakoko ti kekere{8}}ẹgbẹ foliteji nlo resini{9}}cast spade{10}}iru awọn bushings fun awọn asopọ okun to ni aabo. Awọn ohun elo idabobo gẹgẹbi awọn fiusi bayonet, lọwọlọwọ{12}}awọn fuses diwọn (CLF), ati awọn imuni iṣẹ abẹ akọkọ n pese iyasọtọ ti o gbẹkẹle ati aabo apọju.
Awọn ohun elo ti o wọpọ pẹlu alabọde{0} si{1} pinpin foliteji kekere ni ilu ati awọn agbegbe igberiko gẹgẹbi awọn agbegbe ibugbe, awọn ile-iṣẹ iṣowo, awọn ohun elo ile-iṣẹ ina, awọn ile-iwe, ati awọn ile-iwosan, nibiti ailewu ati igbẹkẹle ṣe pataki. O tun jẹ daradara-dara fun loop si ipamo{4}}awọn ọna ṣiṣe pinpin ifunni lati jẹki igbẹkẹle ipese.

Awọn afiwe Gbona: 500 kva pad agesin transformer, olupese, olupese, owo, iye owo
You Might Also Like
2500 kVA Paadi Alakoso Mẹta{1}}Ayipada-13.8/0.63*2 k...
3000 kVA Residential Transformer Box-23.9 / 11.95 * ...
1500 kVA paadi Amunawa Amunawa Iye-23.9 / 0.416 Kv|I...
1000 kVA Òkú Iwaju Amunawa-24 / 0,48 kV|AMẸRIKA 2024
750 kVA paadi Amunawa Iye owo-13.8 / 0.22 kV|Guyana ...
1500 kVA paadi Amunawa Amunawa-34.5 / 0.48 kV|AMẸRIK...
Fi ibere ranṣẹ