50 kVA Amunawa Lori Power Pole-7.97 / 0.12 / 0.24 kV|Canada 2024
Agbara: 50kVA
Foliteji: 7.97/13.8Y-0.12 (0.24) kV
Ẹya: Amorphous mojuto

Oluyipada ti o gbẹkẹle lori ọpa agbara ti n pese agbara daradara ati iduroṣinṣin fun awọn agbegbe ode oni
01 Gbogbogbo
1.1 Project Apejuwe
50 kVA yiiẹyọkan -ọpa alakoso- alayipada ti a gbe pinpinmuna fojusi si IEEE C57.12.20 awọn ajohunše. O jẹ lilo pupọ ni awọn nẹtiwọọki pinpin North America, ti a fi sori ẹrọ ni 13.8 kV ti o wa lori ilẹ-awọn ọna ṣiṣe wye, nibiti a ti so ẹrọ transformer pọ{4}}si{5}iduroṣinṣin ni 7.97 kV ati pese igbẹkẹle 120/240 V pipin-igbejade ipele fun ibugbe ati awọn ohun elo iṣowo ina.
Oluyipada 50 kVA ti o wa lori ọpa agbara gba ipilẹ irin amorphous, eyiti o dinku pupọ ko si - pipadanu fifuye si 0.043 kW nikan. O funni ni agbara to dara pupọ- fifipamọ iṣẹ ṣiṣe paapaa ni ẹru ina. Pẹlu ikọlu ti o ni iwọn ti 2.1%, transformer nfunni ni ilana foliteji to dara ati, papọ pẹlu ± 2×2.5% ko si -ayipada titẹ fifuye, ṣe idaniloju foliteji Atẹle iduroṣinṣin laarin ± 5% ti ipin.
Awọn ẹya apẹrẹ rẹ pẹlu itutu agbaiye ONAN, awọn iyipo aluminiomu, ati polarity aropo, pẹlu ẹgbẹ fekito Ii6. Awọn ẹya ara ẹrọ wọnyi jẹ ki ẹrọ iyipada pọ. O jẹ daradara ati ki o gbẹkẹle fun ọpa ti a gbe soke{2}. Kuro ni o ni a gbaradi arrester Oga. Eyi jẹ ki o rọrun lati ṣafikun awọn ẹrọ aabo.
Awọn transformer ni kekere adanu. O ṣiṣẹ pẹlu ga ṣiṣe. O tun ṣe deede daradara si awọn iwulo oriṣiriṣi. Eyi jẹ ki o jẹ yiyan ti o dara fun awọn ọna ṣiṣe pinpin agbara ode oni.
1.2 Imọ pato
Oluyipada 50kVA lori sipesifikesonu ọpa agbara ati iwe data
|
Jišẹ si
Canada
|
|
Odun
2024
|
|
Iru
Nikan alakoso polu agesin transformer
|
|
Standard
IEEE C57.12.20
|
|
Ti won won Agbara
50 kVA
|
|
Igbohunsafẹfẹ
60HZ
|
|
Polarity
Àfikún
|
|
Ẹgbẹ Vector
Ii6
|
|
Primary Foliteji
7.97 / 13.8Y kV
|
|
Secondary Foliteji
120/240 V
|
|
Ohun elo Yiyi
Aluminiomu
|
|
Ipalara
2.1%
|
|
Ọna Itutu
ONAN
|
|
Tẹ Ayipada
NLTC
|
|
Ibiti titẹ ni kia kia
±2X2.5%
|
|
Ko si Ipadanu Ẹru
0,043 kW
|
|
Lori Ipadanu Fifuye
0.5 kW
|
|
Awọn ẹya ẹrọ
gbaradi arrester Oga
|
1.3 yiya
Oluyipada 50kVA lori iyaworan polu agbara ati apẹrẹ orukọ
![]() |
![]() |
02 iṣelọpọ
2.1 mojuto
Awọn òpó - tí a gbé sódeṣe ẹya mojuto irin amorphous, ti a ṣe lati yo ti irin, boron, silikoni, nickel, ati erogba. Ti a fiwera si otutu ti aṣa - irin silikoni yiyi, koko yii jẹ isotropic, tinrin pupọju (0.03 mm), ati pe o ni agbara eletiriki giga, ti o dinku awọn adanu lọwọlọwọ eddy. O ṣaṣeyọri ni iyalẹnu ti ko si - pipadanu fifuye (0.043 kW) ati pipadanu ẹru (0.5 kW), n funni ni ṣiṣe giga, iṣelọpọ irọrun, ati iṣẹ-iṣe ore-ọfẹ.

2.2 Yiyi

-ọpa ipele alakoso{{1}awọn olupilẹṣẹ ti a gbe sori ẹyọkan ṣe afihan awọn coils foil foil kekere ati awọn coils onirin foliteji giga{{3}. Awọn alabara ti o yan aluminiomu LV coils ni anfani lati dinku iwuwo ati idiyele, lakoko ti o n ṣetọju igbẹkẹle afiwera ati igbesi aye iṣẹ si bàbà. Awọn okun waya foliteji giga- ṣe idaniloju idabobo ati iwọntunwọnsi foliteji.
2.3 ojò
{{0}ojò idana onisẹpo alakoso kan jẹ ti a ṣe lati inu irin kekere, pẹlu ideri ati isalẹ ti a ṣe ni lilo ilana iyaworan tinrin{1}. Ni ipese pẹlu awọn bushings HV meji lori ideri ati awọn bushings eyebolt LV mẹta lori odi ẹgbẹ, apẹrẹ ti o ni edidi ni kikun ṣe idaniloju resistance jijo giga ati igbẹkẹle iṣiṣẹ.

2.4 ik Apejọ

Bii o ṣe le fi okun ati ọgbẹ ọgbẹ sori ẹrọ: Lakọọkọ, dubulẹ C{0}} mojuto alapin akọkọ (nṣisi ti nkọju si oke bii “U”). Mu okun naa ki o si fi iho aarin rẹ ni kikun si ẹsẹ kan ti mojuto, titari si isalẹ si isalẹ. Mu C{3} mojuto keji, so ge rẹ pọ ni pipe pẹlu gige koko akọkọ. Fi rọra pa a titi ti awọn ẹya meji yoo fi darapọ ni kikun. Fi sori ẹrọ ni oke ati isalẹ clamping farahan, fi awọn gun skru.
03 Idanwo
Idanwo baraku
1. Resistance wiwọn
2. Awọn idanwo ipin
3. Ipele{1}} Idanwo ibatan
4. Ko si Awọn ipadanu fifuye ati Ko si fifuye lọwọlọwọ
5. Awọn ipadanu fifuye, Foliteji Impedance ati ṣiṣe
6. Applied Foliteji Igbeyewo
7. Induced Foliteji withstand Igbeyewo
8. Idanwo Leak pẹlu Ipa fun Liquid Immersed Transformers
9. Idiwọn Resistance Insulation
10. Oil Dielectric igbeyewo
11. Monomono Impulse Igbeyewo


Awọn abajade Idanwo
|
Rara. |
Nkan Idanwo |
Ẹyọ |
Awọn iye gbigba |
Awọn iye Diwọn |
Ipari |
|
1 |
Awọn wiwọn Resistance |
% |
/ |
/ |
Kọja |
|
2 |
Awọn Idanwo Ipin |
% |
Iyapa ti ipin foliteji lori titẹ ni akọkọ: Kere tabi dọgba si 0.5% Aami asopọ: Ii6 |
0.02 |
Kọja |
|
3 |
ipele{0}}awọn idanwo ibatan |
/ |
Àfikún |
Àfikún |
Kọja |
|
4 |
Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun
|
% kW |
t:85 iwọn I0 :: pese iye iwọn P0: pese iye iwọn Ifarada fun ko si pipadanu ẹru jẹ +10% |
1.11(100%) 2.16(105%) 0.045(100%) 0.061(105%) |
Kọja |
|
5 |
Fifuye adanu impedance foliteji ati ṣiṣe |
% kW kW |
t:85 iwọn Z%: iye iwọn Pk: iye iwọn Pt: iye iwọn ifarada fun ikọjujasi jẹ ± 10% ifarada fun pipadanu fifuye lapapọ jẹ +6% |
2.21 0.496 0.543 99.37 |
Kọja |
|
6 |
Applied Foliteji Igbeyewo |
kV |
HV: 34kV 60s LV: 10kV 60s |
Ko si iparun ti foliteji idanwo waye |
Kọja |
|
7 |
Induced Foliteji withstand Igbeyewo |
kV |
Foliteji ti a lo (KV): 15.94 Iye akoko:40 Igbohunsafẹfẹ (HZ): 150 |
Ko si iparun ti foliteji idanwo waye |
Kọja |
|
8 |
Idanwo jijo |
kPa |
Ipa titẹ: 20kPA Iye akoko: 12h |
Ko si jijo ati ko si Bibajẹ |
Kọja |
|
9 |
Idiwon Resistance idabobo |
GΩ |
HV&LV si Ilẹ: |
120.0 |
/ |
|
HV{0}LV si Ilẹ |
51.8 |
||||
|
LV-HV si Ilẹ |
62.6 |
||||
|
10 |
Idanwo Dielectric Epo |
kV |
Ti o tobi ju tabi dọgba si 45 |
55.48 |
Kọja |
|
11 |
Idanwo imunmi ina |
kV |
ni kikun igbi, Idaji igbi |
Ko si iparun ti foliteji idanwo waye |
Kọja |
04 Iṣakojọpọ ati Sowo


05 Ojula ati Lakotan
Oluyipada 50 kVA ẹyọkan -ọpa ipele{2}} ti a gbe sori jẹ ti a ṣe fun Ilu Kanada ni ọdun 2024. O tẹle IEEE C57.12.20. O ṣiṣẹ lori 13.8 kV ti o wa lori ilẹ- awọn ọna ṣiṣe wye, fifun 120/240 V fun awọn ile ati awọn iṣowo kekere.
Awọn transformer ni o ni ohun amorphous irin mojuto. Ko tọju pipadanu fifuye - ni 0.043 kW ati pipadanu fifuye ni 0.5 kW. O fipamọ agbara ati ṣiṣe pẹlu ṣiṣe giga. Aluminiomu windings, ONAN itutu agbaiye, ati aropo polarity ṣe awọn kuro iwapọ, ailewu, ati ki o gbẹkẹle. Oga arrester gbaradi faye gba rorun Idaabobo awọn iṣagbega.
Ayipada yi lori ọpa agbara ṣopọ iṣẹ ṣiṣe, igbẹkẹle, ati iṣẹ ṣiṣe ore-ọfẹ, ṣiṣe ni yiyan ti o lagbara fun awọn nẹtiwọọki pinpin ode oni.
Scotech ṣe awọn oluyipada didara fun awọn alabara agbaye. Awọn ọja wa fi agbara pamọ, ge awọn adanu, ati fun agbara iduroṣinṣin. A fi ailewu ati awọn solusan ti a fihan ti o ṣe iranlọwọ awọn grids agbara ṣiṣẹ dara julọ ni gbogbo ọjọ.
Awọn oluyipada Scotech - ti o gbẹkẹle, agbara daradara, awọn nẹtiwọọki to dara julọ.

Awọn afiwe Gbona: Amunawa Lori Polu Agbara, olupilẹṣẹ, olupese, idiyele, idiyele
You Might Also Like
75 kVA Pole Iru Amunawa-34.5 / 0.12 * 0.24 kV|Canada...
100 kVA Tẹlifoonu polu Amunawa-34,5 / 0,24 kV|AMẸRIK...
167 kVA Cooper Paadi Amunawa-13.8 / 0.24 kV|Guyana 2024
100 kVA Amunawa polu Agesin-13.8 / 0,24 kV|Guyana 2025
75 kVA IwUlO Amunawa-24.94 / 0,12 kV|Canada 2025
50 kVA Amunawa Agbara Laini-13.8 / 0.12 * 0.24 kV|Gu...
Fi ibere ranṣẹ