750 kVA paadi Mount Amunawa-25 / 0,6 kV|Canada 2025

750 kVA paadi Mount Amunawa-25 / 0,6 kV|Canada 2025

Orilẹ-ede: Canada 2025
Agbara: 750 kVA
Foliteji: 25D-0.6Y / 0.347 kV
Ẹya: pẹlu fifuye fifọ yipada
Fi ibere ranṣẹ

 

 

750 kva pad mount transformer

Agbara Gbẹkẹle, Apẹrẹ Iwapọ – Awọn Ayirapada ti a gbe Paadi fun Akoj Smarter kan!

 

 

01 Gbogbogbo

1.1 Project Apejuwe

750 kVA mẹta alakoso pad agesin transformer ti a jišẹ si Canada ni 2025. Awọn won won agbara ti awọn transformer jẹ 750 kVA pẹlu ONAN itutu. Foliteji akọkọ jẹ 25D kV pẹlu ± 2 * 2.5% ibiti o tẹ ni kia kia (NLTC), foliteji keji jẹ 0.6y / 0.347 kV, wọn ṣẹda ẹgbẹ fekito ti Dyn1.

CSA - paadi ti a fi iwe-ẹri{1} ti a gbe sori awọn oluyipada ni ibamu pẹlu awọn iṣedede lile ti a ṣeto nipasẹ Canadian Standards Association (CSA) fun iṣẹ itanna, agbara, ati agbara ayika. Paadi - awọn oluyipada ti a gbe soke jẹ logan, iwapọ, ati awọn ẹya eletiriki pinpin daradara ti a ṣe apẹrẹ fun fifi sori ita ni ipele ilẹ. Ti a fi sinu awọn ibi ipamọ ti o tọ, ti o tamper{5}, awọn oluyipada wọnyi n pese iyipada agbara ailewu ati igbẹkẹle fun awọn ohun elo ilu, igberiko, ati awọn ohun elo ile-iṣẹ. Aaye wọn{7} fifipamọ apẹrẹ n dinku ifẹsẹtẹ lakoko ti o n ṣe idaniloju iraye si irọrun fun itọju.

Pẹlu idabobo to ti ni ilọsiwaju, idiwọ ipata, ati iṣelọpọ oju ojo, paadi - awọn oluyipada ti a gbe soke n pese iṣẹ ṣiṣe deede ni awọn agbegbe oniruuru{1}lati awọn grid smart ati awọn eto agbara isọdọtun si awọn eka iṣowo ati awọn nẹtiwọọki ohun elo. Ti a ṣe ẹrọ fun ailewu, ṣiṣe, ati igbesi aye gigun, wọn jẹ yiyan igbẹkẹle fun pinpin agbara ode oni.

 

 

 

1.2 Imọ pato

1500 kVA paadi agesin transformer ni pato iru ati data dì

Jišẹ si
Ilu Jamaica
Odun
2025
Iru
Paadi agesin transformer
Standard
CSA 2.1-06
Ti won won Agbara
750 kVA
Igbohunsafẹfẹ
60HZ
Ipele
3
Ifunni
Loop
Iwaju
Òkú
Itutu agbaiye
ONAN
Primary Foliteji
25D kV
Secondary Foliteji
0.6Y / 0.347 kV
Ohun elo Yiyi
Aluminiomu
Angular nipo
Dyn1
Ipalara
4.75%
Tẹ Ayipada
NLTC
Ibiti titẹ ni kia kia
±2*2.5%
Ko si Ipadanu Ẹru
1.4 kW
Lori Ipadanu Fifuye
8,03 kW
Awọn ẹya ẹrọ
Standard iṣeto ni

 

 

1.3 Yiya

750 kVA paadi agesin transformer aworan atọka yiya ati iwọn.

750 kva pad mount transformer diagram 750 kva pad mount transformer nameplate

 

 

02 iṣelọpọ

2.1 mojuto

Paadi 750kVA yii{1} ti a gbe sori ẹrọ ti n lo awọn laminations mojuto CRGO giga - ni ipele mẹta ti konge{3}, mẹta- iṣeto ẹsẹ. Igbesẹ - awọn isọdi tolera ipele jẹ ẹya awọn isẹpo mitred iwọn 45 ati isomọ iposii lati dinku awọn adanu ati rii daju iduroṣinṣin igbekalẹ. Iṣapejuwe apẹrẹ lamination yii n pese iṣẹ ṣiṣe ti o ga julọ, ni ibamu pẹlu awọn iṣedede CSA, pẹlu awọn ohun kohun irin amorphous iyan fun awọn ohun elo ṣiṣe giga julọ-. Itumọ ti o lagbara ṣe iṣeduro iṣẹ ṣiṣe ti o ni igbẹkẹle ni ibeere awọn agbegbe ohun elo.

amorphous metal core

 

2.2 Yiyi

3 winding transformer

Ayipada 3 yiyi ni awọn ẹya pipeye - ti a ṣe atunṣe HV/LV windings nipa lilo awọn olutọpa aluminiomu pẹlu ohun elo idabobo. Yiyi HV n gba apẹrẹ ọgbẹ -, nigba ti LV nlo foil/helical ikole fun agbara lọwọlọwọ giga. Awọn 3 yikaka iṣeto ni kí rọ foliteji transformation. Axial/radial àmúró duro kukuru -awọn ipa ayika.

 

2.3 ojò

Oluyipada irin-ajo {{0} ore-ọfẹ yii ṣe ẹya ipata -sooro, lulú{2}}ipo irin ti a fi bo pẹlu òjé{3}}ọfẹ, ti n funni ni aabo UV ti o ga julọ ati aabo ayika. Ijo 100% -Apẹrẹ ojò alawọ ewe ti n ṣe idiwọ fun idoti ile lakoko ti o ṣe atilẹyin omi FR3 biodegradable. Imọ-ẹrọ fun iduroṣinṣin ati iṣẹ ṣiṣe, o pese iṣẹ idakẹjẹ (<65dB) and includes reinforced lifting points with optional seismic bracing.

eco-friendly tank

 

2.4 ik Apejọ

transformer leads

1. Yiyi Apejọ & mojuto Stacking

Gbe awọn iyipo HV/LV sori awọn ẹsẹ mojuto, ni idaniloju gbigbe idabobo to dara.

Fi awọn laminations ajaga sii ki o di mojuto lati ṣe iyika oofa pipe kan.

2. Itanna Awọn isopọ

So awọn itọsọna pọ nipasẹ alurinmorin tabi bolting, awọn oluyipada tẹ ni kia kia waya, bushings, ati awọn ebute miiran; daju clearances.

3. Ti nṣiṣe lọwọ Apá gbígbẹ

Gbe apakan ti nṣiṣe lọwọ (core + windings) lọ sinu adiro fun igbale{1}}gbigbona{2}}afẹfẹ gbigbe titi akoonu ọrinrin yoo fi pade awọn iṣedede.

4. ojò fifi sori

Gbe apakan ti nṣiṣe lọwọ ti o gbẹ sinu ojò, mö, ki o si ni aabo pẹlu awọn boluti didi; edidi ojò ideri.

5. Iṣagbesori ẹya ẹrọ

Fi awọn ẹya ẹrọ sori ẹrọ gẹgẹbi awọn igbo, awọn ohun elo iderun titẹ, awọn iwọn epo, fiusi bayonet, ati wiwọ iṣakoso.

6. Epo kikun & Igbẹhin

Igbale-kun epo idabobo si ipele ti a sọ. Lẹhin ti yanju, idanwo epo dielectric agbara ati ọrinrin akoonu; ṣe ik jo sọwedowo.

 

 

03 Idanwo

Rara.

Nkan Idanwo

Ẹyọ

Awọn iye gbigba

Awọn iye Diwọn

Ipari

1

Awọn wiwọn Resistance

%

Iwọn aidogba resistance ti o pọju

0.81

Kọja

2

Awọn idanwo ipin

%

Iyapa ti ipin foliteji lori titẹ ni akọkọ: Kere tabi dọgba si 0.5%

0.00

Kọja

3

ipele{0}}awọn idanwo ibatan

/

Dyn1

Dyn1

Kọja

4

Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun

/

I0 :: pese iye iwọn

0.53%

Kọja

P0: pese iye iwọn

1.197kW

Ifarada fun ko si pipadanu ẹru jẹ +10%

/

5

Fifuye adanu impedance foliteji ati ṣiṣe

/

t:85 iwọn

ifarada fun ikọjujasi jẹ ± 7.5%

ifarada fun pipadanu fifuye lapapọ jẹ +6%

/

Kọja

Z%: iye iwọn

4.55%

Pk: iye iwọn

7.325kW

Pt: iye iwọn

8.522kW

Ṣiṣe ko kere ju 99.15%

99.25%

6

Applied Foliteji Igbeyewo

kV

HV: 50kV 60s

LV: 10kV 60s

Ko si iparun ti foliteji idanwo waye

Kọja

7

Induced Foliteji withstand Igbeyewo

kV

Foliteji ti a lo (KV):

2 Úrì

Ko si iparun ti foliteji idanwo waye

Kọja

Duration(s):48

Igbohunsafẹfẹ (HZ): 150

8

Idanwo jijo

kPa

Ipa titẹ: 20kPA

Iye akoko: 12h

Ko si jijo ati ki o ko

Bibajẹ

Kọja

9

Idiwon Resistance idabobo

HV{0}LV si Ilẹ

10.6

/

LV-HV si Ilẹ

10.4

HV&LV si Ilẹ

9.12

10

Idanwo epo

/

Agbara Dielectric;

57,3 kV

Kọja

Ọrinrin akoonu

9.9 mg / kg

Okunfa ifasilẹ

0.00247%

Furan Analysis

0.03

Gaasi Chromatography Analysis

/

 

750 kva pad mount transformer test
pad mount transformer routine test

 

 

04 Iṣakojọpọ ati Sowo

4.1 Iṣakojọpọ

Paadi {{0} ti a gbe soke ni idii ẹrọ iyipada nlo apoti onigi to lagbara ti a fikun pẹlu awọn okun irin, ti o nfihan awọn iho orita tabi awọn aaye gbigbe fun mimu. Ẹka naa ni ifipamo si awọn skids onigi inu apoti, ati fifẹ pẹlu foomu tabi padding roba lati fa awọn ipaya. Awọn ẹya ẹrọ ti wa ni aba ti lọtọ ni siwa kompaktimenti. Ode ti wa ni bo pelu ṣiṣu ṣiṣu ti ko ni omi ati pẹlu awọn baagi desiccant, lakoko ti awọn akole tọka si aarin ti walẹ, aabo ọrinrin, “Maṣe Tilọ,” ati awọn alaye imọ-ẹrọ. Apẹrẹ akojọpọ transformer yii ṣe idaniloju mọnamọna, ọrinrin - sooro, ati aabo ita gbangba gigun, ti a fi jiṣẹ ni ipo edidi ni kikun fun irọrun lori- ayewo aaye ati fifi sori ẹrọ.

transformer technical specifications

 

4.2 Gbigbe

export clearance documents

Paadi {{0}Olupapada ti a gbe soke yoo jẹ gbigbe labẹ awọn ofin CIF si Port of Vancouver, Canada. Olutaja naa ṣeto gbigbe ati iṣeduro ipilẹ, pese ISPM 15-awọn apoti onigi ti o ni ibamu (irin{4}}ti o ni idamu pẹlu mọnamọna{8}}ọṣọ gbigba) ati mimu awọn iwe aṣẹ ifasilẹ okeere (owo iwe-owo, atokọ iṣakojọpọ, ijẹrisi ipilẹṣẹ, ati bẹbẹ lọ). Sowo nlo 40ft awọn apoti oke-ìmọ tabi awọn agbeko alapin, pẹlu ipilẹ ẹrọ oluyipada welded ati fifẹ fun aabo, pẹlu ibojuwo iwọn otutu jakejado gbigbe. Awọn ideri iṣeduro. Port Vancouver nilo ikede ilosiwaju ti iru epo iyipada (ni ibamu pẹlu awọn ilana EPA Kanada), iwe-ẹri CSA (ti o ba wulo), ati ṣiṣe eto window ṣiṣan fun sisọ. Awọn iwe aṣẹ gbọdọ pẹlu Bill of Lading (pẹlu Canada Customs CCN) ati idabobo ijabọ MSDS epo.

 

 

05 Ojula ati Lakotan

Gẹgẹbi okuta igun-ile ti awọn ọna ṣiṣe pinpin agbara, Paadi {{0}Mounted Transformer n ṣe afihan igbẹkẹle, daradara, ati ilolupo - iyipada agbara ore fun ile-iṣẹ, iṣowo, ati awọn amayederun gbogbo eniyan. Ti a ṣe pẹlu tutu tutu{3} silikoni ti a yiyi ati ikole ni kikun, o ṣe idaniloju isonu{4}} kekere, iṣẹ idakẹjẹ lakoko ti o ba aabo IP67 pade ati awọn iṣedede agbaye to lagbara. Apẹrẹ ojò iwapọ n mu aaye pọ si, ati awọn atọkun ibojuwo smati iṣọpọ jẹ ki iṣakoso latọna jijin ṣiṣẹ. Ifọwọsi nipasẹ CSA/UL fun ibamu ti Ariwa Amerika, o ṣe iṣeduro iṣẹ ṣiṣe ti o tọ ni awọn oju-ọjọ giga ati awọn oju iṣẹlẹ fifuye giga{9}} ṣiṣe ni yiyan ti o dara julọ fun awọn amayederun grid ode oni.

CSA certificated

 

Awọn afiwe Gbona: 750 kva pad òke transformer, olupese, olupese, owo, iye owo

Fi ibere ranṣẹ