300 kVA paadi Amunawa Amunawa-12 / 0.208 kV|Ilu Jamaa ni ọdun 2025

300 kVA paadi Amunawa Amunawa-12 / 0.208 kV|Ilu Jamaa ni ọdun 2025

Orilẹ-ede: Ilu Jamaica 2025
Agbara: 300 kVA
Foliteji: 12GrdY/6.928-0.208/0.12 kV
ẹya: pẹlu igbonwo iru gbaradi arrester
Fi ibere ranṣẹ

 

 

300 kva pad mounted transformer

Foliteji igbagbogbo, ti ko ni idilọwọ -Meta{1}}ayipada paadi ipele ipele, n ṣe idaniloju igbẹkẹle lojoojumọ.

 

 

01 Gbogbogbo

1.1 Project Apejuwe

300 kVA three phase pad mounted transformer ti a fi jiṣẹ si Ilu Jamaica ni ọdun 2025. Agbara iyipada ti transformer jẹ 300 kVA pẹlu itutu ONAN. Foliteji akọkọ jẹ 12GrdY / 6.928 kV pẹlu ± 2 * 2.5% ibiti o tẹ ni kia kia (NLTC), foliteji keji jẹ 0.208 / 0.12 kV, wọn ṣẹda ẹgbẹ fekito ti YNyn0.

Onibara wa, ohun elo idalẹnu ilu ti n ṣiṣẹ ni agbegbe ti o dagba ni iyara ni US Pacific Northwest, n gba 300 kVA, 12kV mẹta{4}}paadi ipele{{5}ti a gbe sori ẹrọ transformer fun ipilẹṣẹ isọdọtun grid pataki kan. Ẹ̀ka yìí ni a ó fi sínú àárín àgbègbè oníṣòwò tuntun kan, tí ó ń ṣe gẹ́gẹ́ bí ibi ìpínpinpin agbára àkọ́kọ́ fún àkópọ̀ àwọn ilé-iṣẹ́ ìtajà, àwọn ọ́fíìsì, àti àwọn ilé gbígbé ìdílé púpọ̀-.

Ise agbese na ṣafihan awọn italaya pataki mẹta:

Resilience si Awọn Wahala Ayika Kan pato:Ipo naa ni iriri iṣẹ ṣiṣe jigijigi pataki ati iṣubu igba otutu otutu. Oluyipada naa gbọdọ jẹ imọ-ẹrọ lati koju awọn ipa agbegbe jigijigi ati ẹru yinyin ilẹ ti o to 150 PSF.

Ibamu ti ko ni adehun:Ibamu ni kikun pẹlu IEEE C57.12.20 ati C57.12.90 awọn ajohunše jẹ dandan. Apẹrẹ gbọdọ tun pade awọn pato ohun elo agbegbe fun iduro lọwọlọwọ lọwọlọwọ ati inrush aropin lọwọlọwọ lati rii daju interoperability grid.

Ijọpọ Ẹwa ni Ilẹ-ilẹ Ilu kan:Ti o wa laarin oju opopona-oju opopona, apade transformer nilo profaili kekere{1}, apẹrẹ ti a ṣe itọju ti ayaworan pẹlu ibaramu awọ aṣa ati ohun -awọn ẹya ti o nfa lati dinku ipa wiwo ati ohun orin.

 

 

 

1.2 Imọ pato

300 kVA paadi agesin transformer iru ati data dì

Jišẹ si
Ilu Jamaica
Odun
2025
Iru
Paadi agesin transformer
Standard
IEEE StdC57.12.34-2022
Ti won won Agbara
300 kVA
Igbohunsafẹfẹ
50HZ
Ipele
3
Ifunni
Loop
Iwaju
Òkú
Itutu agbaiye
ONAN
Primary Foliteji
12GrdY/6.928 kV
Secondary Foliteji
0,208 / 0,12 kV
Ohun elo Yiyi
Ejò
Angular nipo
YNyn0
Ipalara
5.5%
Tẹ Ayipada
NLTC
Ibiti titẹ ni kia kia
±2*2.5%
Ko si Ipadanu Ẹru
0.53kW
Lori Ipadanu Fifuye
4,755 kW
Awọn ẹya ẹrọ
Standard iṣeto ni

 

 

1.3 Yiya

300 kVA paadi agesin transformer aworan atọka yiya ati iwọn.

300 kva pad mounted transformer diagram 300 kva pad mounted transformer nameplate

 

 

02 iṣelọpọ

2.1 mojuto

 

Oluyipada mẹtẹẹta - ipele marun - alapapọ mojuto transformer ti wa ni itumọ ti pẹlu awọn iwe irin silikoni tolera ni pipe, gige ko si{2}} adanu fifuye nipasẹ 15% ati ṣiṣe aṣeyọri ju 99% lọ. Ṣiṣan oofa rẹ ti o ni iwọntunwọnsi dinku hysteresis ati awọn adanu lọwọlọwọ eddy nipasẹ 10–20%, lakoko ti ariwo iṣẹ ti dinku nipasẹ 5–10 dB(A). Apẹrẹ ti o lagbara mu agbara ẹrọ ati iṣẹ ṣiṣe igbona pọ si, mimu iwọn otutu dide ni isalẹ 65 K labẹ ẹru kikun fun igbesi aye iṣẹ ti o gbooro sii.

excellent magnetic core transformer

 

2.2 Yiyi

thick foil conductors

Amunawa yi nlo atunto yiyipo arabara, ni apapọ adapo giga -foliteji (HV) ti o ga pẹlu yiyi foili kekere -foliteji (LV). Yiyi HV naa nlo okun waya ti o ya sọtọ, eyiti o mu agbara idabobo pọ si ati dinku kikankikan aaye ina nipasẹ isunmọ 15–20%, ni idaniloju iṣẹ ṣiṣe ti o gbẹkẹle labẹ awọn ipo foliteji giga{{5}. Nibayi, yiyi LV nlo bankanje conductive ti o nipọn, imudara pinpin lọwọlọwọ ati jijẹ kukuru{7}} agbara iyika duro pẹlu iwọn 25% ni akawe si awọn yikaka waya ti aṣa. Apẹrẹ yii tun mu itusilẹ ooru pọ si, idinku iwọn otutu hotspot nipasẹ iwọn 10-15 ati irọrun fifi sori ẹrọ ati awọn ilana itọju.

 

2.3 ojò

A ṣe ojò epo lati giga - irin agbara lati jẹki idiwọ ipata rẹ ati titẹ -agbara gbigbe. Ilana naa bẹrẹ pẹlu titẹ deede lati ṣe apẹrẹ awọn apẹrẹ irin, atẹle nipa lilo alurinmorin aabo CO2 lati so awọn paati ni aabo, idilọwọ awọn dojuijako tabi abuku. Lẹhin alurinmorin, awọn itọju edidi ni a lo lati ṣe idiwọ jijo epo transformer, ati pe awọn atako - ipata ni a lo fun aabo ipata. Nikẹhin, ojò epo naa gba awọn ayewo didara ti o muna, pẹlu idanwo titẹ ati wiwa jijo, lati rii daju aabo ati iṣẹ rẹ.

transformer oil leakage

 

2.4 ik Apejọ

electrical wiring

Awọn fifi sori ẹrọ lori {{0} ojula ti wa ni ṣiṣan sinu awọn igbesẹ bọtini: lẹhin ti apakan ti nṣiṣe lọwọ ti gbe soke sinu ojò epo, awọn ọna foliteji giga ati kekere ni a ti sopọ pẹlu lilo awọn irinṣẹ iyipo ti iwọn lati rii daju pe iduroṣinṣin ebute. Awọn ẹya ẹrọ to ṣe pataki{{2} pẹlu awọn fiusi bayonet, thermometer, iwọn ipele epo, ati awọn igbo{3} ni a fi sori ẹrọ lati jẹ ki abojuto eto ati aabo ṣiṣẹ. Ni atẹle wiwi itanna fun sikematiki, ilana naa pari pẹlu kikun igbale ti epo idabobo, iyọrisi aaye ìri ni isalẹ -40 iwọn lati ni aabo idabobo to dara julọ ati iṣẹ itutu agba pipẹ.

 

 

03 Idanwo

Rara.

Nkan Idanwo

Ẹyọ

Awọn iye gbigba

Iwọn Iwọn

Ipari

1

Awọn wiwọn Resistance

%

Oṣuwọn aibojumu resistance ti o pọju Kere tabi dọgba si 5%

1.64

Kọja

2

Awọn idanwo ipin

%

Iyapa ti ipin foliteji lori titẹ ni akọkọ: Kere tabi dọgba si 0.5%

Aami asopọ: YNyn0

-0.03%~0.06%

Kọja

3

Ipele{0}} igbeyewo ibatan

/

YNyn0

YNyn0

Kọja

4

Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun

%

kW

Ni iwọn 20

I0 :: pese iye iwọn

P0: pese iye iwọn

0.87%

0.463

Kọja

5

Fifuye adanu impedance foliteji ati ṣiṣe

%

kW

kW

t:85 iwọn

Z%: iye iwọn

Pk: iye iwọn

Pt: iye iwọn

ifarada fun ikọjujasi jẹ ± 7.5%

Ṣiṣe ko kere ju 98.94%

5.50%

4.662

5.125

99.00%

Kọja

6

Applied Foliteji Igbeyewo

kV

HV: 40kV 60s

LV: 10kV 60s

Ko si iparun ti foliteji idanwo waye

Kọja

7

Induced Foliteji withstand Igbeyewo

kV

Foliteji ti a lo (KV):

2 Úrì

Iye akoko:40

Igbohunsafẹfẹ (HZ): 150

Ko si iparun ti foliteji idanwo waye

Kọja

8

Idanwo jijo

kPa

Ipa titẹ: 20kPA

Iye akoko: 12h

Ko si jijo ati ki o ko

Bibajẹ

Kọja

9

Idiwon Resistance idabobo

GΩ

HV{0}LV si Ilẹ:

LV-HV si Ilẹ:

HV&LV si Ilẹ:

26.9

28.7

22.8

Kọja

10

Idanwo Dielectric Epo

kV

Ti o tobi ju tabi dọgba si 45

57.56

Kọja

 

300kva transformer Applied Voltage Test
300kva transformer Ratio Tests

 

 

04 Iṣakojọpọ ati Sowo

4.1 Iṣakojọpọ

Oluyipada naa wa ni ifipamo laarin fireemu irin ti a fikun ati aabo nipasẹ awọn panẹli irin ti o nipọn 0.8mm. Awọn ohun elo to ṣe pataki jẹ aibikita nipa lilo awọn biraketi iwuwo giga -iwuwo polyethylene (HDPE), idinku gbigbọn{3}} eewu ibajẹ ti o fa diẹ sii ju 30%. Ẹyọ naa ti wa ni igbale{6}} pẹlu 0.12mm egboogi - film condensation ati ki o kojọpọ sinu apoti onigi ti ko ni oju ojo, ṣiṣe aabo IP55 fun to oṣu mejila ti ipamọ ita. Eto iṣakojọpọ yii ti ṣe afihan ibajẹ 99.8% kan -oṣuwọn ọfẹ lakoko gbigbe ni idanwo ISTA 3A ti o ni idiwọn.

12kv transformer package

 

4.2 Gbigbe

Kingston port

Ti a ṣe apẹrẹ fun ẹru ọkọ oju omi okun, ẹrọ oluyipada - ipele ipele mẹta - transformer ti wa ni ifipamo laarin apoti ti o ni ifọwọsi pẹlu lilo irin fifẹ mẹrin{2}} ati 3{9}} awọn aabo eti. Ẹyọ naa jẹ abojuto nipasẹ olugbasilẹ mọnamọna oni-nọmba kan, ni idaniloju gbogbo awọn ipa inaro ati petele wa ni isalẹ 2.5g ati 1.2g ni atele jakejado irin-ajo naa. Ọna yii ti ṣaṣeyọri iwọn-ọfẹ 99.9% ibajẹ lori awọn ipa-ọna ti o kọja awọn maili 8,000, ti a fọwọsi nipasẹ idanwo iṣeṣiro ISTA 3E.

 

 

05 Ojula ati Lakotan

Nigbati igbẹkẹle ko ba le bajẹ, -paadi alakoso{1} mẹta yii n pese iṣẹ ti a fihan labẹ awọn ipo ibeere. Ti a ṣe ẹrọ lati kọja awọn iṣedede ile-iṣẹ ati ti a ṣe fun iṣẹ ṣiṣe pẹ ni ibajẹ, giga{3}} awọn agbegbe fifuye, o ju awọn ohun elo lọ-o jẹ oju-ipin ti o lagbara ninu akoj rẹ ti ndagba.