500 kVA paadi Oke Amunawa-24 * 13.8 * 12 / 0.416 * 0.24 kV|Ilu Jamaa ni ọdun 2025
Agbara: 500kVA
Foliteji: 24GrdY/13.8*13.8D*12GrdY/6.9-0.416Y/0.24*0.24/0.12kV
Ẹya: pẹlu meji foliteji yipada

Lati Awọn ipin si Awọn ilu Smart – Paadi-Awọn Ayirapada ti a gbe soke Jeki Agbara Sisan.
01 Gbogbogbo
1.1 Project Apejuwe
500 kVA pad mounted transformer ti a jišẹ si Ilu Jamaica ni ọdun 2025. Agbara ti a ṣe ayẹwo ti transformer jẹ 500 kVA pẹlu ONAN itutu agbaiye. Foliteji akọkọ jẹ 24 / 13.8 * 13.8D * 12 / 6.9 kV pẹlu ± 2 * 2.5% ibiti o tẹ ni kia kia (NLTC), foliteji keji jẹ 0.416 / 0.24 * 0.24D / 0.12 kV, wọn ṣẹda awọn ẹgbẹ fekito ti YNyn0 ati YNd11.
Paadi wa - ẹrọ oluyipada jẹ iwapọ, ojutu pinpin agbara ni kikun ti a ṣe apẹrẹ fun igbẹkẹle, aabo, ati ṣiṣe ni awọn eto ilu ati ile-iṣẹ. Ti ṣe ẹ̀rọ fun isọpọ alailabosi sinu awọn akoj ode oni, o ṣe ẹya piparẹ -iyipada ayika ati iyipada foliteji meji fun iṣẹ ti o rọ, ngbanilaaye atunṣe foliteji irọrun laisi iṣẹ idilọwọ.
Fun imudara aabo, ẹyọ naa pẹlu awọn imuniwọn igbonwo ati fifuye- awọn asopọ igbonwo, ni idaniloju gige asopọ ailewu ati idinku iṣẹ abẹ. Ifunni {{2}lati fi sii jẹ ki iṣakoso okun to munadoko ṣiṣẹ, lakoko ti o ti pese ibojuwo to ti ni ilọsiwaju nipasẹ thermometer epo, atọka ipele omi, ati iwọn titẹ igbale fun iwadii akoko gidi{{3}.
A ṣe pataki aabo pẹlu Bay{0}O{{1}Nẹtiwọọki fuse ati lọwọlọwọ{2}} awọn fiusi ti o fi opin si lati ṣe idiwọ awọn ẹru apọju, pẹlu iyipada ẹru fifuye fun ipinya to ni aabo lakoko itọju. Ti a ṣe lati koju awọn agbegbe lile, oluyipada yii n pese iṣẹ ṣiṣe ti o gbẹkẹle pẹlu itọju to kere{4}} o dara fun awọn ohun elo, awọn eka iṣowo, ati awọn ohun elo agbara isọdọtun.
1.2 Imọ pato
500 kVA substation transformer ni pato iru ati data dì
|
Jišẹ si
America
|
|
Odun
2025
|
|
Iru
Amunawa substation
|
|
Standard
IEEE Std C57.12.34-2022
|
|
Ti won won Agbara
500 kVA
|
|
Igbohunsafẹfẹ
50HZ
|
|
Ipele
3
|
|
Itutu agbaiye
ONAN
|
|
Primary Foliteji
24/13.8 * 13.8D * 12 / 6,9 kV
|
|
Secondary Foliteji
0.416 / 0.24 * 0.24D / 0,12 kV
|
|
Ohun elo Yiyi
Ejò
|
|
Angular nipo
YNyn0, YNd11
|
|
Ipalara
5%
|
|
Tẹ Ayipada
NLTC
|
|
Ibiti titẹ ni kia kia
±2*2.5%
|
|
Ko si Ipadanu Ẹru
Kere ju tabi dogba si 0.767kW
|
|
Lori Ipadanu Fifuye
Kere ju tabi dogba si 7.2kW
|
1.3 Yiya
500 kVA substation transformer aworan atọka iyaworan ati iwọn.
![]() |
![]() |
02 iṣelọpọ
2.1 mojuto
Ayipada yi ṣe ẹya giga{0}}irin tolera to gaju ti a ṣe lati inu ọkà ti o ga julọ{1}}awọn ohun elo irin silikoni ti o da lori. Lamination kọọkan jẹ lesa gangan -ti ge ati siwa pẹlu igbesẹ titiipapọ{4}}awọn isẹpo itan lati dinku jijo ṣiṣan oofa ati dinku awọn adanu- ko si. A ti bo mojuto pẹlu Layer oxide idabobo lati ṣe idiwọ awọn sisanwo eddy, lakoko ti apẹrẹ ti o ni akopọ ṣe mu iduroṣinṣin ẹrọ pọ si ati pe ariwo ariwo dinku- pataki fun awọn fifi sori ilu. Annealed ni lile fun agbara oofa to dara julọ, mojuto yii ṣe idaniloju gbigbe agbara didan kọja awọn eto foliteji meji, mimu ṣiṣe ṣiṣe paapaa labẹ awọn ẹru iyipada.

2.2 Yiyi

Yiyi foil LV naa nlo ṣiṣan bàbà, ni idaniloju pinpin lọwọlọwọ aṣọ, kukuru kukuru-irapada ayika, ati imudara ooru. Nibayi, yikaka Layer HV gba awọn olutọsọna idẹ idabobo ni ọgbẹ ninu awọn disiki concentric, pẹlu iwe kraft interleaved fun agbara dielectric ti iwọn. Awọn ilana iṣipopada ni a lo lati dinku awọn adanu eddy, lakoko ti axial ati awọn ọna itutu agbaiye radial mu iṣakoso igbona ṣiṣẹ.
2.3 ojò
Tanki transformer jẹ alagbara, ipata - apade irin ti o tako ti o nfi awọn ogiri corrugated 3D fun imugboroosi epo ati awọn imu itutu agbaiye fun itusilẹ ooru palolo. Pẹ̀lú iṣẹ́ ìkọ́ tí a ṣe ní kíkún, tí a ti dánwò nípa rédíò, ó ní àwọn ebute oko USB tí a ti gbẹ́ ṣáájú{3} pẹ̀lú àwọn ọ̀gá ìlẹ̀, tí a sì kọ- sínú àwọn ibi gbígbé/àgbéga. Inu inu pẹlu awọn awo baffle fun sisan epo to dara julọ, lakoko ti UV{6}}kun epoxy ti o sooro n ṣe idaniloju pe pipẹ-itọju igba ni awọn agbegbe ita.

2.4 ik Apejọ

Ipejọ ikẹhin ti paadi yii{0}} transformer ti o gbe ṣopọpọ mojuto - apejọ okun, ojò, ati awọn ẹya ẹrọ sinu eto iṣọkan kan. Ipilẹ ti o gbẹ -Ẹka ti o yipo ni a ti sọ silẹ ni pẹkipẹki sinu ipata{4}ojò irin ti sooro, ti o tẹle pẹlu fifi sori awọn igbo, awọn iyẹ tutu, ati awọn paati iṣakoso. Awọn igbesẹ to ṣe pataki pẹlu:
• Epo kikun labẹ igbale fun impregnation idabobo pipe
• Iṣatunṣe ẹrọ ti awọn iyipada fifọ fifuye & awọn asopọ okun
• Idanwo iṣẹ ṣiṣe ti gbogbo awọn ẹrọ ibojuwo (awọn iwọn, awọn itaniji)
03 Idanwo
|
Rara. |
Nkan Idanwo |
Ẹyọ |
Awọn iye gbigba |
Awọn iye Diwọn |
Ipari |
|
1 |
Awọn wiwọn Resistance |
% |
Iwọn aidogba resistance ti o pọju |
0.76 |
Kọja |
|
2 |
Awọn idanwo ipin |
% |
Iyapa ti ipin foliteji lori titẹ ni akọkọ: Kere ju tabi dọgba si ± 0.5% Aami asopọ: YNyn0/YNd11 |
0.14% ~ 0.15% |
Kọja |
|
3 |
Ipele{0}} igbeyewo ibatan |
/ |
YNyn0/YNd11 |
YNyn0/YNd11 |
Kọja |
|
4 |
Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun |
% kW |
I0 :: pese iye iwọn P0: pese iye iwọn Ifarada fun ko si pipadanu ẹru jẹ +0% |
0.59% 0.7535 |
Kọja |
|
5 |
Fifuye adanu impedance foliteji ati ṣiṣe |
% kW kW |
t:85 iwọn ifarada fun ikọjujasi jẹ ± 7.5% ifarada fun pipadanu fifuye lapapọ jẹ +0% |
/ |
Kọja |
|
Z%: iye iwọn |
5.02% |
||||
|
Pk: iye iwọn |
6.649kW |
||||
|
Pt: iye iwọn |
7.4025kW |
||||
|
Ṣiṣe ko kere ju 99.05% |
99.10% |
||||
|
6 |
Applied Foliteji Igbeyewo |
kV |
HV: 40kV 60s LV: 10kV 60s |
Ko si iparun ti foliteji idanwo waye |
Kọja |
|
7 |
Induced Foliteji withstand Igbeyewo |
kV |
Foliteji ti a lo (KV):2Ur |
Ko si iparun ti foliteji idanwo waye |
Kọja |
|
Iye akoko:40 |
|||||
|
Igbohunsafẹfẹ (HZ): 150 |
|||||
|
8 |
Idanwo jijo |
kPa |
Ipa titẹ: 20kPA Iye akoko: 12h |
Ko si jijo ati ki o ko Bibajẹ |
Kọja |
|
9 |
Idiwon Resistance idabobo |
GΩ |
HV{0}LV si Ilẹ: |
11.0 |
/ |
|
LV-HV si Ilẹ: |
9.51 |
||||
|
HV&LV si Ilẹ: |
20.1 |
||||
|
10 |
Idanwo Dielectric Epo |
kV |
Ti o tobi ju tabi dọgba si 45 |
58.6 |
Kọja |


04 Iṣakojọpọ ati Sowo
4.1 Iṣakojọpọ
Yi paadi agesin transformer ti wa ni dipo nipa akọkọ laying kan Layer ti Tinah bankanje apo lori transformer atẹ ati ki o bo awọn transformer pẹlu awọn Tinah bankanje apo. Nigbati o ba n di apo apamọwọ tin, ṣiṣi silẹ yẹ ki o fi silẹ, nipasẹ eyiti a ti lo ẹrọ igbale kan lati yọ gaasi naa jade, lẹhinna ṣiṣi ti wa ni edidi pẹlu ẹrọ idamu. Nibayi, desiccant ti wa ni gbe inu awọn package lati se ipata. Lẹhin igbale, awọn oludabobo igun ti a ṣe ti foomu, ṣiṣu, tabi paali (awọn oludabobo igun pataki ti a tẹ lati paali) ti wa ni afikun ni ayika transformer, eyi ti o wa ni ipari pẹlu fiimu aabo. Nikẹhin, o ti ṣajọ sinu apoti onigi kan, lori eyiti awọn ami orita ati aarin awọn ami isamisi walẹ yẹ ki o fun sokiri.

4.2 Gbigbe

Paadi yii - transformer ti o gbe yoo jẹ gbigbe labẹ awọn ofin FOB (Ọfẹ Lori Igbimọ), pẹlu olupese ti o ni iduro fun jiṣẹ awọn ọja naa si Port Yiwu ati ipari ikojọpọ sori ọkọ oju omi naa. Ohun-ini ati gbigbe eewu si olura ni kete ti awọn ẹru ba kọja oju-irin ọkọ oju-omi ni Yiwu Port. Ẹru omi okun ti o tẹle ati ifijiṣẹ ikẹhin si Ilu Jamaica ni yoo ṣeto nipasẹ olura. Lakoko gbigbe, ohun elo gbọdọ wa ni ṣinṣin ni aabo lati ṣe idiwọ gbigbọn ati ọrinrin, pẹlu awọn atokọ iṣakojọpọ pipe ati awọn iwe aṣẹ okeere ti a pese fun imukuro aṣa.
05 Ojula ati Lakotan
Pẹlu iṣẹ ṣiṣe giga, apẹrẹ iwapọ, ati agbara to lagbara, Paadi yii{0}Ayipada ti a gbe soke jẹ yiyan ti o dara julọ fun awọn ọna ṣiṣe agbara ile-iṣẹ, iṣowo, ati gbogbo eniyan. Ti ṣelọpọ ni ibamu ti o muna pẹlu awọn iṣedede kariaye, gbogbo ẹyọkan ṣe iṣeduro iṣẹ ṣiṣe giga ati ailewu. Boya o nilo pinpin agbara igbẹkẹle tabi awọn solusan adani fun awọn agbegbe nija, ẹgbẹ wa ti ṣetan lati pese atilẹyin iwé. Kan si wa loni fun awọn alaye ni pato tabi awọn iṣẹ ti a ṣe deede-a ti pinnu lati jiṣẹ awọn ojutu agbara iduroṣinṣin ati to munadoko fun awọn iwulo rẹ!

Awọn afiwe Gbona: 500 kva pad òke transformer, olupese, olupese, owo, iye owo
You Might Also Like
300 kVA Epo ti o kun Amunawa-13.2 / 0.48 kV|Guyana 2024
1500 kVA paadi Amunawa Amunawa Iye-23.9 / 0.416 Kv|I...
500 kVA Meta Alakoso Pinpin Amunawa-4.16 / 0,6 kV|Ca...
1000 kVA paadi Amupada Iye Akojọ-13.8 / 0.415 kV|Ilu...
1500 kVA paadi Amunawa Amunawa-34.5 / 0.48 kV|AMẸRIK...
500 kVA paadi Amunawa Amunawa Iye-22.86 / 0.208 kV|A...
Fi ibere ranṣẹ