2000 kVA paadi Amunawa Pipin Amunawa-4.16 / 0.08 kV|AMẸRIKA 2024

2000 kVA paadi Amunawa Pipin Amunawa-4.16 / 0.08 kV|AMẸRIKA 2024

Orilẹ-ede Ifijiṣẹ: USA 2024
Agbara: 2000kVA
Foliteji: 4160-80GrdY/277 V
Ẹya-ara: 600A bushings ti o niiṣe
Fi ibere ranṣẹ

 

 

2000 kVA pad mounted distribution transformer

Agbara Gbẹkẹle, Apẹrẹ Iwapọ - Paadi Gbẹkẹle Rẹ{1}}Ayipada Pinpin Ti A gbe soke

 

 

01 Gbogbogbo

1.1 Project Apejuwe

Ti a fi jiṣẹ si AMẸRIKA ni ọdun 2024, 2000 kVA mẹta yii -paadi alakoso-ti a gbe sori awọn oluyipada pinpin ni a ṣe lati ni ibamu pẹlu IEEE Std C57.12.34-2022 ati ni ibamu pẹlu awọn ilana ṣiṣe agbara agbara DOE 2016. Oluyipada naa ṣe ẹya akọkọ 4.16 kV ati ile-iwe giga 480GrdY/277 V pẹlu ẹgbẹ fekito Dyn1 kan. O nlo awọn iyipo bàbà fun iṣẹ ti o gbẹkẹle ati agbara, itutu agbaiye KNAN fun itusilẹ ooru to munadoko, ati omi ester adayeba FR3 fun aabo ina ti ilọsiwaju ati iduroṣinṣin ayika.

Apẹrẹ naa ṣe ẹya eto ifunni loop ati oku{0}} iwọle iwaju, n ṣe atilẹyin iṣẹ ṣiṣe ailewu ati irọrun fifi sori ẹrọ. O tun pẹlu ko si - oluyipada tẹ ni kia kia pẹlu iwọn ilana foliteji ± 2 × 2.5%. Pẹlu ikọlu ti 5.75%, ko si - pipadanu fifuye ti 1.350 kW, ati ipadanu ẹru ti 16.000 kW, transformer yii n pese iyipada agbara daradara ati iduroṣinṣin fun alabọde{10}} awọn ọna ṣiṣe pinpin foliteji.

Ti a ṣe apẹrẹ lati ba awọn ibeere ohun elo ati awọn eto ile-iṣẹ ṣe loni, paadi wa{0}} awọn transformers pinpin ti a gbe sori nfunni ni iwapọ, apẹrẹ profaili kekere{1} laisi ibajẹ lori ailewu tabi igba pipẹ{2}.

 

 

 

1.2 Imọ pato

2000kVA mẹta paadi paadi agesin transformer sipesifikesonu ati data dì

Jišẹ si
USA
Odun
2024
Iru
Meta alakoso paadi òke transformer
Standard
IEEE Std C57.12.34-2022
Ti won won Agbara
2000 kVA
Igbohunsafẹfẹ
60HZ
Ifunni
Loop
Iwaju
Òkú
Ipele
Mẹta
Itutu agbaiye
KNAN
Insulant olomi
FR3 Epo
Primary Foliteji
4,16 kV
Secondary Foliteji
0,48 kV
Ẹgbẹ Vector
Dyn1
Ohun elo Yiyi
Ejò
Ipalara
5.75%
Ṣiṣe ati adanu Standard
Ọdun 2016
Tẹ Ayipada
NLTC
Ibiti titẹ ni kia kia
±2*2.5%
Ko si Ipadanu Ẹru
1.350 kW
Lori Ipadanu Fifuye
16.000 kW
Awọn ẹya ẹrọ
Standard iṣeto ni

 

 

1.3 Yiya

2000kVA mẹta paadi paadi agesin transformer mefa ati iwuwo awọn alaye

2000 kVA pad mounted distribution transformer drawing 2000 kVA pad mounted distribution transformer nameplate

 

 

02 iṣelọpọ

2.1 mojuto

Gẹgẹbi ọna oofa to ṣe pataki, mojuto transformer n gbe ṣiṣan laarin awọn iyipo akọkọ ati atẹle. Awọn ohun kohun SCOTECH lo awọn laminations irin silikoni pẹlu agbara to dara julọ, ti n mu awọn adanu kekere ṣiṣẹ labẹ iwuwo ṣiṣan giga. Awọn ohun elo ti a ti yan ni iṣọra ṣe idaniloju idahun oofa ti o duro duro ati ṣiṣe gigun - jakejado awọn ẹru oriṣiriṣi.

2000 kVA pad mounted distribution transformer core

 

2.2 Yiyi

Ti a ṣe apẹrẹ fun awọn nẹtiwọọki 4.16 kV, oluyipada 2000 kVA Dyn1 yii nlo awọn iyipo idẹ. Awọn coils HV gba ọpọlọpọ - eto helical Layer pẹlu iwe{5}} waya ti a bo fun idabobo ti o ga julọ. LV bankanje yikaka iyi agbara darí, ooru wọbia, ati eto dede labẹ lemọlemọfún fifuye.

 

2.3 ojò

2000 kVA pad mounted distribution transformer oil tank

Ojò transformer ti wa ni edidi hermetically lati dènà afẹfẹ ati ọrinrin, idabobo epo idabobo lati ifoyina ati idoti. Eyi ṣe ilọsiwaju igbesi aye epo, ṣetọju agbara dielectric, ati idaniloju iduroṣinṣin igba pipẹ ti awọn paati inu.

 

2.4 600AT-Asopọ pẹlu Arrester igbonwo

600A bushing jẹ ibamu pẹlu awọn eto 4.16kV pẹlu fifuye ~ 277A. O n pese iṣẹ iduroṣinṣin pẹlu idabobo igbẹkẹle ati adaṣe fun lilo igba pipẹ{{4}. Sopọ nipasẹ iru asopọ okun T{6}, ẹgbẹ kan so okun agbara nigba ti ekeji so pọ mọ igbonwo-iru imudani iṣẹ abẹ, ti n pese agbara apọju ati aabo monomono.

600A T-Connector with Elbow Arrester

 

2.5 ik Apejọ

2000 kVA pad mounted distribution transformer assembly

Kokoro ati awọn windings ti wa ni apejọ, ni ibamu, ati ni ifipamo pẹlu awọn atilẹyin idabobo to dara. Awọn okun onirin ti wa ni idayatọ ati sopọ si awọn igbo fun alurinmorin nigbamii. Ojò ti o mọtoto ti pese sile fun apejọ. Apakan ti nṣiṣe lọwọ ni a gbe soke sinu ojò, ti o wa ni deede, ilẹ ti wa ni aabo, ati awọn atilẹyin isalẹ ti wa ni tunṣe lati rii daju iduroṣinṣin ati idabobo.

 

03 Idanwo

Igbeyewo baraku ati Standard Igbeyewo

1. Awọn wiwọn Resistance ni ibamu si IEEE C57.12.90-2021 Abala 5

2. Ipele{1}} Idanwo ibatan gẹgẹbi IEEE C57.12.90-2021 Abala 6

3. Awọn idanwo ipin ni ibamu si IEEE C57.12.90-2021 Abala 7

4. Ko si Awọn ipadanu fifuye ati Ko si fifuye lọwọlọwọ gẹgẹbi IEEE C57.12.90-2021 Abala 8

5. Awọn adanu fifuye, Foliteji Impedance ati Iṣiṣẹ ni ibamu si IEEE C57.12.90-2021 Abala 9

6. Igbeyewo Imudaduro Foliteji ti a fa ni ibamu si IEEE C57.12.90-2021 Abala 10.5.1

7. Idanwo Foliteji ti a lo ni ibamu si IEEE C57.12.90-2021 Abala 10.6

8. Idanwo Leak pẹlu Ipa fun Awọn Ayirapada Immersed Liquid Immersed - idanwo jijo ni 15 kPa yoo ṣee ṣe fun wakati 12 laisi jijo. Ko si abuku lailai.

9. Idiwọn Resistance Insulation

10. Oil Dielectric igbeyewo

 

2000 kVA pad mounted distribution transformer testing
2000 kVA pad mounted distribution transformer fat

 

Abajade Idanwo

Rara.

Nkan Idanwo

Ẹyọ

Awọn iye gbigba

Awọn iye Diwọn

Ipari

1

Awọn wiwọn Resistance

%

Iwọn aidogba resistance ti o pọju

0.453

Kọja

2

Awọn idanwo ipin

%

Iyapa ti ipin foliteji lori titẹ ni akọkọ: Kere tabi dọgba si 0.5%

Asopọmọra aami: Dyn1

0.05%-0.10%

Kọja

3

ipele{0}}awọn idanwo ibatan

/

Dyn1

Dyn1

Kọja

4

Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun

%

kW

I0 :: pese iye iwọn

P0: pese iye iwọn

Ifarada fun ko si pipadanu ẹru jẹ +0%

0.10%

1.390

Kọja

5

Fifuye adanu impedance foliteji ati ṣiṣe

%

kW

kW

t:85 iwọn

Z%: iye iwọn

Pk: iye iwọn

Pt: iye iwọn

ifarada fun ikọjujasi jẹ ± 7.5%

ifarada fun pipadanu fifuye lapapọ jẹ +0%

Ṣiṣe ko kere ju 99.51%

5.62%

15.032

16.422

99.52%

Kọja

6

Applied Foliteji Igbeyewo

kV

HV: 40kV 60s

LV: 10kV 60s

Ko si iparun ti foliteji idanwo waye

Kọja

7

Induced Foliteji withstand Igbeyewo

kV

Foliteji ti a lo (KV):

0.960

Iye akoko:40

Igbohunsafẹfẹ (HZ): 180

Ko si iparun ti foliteji idanwo waye

Kọja

8

Idanwo jijo

kPa

Ipa titẹ: 50kPA

Iye akoko: 12h

Ko si jijo ati ki o ko

Bibajẹ

Kọja

9

Idiwon Resistance idabobo

HV{0}LV si Ilẹ:

LV-HV si Ilẹ:

HV&LV si Ilẹ:

2.66

3.25

3.72

/

10

Idanwo Dielectric Epo

kV

Ti o tobi ju tabi dọgba si 40

53.6

Kọja

 

 

04 Iṣakojọpọ ati Sowo

2000 kVA pad mounted distribution transformer packing
2000 kVA pad mounted distribution transformer shipping

05 Ojula ati Lakotan

Scotech's 2000 kVA mẹta{1} ipele paadi ti a gbe sori ẹrọ oluyipada pinpin jẹ ti a ṣe pẹlu iṣọra iṣọra ati awọn sọwedowo didara to muna lati rii daju pe igbẹkẹle, daradara, ati iyipada agbara ailewu fun alabọde{2}} awọn ọna ṣiṣe foliteji. Ti a ṣelọpọ pẹlu pipe -awọn ohun kohun tolera, bankanje{5}egbo LV coils, ati iwe{6}}iyẹfun HV bàbà, o ṣe idaniloju ariwo kekere, idabobo to lagbara, ati igba pipẹ-. Omi irin logan n ṣe aabo fun awọn paati inu si awọn ipaya ati awọn gbigbọn, lakoko ti o ti sopọ Bay -O-Net fuses ati IEEE 386-ibaramu MOV igbonwo imudani ti n pese aabo eto imudara.

Ti a ṣe apẹrẹ lati pade IEEE Std C57.12.34{2}}2022 ati DOE 2016 awọn ajohunše ṣiṣe, paadi mounted transformer pinpin nfunni ni iwapọ, kekere{4}ojuu profaili ti o dara julọ fun iwulo ati lilo ile-iṣẹ. Ni Scotech, a ti pinnu lati jiṣẹ oke{5}} paadi ti o gbe awọn ayirapada pinpin didara ti o ṣe pataki aabo, iṣẹ ṣiṣe, ati iduroṣinṣin ayika - mimu awọn iṣẹ rẹ ṣiṣẹ pẹlu igboiya.

2000kVA 416kV6  pad mounted distribution transformer

 

Awọn afiwe Gbona: Amunawa pinpin pad ti a gbe sori ẹrọ, olupilẹṣẹ, olupese, idiyele, idiyele

Fi ibere ranṣẹ