150 KVA 3-alakoso Paadi Amunawa Amunawa-34.5 / 0.208 KV|AMẸRIKA 2025

150 KVA 3-alakoso Paadi Amunawa Amunawa-34.5 / 0.208 KV|AMẸRIKA 2025

Orilẹ-ede: USA 2025
Agbara: 150 kVA
Foliteji: 34.5 / 0.208kV
Ẹya: pẹlu bayonet fiusi
Fi ibere ranṣẹ

Jiangshan Scotech Electrical Co., Ltd jẹ ọkan ninu awọn olupese ti o gbẹkẹle julọ ati awọn olupese ti 150 kva 3 -phase pad mounted transformer-34.5/0.208 kv|USA 2025 ni China. Jọwọ lero ọfẹ lati ra awọn ọja to munadoko fun tita nibi ati gba awọn aworan atọka lati ile-iṣẹ wa. Kan si wa fun alaye sii.

 

3-phase pad mounted transformer

Awọn Grids Alawọ ewe Bẹrẹ lori Ilẹ: Eco- Awọn Ayirapada ti a gbe Paadi mimọ.

 

 

01 Gbogbogbo

1.1 Project Apejuwe

150 kVA mẹta alakoso pad agesin transformer ti a jišẹ si USA ni 2025. Awọn won won agbara ti awọn transformer jẹ 150 kVA pẹlu ONAN itutu. Iwọn giga giga jẹ 34.5D kV pẹlu ± 2 * 2.5% ibiti o tẹ ni kia kia (NLTC), foliteji kekere jẹ 0.208Y / 0.12 kV, wọn ṣẹda ẹgbẹ fekito ti Dyn1.

Paadi - awọn transformers ti a gbe soke jẹ idi{1}} awọn transformers pinpin ita gbangba, ti a ṣe lati fi sori ẹrọ ni ipele ilẹ lori awọn ipilẹ konti ti a fi agbara mu. Gẹgẹbi paati pataki ti awọn amayederun pinpin agbara ipamo, wọn ni igbẹkẹle sin ọpọlọpọ awọn oju iṣẹlẹ, lati awọn agbegbe ibugbe ati awọn agbegbe iṣowo si awọn papa itura ile-iṣẹ.

Ko dabi opopo - awọn oluyipada ti a gbe soke, kekere{1}profaili wọn, apade{2}apẹrẹ iṣọpọ kii ṣe nikan dapọ pẹlu ọgbọn si awọn agbegbe ilu ati igberiko ṣugbọn tun fi owo-ori wa lori aabo ati itọju. Ti a gbe sinu gaungaun, tamper{4}} awọn apoti ẹri, awọn transformers wọnyi wa ni awọn atunto akọkọ meji: okú-iwaju ati laaye-iwaju. Oku -iyatọ iwaju, ti o ni ojurere lọpọlọpọ ni awọn agbegbe ita gbangba, ṣafipamọ gbogbo awọn paati foliteji giga{9} laarin edidi, awọn ideri idabobo. Apẹrẹ yii ṣe imukuro iraye taara si awọn ẹya itanna laaye, dinku eewu ti mọnamọna ina fun oṣiṣẹ itọju ati gbogbo eniyan. Ní àfikún sí i, àgọ́ tí a fi edidi dí erùpẹ̀, ọ̀rinrin, àti olè jíjà, ní dídín àwọn àìní àbójútó ìgbà pípẹ́ sílẹ̀ àti ìmúdájú dédé, wàhálà{13}}ọ̀fẹ́.

 

 

 

1.2 Imọ pato

150 kVA paadi agesin transformer ni pato iru ati data dì

Jišẹ si
USA
Odun
2025
Iru
Paadi agesin transformer
Standard
ANSI / IEEE C57.12.00
Ti won won Agbara
150 kVA
Igbohunsafẹfẹ
60HZ
Ipele
3
Ifunni
Loop
Iwaju
Òkú
Itutu agbaiye
ONAN
Primary Foliteji
34.5D kV
Secondary Foliteji
0.208Y / 0.12 kV
Ohun elo Yiyi
Aluminiomu
Ẹgbẹ Vector
Dyn1
Ipalara
4.0%(±7.5%)
Iṣẹ ṣiṣe
97%
Tẹ Ayipada
NLTC
Ibiti titẹ ni kia kia
±2*2.5%
Ko si Ipadanu Ẹru
0,61 kW
Lori Ipadanu Fifuye
2.0 kW

 

1.3 yiya

150 kVA paadi agesin transformer aworan atọka yiya ati iwọn.

3-phase pad mounted transformer diagram 3-phase pad mounted transformer nameplate

 

 

02 iṣelọpọ

2.1 mojuto

3-phase pad mounted transformer iron core

SCOTECH paadi - mojuto transformer ti a gbe soke, ti a ṣe lati giga - ọkà permeability - oriented silicon steel sheets, gba igbesẹ mitered ni kikun - imọ-ẹrọ apapọ ipele. O ni idamu oofa oofa kekere, ipadanu eddy lọwọlọwọ ati ariwo iṣẹ ti o dinku, pẹlu eto didi ti o lagbara ti o ṣe idaniloju iṣẹ ṣiṣe iduroṣinṣin igba pipẹ {{5} ni awọn eto ita gbangba.

 

2.2 Ejò Ilẹ Okun

Okùn ilẹ bàbà ti SCOTECH paadi - ti a fi sori ẹrọ transformer jẹ ti bàbà elekitirotiki mimọ - giga fun iṣesi to gaju ati ilodisi ipata. Ni pipe ati ni aabo ti a somọ si apade ti oluyipada ati eto ilẹ, o yara yiyi awọn ṣiṣan aṣiṣe lọ si ilẹ, ni aabo awọn ohun elo ni imunadoko lati ibajẹ apọju ati aridaju aabo eniyan. Itumọ ti o lagbara ṣe duro awọn ipo ita gbangba ti o le, ti n pese iṣẹ ṣiṣe didasilẹ igba pipẹ - fun awọn ohun elo pinpin ilu.

Copper Ground Strap

 

2.3 Creepage Ijinna

Creepage Distance

Ijinna oju-iwe lori paadi ti a gbe sori ẹrọ iyipada jẹ ọna ti o kuru ju ni oke ti awọn igbo tabi idabobo lati apakan laaye si ilẹ. O ti wa ni imomose gigun pẹlu awọn grooves tabi awọn ita lati ṣe idiwọ titele itanna ati filasi ni tutu tabi awọn ipo ita gbangba ti doti, ni idaniloju aabo ati igbẹkẹle.

 

2,4 LV Bushing

Ihò mẹrin - kekere {{1} foliteji (LV) ti awọn oluyipada paadi ti a fi sori ẹrọ ni oju ilẹ asiwaju Ejò ati fifi sori ẹrọ petele, ti o nfihan 4 -M12×50 studs welded, Φ85×Φ55×6 oruka edidi fun dídimimọ, ati pin ijinna Ti o tobi ju tabi dọgba si 35mm. O withstands 10kV igbohunsafẹfẹ foliteji, 30kV monomono idasesile foliteji, apa kan itujade Kere ju tabi dogba si 10 pc ni 1.2kV, ati 31.25kA/2s kukuru-Circuit lọwọlọwọ, pẹlu kan 1250N fifẹ fifuye agbara ati idurosinsin isẹ lati -35 ìyí si +40 ìyí pinpin jade.

LV Bushing

 

2.5 Oil Filling àtọwọdá

Oil Filling Valve

Àtọwọdá nkún epo ti awọn oluyipada paadi ti a fi sori ẹrọ ni a fi sori ẹrọ ni kekere - yara foliteji, ti a ṣe ni pataki fun abẹrẹ ti o rọrun ati atunṣe epo idabobo lati ṣetọju awọn ipele epo to dara julọ. O ṣe awọn ọna ṣiṣe edidi ti o gbẹkẹle lati ṣe idiwọ jijo epo ati ọrinrin iwọle, papọ pẹlu oju-ọjọ{2}sooro ati ipata{3} ti o ṣe deede si awọn agbegbe ita gbangba. Olumulo -ore ninu iṣiṣẹ, àtọwọdá naa ngbanilaaye itọju to munadoko lakoko ti o n ṣe idaniloju iṣẹ idabobo ti transformer ati igbẹkẹle iṣiṣẹ pipẹ-.

 

 

03 Idanwo

Awọn idanwo ipin fun awọn oluyipada ti a gbe sori paadi jẹ awọn ilana ṣiṣe idaniloju iṣẹ ṣiṣe to ṣe pataki ti o wọn ipin foliteji laarin awọn iyipo akọkọ ati keji, ni igbagbogbo ti a ṣe labẹ ko - fifuye tabi awọn ipo fifuye ti o ni iwọn pẹlu ohun elo idanwo deede. Awọn idanwo wọnyi ni ifọkansi lati jẹrisi pe ipin iyipada gangan ni ibamu pẹlu awọn pato ti a ṣe, idamo eyikeyi awọn iyapa ti o pọju ti o fa nipasẹ awọn aṣiṣe yiyi, awọn aiṣedeede iṣelọpọ, tabi yiya iṣẹ. Nipa ifẹsẹmulẹ deede ti iyipada foliteji, awọn idanwo ipin rii daju pe ẹrọ oluyipada n pese iduroṣinṣin, agbara ofin ni deede si awọn ọna isalẹ, ṣe idiwọ ibaje apọju / ailagbara si ohun elo ti a ti sopọ, ati ṣetọju iṣẹ igbẹkẹle laarin awọn nẹtiwọọki pinpin ilu.

Ratio test
Ratio tests

 

 

04 Iṣakojọpọ ati Sowo

image021
iṣakojọpọ
image023
sowo

 

 

 

05 Ojula ati Lakotan

Ti a ṣe apẹrẹ lati pade awọn ibeere ti pinpin agbara ilu ilu ode oni, oluyipada paadi wa ti o dapọ mọ-ẹrọ ti o lagbara, iṣẹ ṣiṣe to munadoko, ati ailewu aibikita lati fi awọn solusan agbara igbẹkẹle fun awọn agbegbe iṣowo, awọn ohun elo ile-iṣẹ, ati awọn agbegbe ibugbe. Pẹlu iwapọ rẹ, oju-ọjọ{1} apẹrẹ ti o sooro, awọn paati ere (pẹlu awọn ohun kohun giga{2}}, awọn okun ilẹ idẹ to ni aabo, ati kekere ti o lọra{3}}foliteji bushings), ati idanwo lile (gẹgẹbi ijẹrisi ipin ati awọn sọwedowo idabobo), o ṣe idaniloju iṣẹ iduroṣinṣin paapaa ni awọn ipo ita gbangba lakoko ti o dinku awọn iwulo itọju. Boya ni atilẹyin imugboroja grid, awọn amayederun pataki, tabi ipese agbara lojoojumọ, transformer yii duro bi dukia ti o ni igbẹkẹle- mimu gbigbe agbara pọ si, idinku akoko idinku, ati ibamu pẹlu awọn iwulo idagbasoke ti ọlọgbọn, awọn nẹtiwọọki pinpin alagbero. Yan ojutu kan ti o dapọ agbara, ṣiṣe, ati alaafia ọkan fun awọn ibeere pinpin agbara rẹ.

power distribution

 

Awọn afiwe Gbona: 3-alakoso paadi agesin transformer, olupese, olupese, owo, iye owo

Fi ibere ranṣẹ