50 kVA Amunawa Agbara Laini-13.8 / 0.12 * 0.24 kV|Guyana 2024

50 kVA Amunawa Agbara Laini-13.8 / 0.12 * 0.24 kV|Guyana 2024

Orilẹ-ede Ifijiṣẹ: Guyana 2024
Agbara: 50kVA
Foliteji: 13.8 / 0.12 * 0,24 kVA
Fi ibere ranṣẹ

 

 

transformer power line

SCOTECH Ipele Ipele Kanṣo ti Awọn Ayirapada: Agbara Gbẹkẹle lati 10kVA si 500kVA fun Gbogbo iwulo Grid

 

 

01 Gbogbogbo

1.1 Project Apejuwe

Aṣẹ lati ọdọ alabara wa ni Guyana 2024, ile-iṣẹ iṣẹ ẹrọ itanna kan, pẹlu awọn oluyipada pẹlu agbara 25kVA, 50kVA, 75kVA, 100kVA, ati 167kVA. 50kVA Ideal fun alabọde{7}} awọn agbegbe ibugbe tabi awọn iṣowo kekere.

Oluyipada naa ni ibamu daradara si IEEE & ANSI C57.12.00 awọn ajohunše. Ṣiṣẹ ni foliteji akọkọ ti 13,800V, ti nlọ si isalẹ si 120/240V ni ẹgbẹ keji, pẹlu igbohunsafẹfẹ ti 60Hz ati awọn iyipo idẹ. Ikọju naa jẹ 2%, idinku idinku foliteji labẹ fifuye.

Ni ipese pẹlu eto itutu agbaiye ONAN ati NLTC kan (Ko si Oluyipada Iyipada Fifuyẹ), o funni ni iwọn 10% titẹ ni kia kia (± 2.5% fun tẹ ni kia kia), iduroṣinṣin foliteji keji paapaa pẹlu awọn iyipada akọkọ. Ipadanu - ko si jẹ 160W, ati pe - pipadanu fifuye jẹ 512W, mimu lilo agbara ṣiṣẹ. Oluyipada naa ṣe ẹya polarity iyokuro ati ẹgbẹ fekito ti Ii0, ti n ṣalaye ibatan alakoso rẹ.

Gẹgẹbi olupilẹṣẹ oludari ti awọn Ayirapada, a funni ni awọn solusan oluyipada pipe fun awọn iwulo pinpin itanna rẹ.

 

 

1.2 Imọ pato

50kVA Single alakoso polu agesin transformer sipesifikesonu ati data dì

Jišẹ si
Guyana
Odun
2024
Iru
Nikan alakoso polu agesin transformer
Standard
IEEE & ANSI C57.12.00
Ti won won Agbara
50 kVA
Igbohunsafẹfẹ
60HZ
Polarity
Iyokuro
Ẹgbẹ Vector
Ii0
Primary Foliteji
13800 V
Secondary Foliteji
120/240 V
Ohun elo Yiyi
Idẹ
Ipalara
2%
Ọna Itutu
ONAN
Tẹ Ayipada
NLTC
Ibiti titẹ ni kia kia
±2X2.5%(Apapọ ibiti=10%)
Ko si Ipadanu Ẹru
160 W
Lori Ipadanu Fifuye
512 W
Awọn ẹya ẹrọ
Standard iṣeto ni

 

 

1.3 Yiya

50kVA Single alakoso polu agesin transformer mefa ati iwuwo awọn alaye

image003 image005

 

 

02 iṣelọpọ

2.1 mojuto

Anfani igbekale ti mojuto ọgbẹ ni pe o ngbanilaaye ohun elo ferromagnetic lati lo ni kikun awọn ohun-ini itanna eleto giga rẹ, idinku iye adanu ipadanu mojuto. Ẹsẹ koko ati àjaga agbelebu -apakan ti ẹyọkan-oju ọgbẹ alakoso jẹ onigun mẹrin ati ọgbẹ lemọlemọ pẹlu okun irin oofa, dinku ni pataki ko si - pipadanu fifuye, ko si - fifuye lọwọlọwọ, ati ariwo transformer.

wound core

 

2.2 Yiyi

high-purity enameled round copper wire

Awọn yiyipo oniyipada wa nlo giga -funfun enameled yika okun waya Ejò, ti n ṣe ifihan adaṣe itanna to dara julọ ati idabobo iwapọ. Iboju enamel pese idabobo aṣọ ati agbara dielectric ti o gbẹkẹle. Gba igbekalẹ okun iṣapeye ti yiyi foil fun kekere-awọn coils foliteji ati yiyi waya fun giga{4}}awọn coils foliteji, ni idaniloju iduroṣinṣin iṣẹ ṣiṣe to dara julọ, igbẹkẹle, ati ṣiṣe igbona.

 

2.3 ojò

Ojò irin ìwọnba pẹ̀lú àwọn ọ̀kọ̀ gbígbé tí a fi weled àti àwọn biraketi hanger fun gbigbe taara -si{1}}òpó. KVA Rating lori ojò odi. Awọn ideri aabo ni a lo si awọn tanki lati dinku ibajẹ. Lati rii daju iṣẹ ailewu ti awọn oluyipada itanna wọnyi laibikita ifihan si awọn ipo oju-ọjọ lile ati awọn ipo jijin wọn, igbẹkẹle ti kọ sinu awọn pato wọn.

transformer specifications

 

2.4 ik Apejọ

core coil drying

1. Apejọ Yiyi:Rọra awọn iyipo HV/LV sori mojuto laminated, aridaju titete to dara ati iduroṣinṣin idabobo.

2. Awọn Isopọ Itanna:Sopọ yikaka nyorisi tẹ ni kia kia oluyipada, bushings, ati awọn miiran irinše, ki o si oluso ati ki o idabobo awọn isẹpo.

3. Kokoro -Gbigbe okun:Gbe apakan ti nṣiṣe lọwọ ti o pejọ (mojuto + windings) sinu adiro gbigbe fun alapapo igbale lati yọ ọrinrin kuro.

4. Fifi sori ojò:Gbe apakan ti nṣiṣe lọwọ ti o gbẹ sinu ojò, gbe si ni aabo, ati rii daju idabobo to dara lati awọn odi ojò.

5. Iṣagbesori Ẹya ẹrọ:Fi bushings sori ẹrọ, àtọwọdá iderun titẹ ati awọn ẹya ẹrọ miiran, lẹhinna ṣayẹwo fun awọn n jo.

6. Nkún Epo & Ṣiṣeto:Igbale-kun pẹlu epo idabobo, degas, ati gba laaye lati yanju ṣaaju ṣiṣe ayẹwo awọn ipele epo ati agbara dielectric.

 

 

03 Idanwo

Idanwo baraku

1. Resistance wiwọn

2. Awọn idanwo ipin

3. Polarity igbeyewo

4. Ko si Awọn ipadanu fifuye ati Ko si fifuye lọwọlọwọ

5. Fifuye adanu ati Impedance Foliteji

6. Applied Foliteji Igbeyewo

7. Induced Foliteji withstand Igbeyewo

8. Idiwọn Resistance Insulation

9. Idanwo Leak pẹlu Ipa fun Liquid Immersed Transformers

10. Oil Dielectric igbeyewo

transformer power line test

Awọn abajade Idanwo

Rara.

Nkan Idanwo

Ẹyọ

Awọn iye gbigba

Iwọn Iwọn

Ipari

1

Awọn wiwọn Resistance

/

/

/

Kọja

2

Awọn idanwo ipin

/

Iyapa ti ipin foliteji lori titẹ ni akọkọ: Kere tabi dọgba si 0.5%

Aami asopọ: Ii0

-0.04

Kọja

3

Awọn idanwo polarity

/

Iyokuro

Iyokuro

Kọja

4

Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun

%

kW

I0 :: pese iye iwọn

P0: pese iye iwọn

Ifarada fun ko si pipadanu ẹru jẹ +10%

0.95

0.130

Kọja

5

Awọn adanu fifuye, foliteji impedance, awọn adanu lapapọ ati ṣiṣe

/

kW

kW

t:85 iwọn

Z%: iye iwọn

Pk: iye iwọn

Pt: iye iwọn

ifarada fun ikọjujasi jẹ ± 10%

ifarada fun pipadanu fifuye lapapọ jẹ +6%

2.08

0.518

0.648

99.02

Kọja

6

Applied Foliteji Igbeyewo

/

HV: 34KV 60s

LV: 10kV 60s

Ko si iparun ti foliteji idanwo waye

Kọja

7

Induced Foliteji withstand Igbeyewo

/

Foliteji ti a lo (KV):

2 Úrì

Iye akoko: 48

Igbohunsafẹfẹ (HZ): 150

Ko si iparun ti foliteji idanwo waye

Kọja

8

Idiwon Resistance idabobo

HV{0}LV si Ilẹ

LV-HV si Ilẹ

HV&LV si Ilẹ

83.6

76.9

75.3

/

9

Idanwo jijo

/

Ipa titẹ: 20kPA

Iye akoko: 12h

Ko si jijo ati ki o ko

Bibajẹ

Kọja

10

Idanwo Dielectric Epo

kV

Ti o tobi ju tabi dọgba si 45

51.41

Kọja

 

04 Iṣakojọpọ ati Sowo

transformer power line packing transformer power line shipping
 

05 Ojula ati Lakotan

Ayipada 50kVA ẹyọkan -ọpa ipele- ti a gbe soke fun Guyana ṣe idaniloju pipe, iduroṣinṣin, ati pinpin agbara ailewu.

Ti a ṣe pẹlu -didara idẹ giga, kekere-egbo ọgbẹ pipadanu, ati itagbangba ita gbangba{2}}ojò ti o ṣetan, o pese igbẹkẹle gigun{{3} paapaa ni awọn agbegbe ti o nbeere.

50 kVA transformer power line

 

 