1000 kVA paadi Oke Ayirapada Fun tita-4.16 / 0.48 kV|AMẸRIKA 2025

1000 kVA paadi Oke Ayirapada Fun tita-4.16 / 0.48 kV|AMẸRIKA 2025

Orilẹ-ede: Amẹrika 2025
Agbara: 1000 kVA
Foliteji: 4.16D-0.48Y / 0.277 kV
Ẹya: pẹlu Schrader àtọwọdá
Fi ibere ranṣẹ

 

 

pad mount transformers for sale

Awọn paadi ipele mẹta{0}{1} ti a gbe sori ẹrọ iyipada: Ṣasiwaju akoko tuntun ti agbara oye, ti n tan imọlẹ gbogbo igun.

 

01 Gbogbogbo

1.1 Akopọ & Awọn ibeere alabara

Ni 2025, a pese 1000 kVA mẹta -paadi alakoso{3}} transformer (4.16 kV Delta / 0.48Y/0.277 kV, Dyn1, ONAN, ± 2×2.4% NLTC) si ọja AMẸRIKA.
Eto imọ-ẹrọ jẹ boṣewa, ṣugbọn awọn italaya lẹhin awọn ibeere alabara ko rọrun lati rọrun.

Key Onibara irora Points

 

1. Ailewu ni awọn agbegbe ti o kun tabi ti a fi pamọ

Paadi - awọn oluyipada ti a gbe sori nigbagbogbo joko ni awọn aaye wiwọ{1} lẹgbẹ awọn oju opopona, awọn iwaju ile itaja, awọn aaye gbigbe, tabi awọn aaye ohun elo kekere. Awọn alabara nilo ẹyọ kan ti o duro lailewu laibikita ẹniti o rin nipasẹ tabi ẹniti o ṣe itọju. Ko si giga ti o fara han -foliteji, ko si olubasọrọ lairotẹlẹ, ko si iyanilẹnu.

2. Gígùn- Àkókò Àkókò Lodi si Oju-ọjọ ati Ayika

Ojo, ọriniinitutu, kurukuru iyọ, awọn iyipada iwọn otutu ojiji -ọdun lẹhin ọdun, ibi ipamọ naa dojukọ wahala nigbagbogbo. Awọn alabara fẹ oluyipada kan ti kii yoo baje, jo, tabi ibajẹ, ati pe o tọju awọn paati inu ni aabo fun awọn ewadun.

3. Idurosinsin isẹ Labẹ Adalu Load Awọn ipo

Ilu ati awọn akoj ti iṣowo ṣọwọn huwa ni asọtẹlẹ. Awọn oke ibugbe ni alẹ, awọn oke iṣowo lakoko ọsan, awọn iṣẹ-ṣiṣe ile-iṣẹ lẹẹkọọkan{1} gbogbo wọn beere fun ẹrọ iyipada ti o duro ni iwọntunwọnsi, yago fun igbona pupọ, ati fifun foliteji deede laisi idilọwọ.

4. Iye owo igbesi aye kekere Pẹlu Itọju to kere julọ

Awọn adanu agbara kojọpọ, ati pe itọju igbagbogbo kii ṣe olowo poku. Awọn onibara n wa transformer kan ti "nṣiṣẹ ni idakẹjẹ ni abẹlẹ," pẹlu awọn adanu kekere, ibojuwo rọrun, ati akoko idaduro diẹ {{1} lakoko ti o wa ni ibamu ni kikun pẹlu awọn iṣedede IEEE / ANSI fun iṣọpọ ohun elo irọrun.

 

1.2 Ojutu wa

 

Loop-Ifunni + Òkú-Apẹrẹ Titipade ni kikun iwaju

Fun iṣẹ akanṣe yii, ailewu kii ṣe ibeere nikan-o jẹ aaye ibẹrẹ.
A yan aloop{0}}eto ifunnipelu aòkú-iwaju, ètò tí a fi pa mọ́, ọkan ninu awọn atunto ailewu julọ fun ilu ode oni ati awọn nẹtiwọọki pinpin iṣowo.

Ko si awọn ebute ti o han. Ko si eewu olubasọrọ lairotẹlẹ. Ko si ailagbara si ojo, eruku, tabi ọwọ iyanilenu. Ni wiwo HV duro ni edidi inu yara lile kan, fifun awọn oniṣẹ ni igboya paapaa ni ọpọlọpọ eniyan tabi aaye- awọn agbegbe to lopin. Àti pé pẹ̀lú ìrọ̀lẹ́ ìtọ́kasí -, abala kan nínú nẹ́tíwọ́kì náà lè wà ní àbójútó láìsé gbogbo ẹ̀rọ - ìjábọ̀ díẹ̀, àwọn ìṣiṣẹ́ dídara, àti ìfisíni mọ́ lápapọ̀.

Eyi ni awọn ohun elo apẹrẹ nigbagbogbo yan nigbati igbẹkẹle ati aabo gbogbo eniyan gbọdọ wa ni akọkọ.

 

Yiyi Aluminiomu + Fíìlì LV + Giga-Iṣe Pipadanu Iṣẹ ṣiṣe

A tun ṣe iṣapeye fun ohun ti o ṣe pataki fun igba pipẹ-: iye owo iṣẹ.
Awọn transformer nloaluminiomu windingslori HV ẹgbẹ atikikun -ikole bankanjení ẹ̀gbẹ́ LV{0}}ìwọ̀n wúwo, tó gbéṣẹ́, àti agbára ẹ̀rọ tó lágbára lábẹ́ àwọn ipò gidi{1} ayé.

Ati ṣiṣe naa sọrọ fun ararẹ.
Pẹlu1.3 kW ko si - pipadanu fifuyeati6,94 kW fifuye pipadanu, Ẹyọ naa n pese iṣẹ giga ti o gbẹkẹle pẹlu idinku agbara egbin. Awọn owo kekere, aapọn ooru dinku, ati igbesi aye idabobo to gun. O jẹ iru ṣiṣe ti o sanwo ni idakẹjẹ ni gbogbo ọdun kan.

 

Abojuto okeerẹ & Package Idaabobo

Ailewu isẹ tun tumo si mọ ohun ti n ṣẹlẹ inu awọn ojò.
Ẹka yii wa ni ipese pẹlu ibojuwo pipe ati package aabo, pẹlu:

Iwọn ipele epo

Titẹ thermometer

Ipa - Iwọn igbale

Titẹ iderun àtọwọdá

Dekun titẹ iderun ẹrọ

Gas iṣapẹẹrẹ ibudo

Papọ, awọn paati wọnyi ṣiṣẹ bi eto ikilọ kutukutu{0}}rọrun, igbẹkẹle, ati irọrun fun awọn onimọ-ẹrọ aaye lati tumọ. Wọn ṣe iranlọwọ lati rii igbega iwọn otutu, gaasi idẹkùn, titẹ ajeji, tabi pipadanu epo ni iwo kan, imudara akoko idahun nigbati akoj naa ba ni wahala.

 

Apẹrẹ & Idanwo fun IEEE C57.12.34-2022

Gbogbo bọtini sipesifikesonu{{0} lati agbara ẹrọ si igbega iwọn otutu ati iṣẹ dielectric{1} tẹleIEEE C57.12.34-2022, òṣùwọ̀n ìtumọ̀ fún paadi Àríwá Amẹ́ríkà{0}}

Eyi ni idaniloju pe ẹyọ naa ṣepọ laisiyonu pẹlu awọn ireti ohun elo kọja agbegbe naa.
Apẹrẹ ti o ni ibamu pẹlu akoj AMẸRIKA, ti a ṣe fun igbẹkẹle, iṣẹ igba pipẹ-.

 

1.3 Imọ Specification

1000 KVA paadi agesin transformer iru ati data dì

Jišẹ si
America
Odun
2025
Iru
Paadi agesin transformer
Standard
IEEE StdC57.12.34-2022
Ti won won Agbara
1000KVA
Igbohunsafẹfẹ
60HZ
Ipele
3
Ifunni
Loop
Iwaju
Òkú
Itutu agbaiye
ONAN
Primary Foliteji
4.16D kV
Secondary Foliteji
0.48Y / 0.277 kV
Ohun elo Yiyi
Aluminiomu
Angular nipo
Dyn1
Ipalara
5.75%
Tẹ Ayipada
NLTC
Ibiti titẹ ni kia kia
±2*2.4%
Ko si Ipadanu Ẹru
1.3kW
Lori Ipadanu Fifuye
6,94 kW
Awọn ẹya ẹrọ
Standard iṣeto ni

 

1.4 Yiya

1000 kVA paadi agesin transformer aworan atọka yiya ati iwọn.

3 phase transformer wiring diagram circuit diagram of a transformer

 

 

02 iṣelọpọ

2.1 mojuto

Ẹ̀ka ọ̀wọ̀n mẹ́tẹ̀ẹ̀ta- n pèsè àtìlẹ́yìn òmìnira fún ìpele kọ̀ọ̀kan, tí ń gbani láàyè fún pípín ẹrù ìwọ̀ntúnwọ̀nsì púpọ̀ síi jákèjádò òpó kọ̀ọ̀kan nígbà iṣẹ́. Eyi dinku kikọlu oofa ati awọn adanu agbara, ni idaniloju iṣelọpọ agbara iduroṣinṣin. Apẹrẹ mojuto ṣafikun Circuit oofa pipade kan ti o dinku itẹlọrun oofa ati awọn adanu ni pataki, imudara ṣiṣe gbogbogbo ti gbigbe agbara ni oluyipada. Lilo awọn iwe ohun alumọni ohun alumọni pẹlu agbara giga bi ohun elo mojuto kii ṣe imudara iṣiṣẹ eletiriki nikan ṣugbọn o tun dinku awọn adanu lọwọlọwọ eddy ati alapapo, ni idaniloju iṣẹ ṣiṣe ti ohun elo.

core type 3 phase transformer

 

2.2 Yiyi

aluminum wire

Kekere-Foili Yiyi

Ilana: Irin bankanje mu lọwọlọwọ agbara ati ki o din adanu.

Idabobo: Ṣe ilọsiwaju iduroṣinṣin ni lilo kekere{{0}voltage.

Ooru Ifakalẹ: Eedi daradara pinpin ooru.

EMI: Din itanna kikọlu.

Giga -Wire Wireti Foliteji

Ikole: Nlo waya aluminiomu fun gbigbejade giga - daradara.

Idabobo: Aabo lodi si kukuru iyika.

Fifuye ni irọrun: Adapts si orisirisi èyà.

Gbigbọn Resistance: Ṣe idaniloju igbẹkẹle labẹ wahala.

 

2.3 ojò

Ṣiṣe deede ti irin nipa lilo gige laser tabi imọ-ẹrọ gige pilasima. Awọn irin awo ti wa ni marun-ati akoso, ati awọn atunse ti deede ti wa ni idaniloju nipa laifọwọyi ẹrọ. Gba ilana alurinmorin boṣewa giga, gẹgẹbi alurinmorin laifọwọyi tabi alurinmorin arc arc afọwọṣe, lati rii daju agbara ati wiwọ ti weld. Gbogbo ojò ti wa ni iyanrin lati yọkuro ohun elo afẹfẹ ati lẹhinna fun sokiri pẹlu alakoko ati ẹwu oke lati jẹki resistance ipata. Ni awọn agbegbe pataki, gbona -dip galvanizing tabi awọn miiran to ti ni ilọsiwaju egboogi - ibora le tun lo.

welded tanks for oil storage

2.3 ik Apejọ

 

1000kva pad mount transformer price

 

Akọkọ Unit fifi sori: Gbe ẹrọ oluyipada soke, so awọn laini foliteji giga ati kekere, ati ṣayẹwo ilẹ.

Awọn isopọ onirin: So awọn ebute foliteji giga ati kekere ati ṣayẹwo aworan atọka.

Awọn ẹya ẹrọ ati Itutu: Fi sori ẹrọ eto itutu agbaiye ati awọn ẹya ẹrọ pataki.

Ibẹrẹ ati N ṣatunṣe aṣiṣe: Ṣiṣe ayẹwo ni kikun, agbara lori idanwo, ati awọn atunṣe igbasilẹ.

2.4 irinše

202501151329IMG3788
Fusing bayonet w/ISO awọn ọna asopọ
202501151329IMG3790
4 Ipo Fifuye Bireki yipada
202501151329IMG3793
De-oluyipada tẹ ni kia kia
202501151330IMG3796
200A Wells ati awọn ifibọ HV Bushing
202501151330IMG3801
Abojuto & Awọn ẹya ẹrọ Idaabobo
202501151330IMG3809
6-Iho Spades LV Bushing

 

03 Idanwo

Rara.

Nkan Idanwo

Ẹyọ

Awọn iye gbigba

Awọn iye Diwọn

Ipari

1

Awọn wiwọn Resistance

%

Iwọn aidogba resistance ti o pọju

2.93

Kọja

2

Awọn idanwo ipin

%

Iyapa ti ipin foliteji lori titẹ ni akọkọ: Kere tabi dọgba si 0.5%

-0.13

Kọja

3

Ipele{0}} igbeyewo ibatan

/

Dyn1

Dyn1

Kọja

4

Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun

%

I0 :   pese iye iwọn

0.43

Kọja

kW

P0Pese iye iwọn (diwọn 85)

1.289

/

Ifarada fun ko si pipadanu fifuye jẹ ± 10%

/

5

Awọn adanu fifuye, foliteji ikọlu, awọn adanu lapapọ ati ṣiṣe

/

t:85 iwọn

ifarada fun ikọjujasi jẹ ± 7.5%

Ifarada fun pipadanu fifuye lapapọ jẹ ± 6%

/

Kọja

%

Z%: iye iwọn

5.42

kW

Pk: iye iwọn

7.223

kW

Pt: iye iwọn

8.451

%

Ṣiṣe ko kere ju 99.43%

99.43

6

Applied Foliteji Igbeyewo

/

HV: 19kV 60s

LV: 10kV 60s

Ko si iparun ti foliteji idanwo waye

Kọja

7

Induced Foliteji withstand Igbeyewo

/

Applied foliteji (KV): 0,96

Ko si iparun ti foliteji idanwo waye

Kọja

Iye akoko: 48

Igbohunsafẹfẹ (HZ): 150

8

Idiwon Resistance idabobo

HV{0}LV si Ilẹ:

20.8

/

LV-HV si Ilẹ:

31.0

HV&LV si Ilẹ:

19.4

9

Idanwo jijo

/

Ipa titẹ: 20kPA

Ko si jijo ati ki o ko

Bibajẹ

Kọja

Iye akoko: 12h

10

Idanwo epo

kV

Dielectric Agbara

54.9

Kọja

mg/kg

Ọrinrin akoonu

9.7

%

Okunfa ifasilẹ

0.00227

mg/kg

Furan Analysis

/

/

Gaasi Chromatography Analysis

/

 

image015
image017

 

 

04 Iṣakojọpọ ati Sowo

1000kva pad mounted transformer cost
1000kva pad mount transformer manufacturer

 

05 Ojula ati Lakotan

Ni akojọpọ, ẹrọ oluyipada{0}mẹta wa{0}}{1} ti a gbe soke nfunni ni iṣẹ ṣiṣe to lagbara ati awọn ojutu pinpin agbara igbẹkẹle fun awọn ohun elo lọpọlọpọ. Pẹlu apẹrẹ iwapọ rẹ, fifi sori irọrun, ati awọn ẹya aabo to ti ni ilọsiwaju, o jẹ yiyan pipe fun awọn ọna itanna igbalode ti o nilo ṣiṣe ati agbara. A ti pinnu lati pese awọn ọja to gaju- ti o baamu awọn iwulo idagbasoke ti awọn alabara wa, ni idaniloju iṣẹ ṣiṣe to dara julọ ati itẹlọrun. Yan awọn oluyipada wa fun awọn iwulo agbara rẹ ki o ni iriri iyatọ ninu didara ati iṣẹ.

1000kva pad mount transformer supplier

 

Awọn afiwe Gbona: Awọn oluyipada pad fun tita, olupese, olupese, idiyele, idiyele