500 KVA Green Electric Amunawa Apoti-23.9 / 0.22 KV|Ilu Jamaa ni ọdun 2025

500 KVA Green Electric Amunawa Apoti-23.9 / 0.22 KV|Ilu Jamaa ni ọdun 2025

Orilẹ-ede: Ilu Jamaica 2024
Agbara: 500 kVA
Foliteji: 23.9GrdY/13.8-0.22/0.11d kV
Ẹya-ara: pẹlu awọn ifibọ fifọ fifuye
Fi ibere ranṣẹ

 

image001

Ṣeto rẹ ki o gbagbe rẹ. Agbara Ailopin lati Ayipada Paadi Ipele mẹta wa.

 

 

01 Gbogbogbo

1.1 Project Apejuwe

500 kVA mẹta alakoso pad mounted transformer ti a jišẹ si Jamaica ni 2024. Awọn won won agbara ti awọn transformer jẹ 500 kVA pẹlu ONAN itutu. Iwọn giga jẹ 23.9GrdY / 13.8 kV pẹlu ± 2 * 2.5% ibiti o tẹ ni kia kia (NLTC), foliteji kekere jẹ 0.22 / 0.11d kV, wọn ṣẹda ẹgbẹ vector ti YNd11.

Paadi - transformer ti a gbe soke jẹ okuta igun ile ti pinpin ina mọnamọna ti ode oni, ti o npa aafo laarin awọn laini agbara giga{1} ati awọn aini agbara kekere ti awọn ile, awọn iṣowo, ati agbegbe. Ti a ṣe ẹ̀rọ fun igbẹkẹle, aabo, ati isọpọ ẹwa, alagbara wọnyi, irin - awọn ẹya ti o wa ni pipade jẹ ibi gbogbo ati oju ti o ṣe pataki ni awọn ipin, awọn papa iṣowo, ati awọn papa itura ile-iṣẹ.

Ko dabi ọpá ibile - awọn ẹya ti a gbe soke, paadi - awọn transformer ti a gbe soke ti wa ni ipilẹ ni aabo ati fi sori ẹrọ lori kọnkan ni ipele ilẹ. Apẹrẹ yii ṣe pataki aabo gbogbo eniyan pẹlu itọsi-, apade titiipa ti o daabobo awọn paati laaye lati iraye si laigba aṣẹ ati awọn eroja. Apẹrẹ profaili kekere wọn- dinku oju wiwo ati ipa aaye, gbigba wọn laaye lati dapọ mọ inu ala-ilẹ nigba ti o nfi agbara ipele mẹta pataki- tabi ẹyọkan- ranse.

Ti a ṣe lati koju awọn ipo ayika ti o lewu, paadi wa{0}} awọn oluyipada ti a gbe sori jẹ bakanna pẹlu agbara ati iṣẹ itọju kekere-. Wọn ṣe aṣoju idoko-owo bọtini kan ni atunṣe ati awọn amayederun agbara ti o munadoko, ni idaniloju ailewu, iduroṣinṣin, ati ifijiṣẹ igbẹkẹle ti ina ni ibi ti o nilo julọ.

 

 

 

1.2 Imọ pato

500 kVA paadi agesin transformer ni pato iru ati data dì

Jišẹ si
USA
Odun
2024
Iru
Paadi agesin transformer
Standard
IEEE Std C57.12.34-2022
Ti won won Agbara
500 kVA
Igbohunsafẹfẹ
60HZ
Ipele
3
Ifunni
Loop
Iwaju
Òkú
Itutu agbaiye
ONAN
Primary Foliteji
23,9GrdY / 13,8 kV
Secondary Foliteji
0.22 / 0.11d kV
Ohun elo Yiyi
Ejò
Ẹgbẹ Vector
YNd11
Ipalara
5%
Iṣẹ ṣiṣe
99.26%
Tẹ Ayipada
NLTC
Ibiti titẹ ni kia kia
±2*2.5%
Ko si Ipadanu Ẹru
0,725 kW
Lori Ipadanu Fifuye
7.4 kW

 

1.3 Yiya

500 kVA paadi agesin transformer aworan atọka yiya ati iwọn.

image003 image005

 

 

02 iṣelọpọ

2.1 mojuto

image007

Ayipada naa nlo iwapọ mẹta - ipele marun - koko. Apẹrẹ ilọsiwaju yii dinku awọn adanu oofa ati ariwo lakoko imudara iduroṣinṣin iṣiṣẹ, jiṣẹ iṣẹ ti o ga julọ fun awọn iwulo pinpin agbara ode oni.

 

2.2 Yiyi

Paadi - ti a gbe sori ẹrọ n ṣe awọn ẹya ara ẹrọ ti o ni ilọsiwaju idapọmọra windings pẹlu kekere {{1} foil foil ati giga{2}} awọn ikole waya foliteji, mejeeji ṣe ti ga{3}Ejò amuse. Apẹrẹ yii ṣe idaniloju itusilẹ ooru to dara julọ, kukuru giga ju-idaabobo ayika, ati ilo aye to dara julọ. Gbogbo {{7}Eto yiyi Ejò n pese imudara imudara, awọn adanu ti o dinku, ati iṣẹ ṣiṣe ti o gbẹkẹle jakejado igbesi-aye iṣẹ ti transformer.

image009

 

2.3 ojò

image011

Ojò oluyipada ti wa ni ti won ko lati ti o tọ ìwọnba irin, pese logan darí Idaabobo ati ki o munadoko ooru wọbia fun ti abẹnu irinše. Ilana welded rẹ ṣe idaniloju epo pipe - iṣotitọ wiwọn lakoko ti o duro de awọn aapọn ayika. Apẹrẹ ojò ṣafikun awọn imu itutu agbaiye ilana lati mu agbegbe dada dara fun iṣakoso igbona, mimu awọn iwọn otutu iṣiṣẹ iduroṣinṣin jakejado igbesi aye iṣẹ.

 

2.4 ik Apejọ

Ipejọpọ ikẹhin ti paadi{0} ti a gbe sori ẹrọ oluyipada ṣopọ kọnkọn, awọn yikaka, ati awọn paati sinu ojò irin kekere kan ti a fi edidi, eyiti o kun fun omi dielectric. Apejọ naa ti pari nipasẹ fifi awọn bushings, awọn ohun elo aabo, ati awọn ẹya ẹrọ iṣakoso sori ojò ti o ni edidi.

image013

 

 

03 Idanwo

Idanwo ti o tẹle awọn iṣedede IEEE gẹgẹbi IEEE C57.12.00-2021, IEEE Std C57.12.34-2022, ati IEEE C57.12.90-2021. Awọn idanwo laiṣe pẹlu wiwọn resistance yikaka, idanwo ipin foliteji, ipele- Idanwo ibatan, awọn adanu fifuye ko si ati wiwọn lọwọlọwọ ko si, awọn adanu fifuye/foliteji impedance/ idanwo ṣiṣe, idanwo foliteji ti a lo, idanwo ifaramọ foliteji, idanwo jo (fun iru omi-omi), wiwọn idabobo idabobo, ati idanwo dielectric epo.

Rara.

Nkan Idanwo

Ẹyọ

Gbigba

Awọn iye

Iwọn Iwọn

Ipari

1

Awọn wiwọn Resistance

%

Iwọn aidogba resistance ti o pọju

0.44

Kọja

2

Awọn idanwo ipin

%

Iyapa ti ipin foliteji lori titẹ ni akọkọ: Kere tabi dọgba si 0.5%

Aami asopọ: YNd11

-0.04% ~ 0.03%

Kọja

3

ipele{0}}awọn idanwo ibatan

/

YNd11

YNd11

Kọja

4

Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun

/

I0 :: pese iye iwọn

0.38%

Kọja

P0: pese iye iwọn (t: 20 iwọn)

0,6546kW

Ifarada fun ko si pipadanu ẹru jẹ +10%

/

5

Fifuye adanu impedance foliteji ati ṣiṣe

/

t:85 iwọn

ifarada fun ikọjujasi jẹ ± 7.5%

ifarada fun pipadanu fifuye lapapọ jẹ +6%

/

Kọja

Z%: iye iwọn

5.29%

Pk: iye iwọn

7.089kW

Pt: iye iwọn

7,744 kW

Ṣiṣe ko kere ju 99.05%

99.10%

6

Applied Foliteji Igbeyewo

kV

HV: 40kV 60s

LV: 10kV 60s

Ko si iparun ti foliteji idanwo waye

Kọja

7

Induced Foliteji withstand Igbeyewo

kV

Foliteji ti a lo (KV):2Ur

Ko si iparun ti foliteji idanwo waye

Kọja

Foliteji ti o ni ilọsiwaju (KV): 0.44

Iye akoko:40

Igbohunsafẹfẹ (HZ): 150

8

Idanwo jijo

kPa

Ipa titẹ: 20kPA

Ko si jijo ati ki o ko

Bibajẹ

Kọja

Iye akoko: 12h

9

Idiwon Resistance idabobo

GΩ

HV{0}LV si Ilẹ:

OL

/

LV-HV si Ilẹ:

OL

HV&LV si Ilẹ:

OL

10

Idanwo Dielectric Epo

kV

Ti o tobi ju tabi dọgba si 45

58.3

Kọja

 

image015001
image017001

 

 

04 Iṣakojọpọ ati Sowo

4.1 Iṣakojọpọ

image019

Oluyipada paadi ti a fi sori ẹrọ jẹ akopọ ninu apoti onigi ti o lagbara ti a ṣe ti itẹnu, ti o ni ipese pẹlu awọn palleti onigi fun mimu rọrun. Crate naa ṣe afihan awọn aami gbigbe pẹlu awọn itọnisọna mimu (fun apẹẹrẹ, duro ṣinṣin, daabobo lati ipa ati ojo, maṣe ṣe akopọ) ati awọn ami sipesifikesonu, pese aabo to lagbara fun gbigbe irinna gigun-.

 

4.2 Gbigbe

Oluyipada ti a kojọpọ ni awọn apoti itẹnu ti o tọ pẹlu awọn pallet onigi fun iduroṣinṣin, ti gbe nipasẹ okun labẹ awọn ofin CIF si Port Kingston. O ni aabo nipasẹ iṣeduro oju omi lodi si awọn ewu irekọja, ati gbigbe naa tẹle awọn ilana gbigbe ilu okeere, pẹlu gbogbo awọn iwe aṣẹ pataki fun imukuro aṣa, ni idaniloju pe o de ibudo opin irin ajo lailewu ati ni ipo to dara.

image021

 

 

05 Ojula ati Lakotan

Ni akojọpọ, paadi {{0} ti a gbe sori ẹrọ ti n ṣakopọ iṣẹ-ṣiṣe ti o lagbara, iṣẹ ṣiṣe ti o gbẹkẹle, ati iṣẹ ṣiṣe ti o tọ lati pade awọn ibeere ti pinpin itanna ode oni. Ti a ṣe apẹrẹ fun aabo, ṣiṣe, ati iṣẹ igba pipẹ-, o pese ojuutu igbẹkẹle fun awọn ohun elo ati awọn ohun elo ile-iṣẹ. Ṣe alabaṣepọ pẹlu wa fun ohun elo agbara ti o pese didara julọ- ni bayi ati fun awọn ọdun ti mbọ.

image023

 

Awọn afiwe Gbona: Apoti oluyipada itanna alawọ ewe, olupese, olupese, idiyele, idiyele