25 KVA Nikan Alakoso polu Amunawa-25 / 0.347 KV|Canada 2024
Agbara: 25 kVA
Foliteji: 25/0.347kV
Ẹya ara ẹrọ: Giga -foliteji bushings ilọpo meji

25 kVA oluyipada ọpọn apa kan - igbẹkẹle, daradara, ati monomono{1}}Agbara ita gbangba ni idaabobo
01 Gbogbogbo
1.1 Project Apejuwe
Mẹta 25 kVA ẹyọkan -pase alakoso-awọn transformer ti a gbe soke ni a pese fun alabara Ilu Kanada nipasẹ Scotech ni ọdun 2024 gẹgẹ bi apakan ti aṣẹ mẹsan{4}. Ni ibamu patapata si awọn iṣedede CSA C2.2-06. Ti won won fun a jc foliteji ti 25 kV ati ki o kan Atẹle foliteji ti 0.347 kV, laimu kan lapapọ agbara ti 25 kVA labẹ lemọlemọfún fifuye. O nlo itutu agba epo adayeba ONAN, epo nkan ti o wa ni erupe ile bi alabọde idabobo, polarity aropo, ati ẹgbẹ fekito Ii6.
Oluyipada yii ṣe ẹya awọn iyipo aluminiomu, idinku iwuwo ati idiyele, ṣiṣe fifi sori ẹrọ ati gbigbe rọrun. Iṣeduro 2.8% rẹ ṣe iranlọwọ fun iwọntunwọnsi kukuru - awọn ṣiṣan iyika ati ilana foliteji ninu awọn eto pinpin, awọn eto aabo dirọrun. O ti ni ipese pẹlu NLTC (Bẹẹkọ-Iyipada Fifuye Tẹ ni kia kia) pẹlu igbesẹ 2.5% kan, ngbanilaaye atunṣe foliteji igbejade lakoko iṣẹ lati jẹ ki foliteji duro. O tun ni 33 kV awọn imuni monomono polima ati giga meji giga -foliteji bushings fun imunadoko monomono ati aabo apọju.
Iṣeto foliteji yii jẹ wọpọ ni Ariwa Amẹrika ati awọn eto pinpin Ilu Kanada. Awoṣe yii n ṣe iranṣẹ fun awọn agbegbe igberiko, awọn agbegbe ibugbe, ati awọn iṣowo kekere nibiti agbara ẹyọkan ti iduroṣinṣin{1}} ṣe pataki. Isopọ akọkọ 25 kV jẹ ki o jẹ yiyan ti o lagbara fun atokan tabi awọn eto loop ni awọn agbegbe ita gbangba pẹlu iṣẹ ṣiṣe monomono ti o ga julọ. Boya a lo lori awọn laini akọkọ ti igberiko tabi ni opin nẹtiwọọki oruka, ẹrọ oluyipada yii n pese iṣẹ iduroṣinṣin ati igbẹkẹle.
1.2 Imọ pato
25 kVA nikan alakoso polu transformer sipesifikesonu ati data dì
|
Jišẹ si
Canada
|
|
Odun
2024
|
|
Iru
Polu agesin Amunawa
|
|
Standard
CSA C2.2-06
|
|
Ti won won Agbara
25kVA
|
|
Igbohunsafẹfẹ
60HZ
|
|
Polarity
Àfikún
|
|
Ipele
1
|
|
Itutu agbaiye
ONAN
|
|
Insulant olomi
Epo Eruku
|
|
Primary Foliteji
25 kV
|
|
Secondary Foliteji
0,347 kV
|
|
Ẹgbẹ Vector
Ii6
|
|
Ohun elo Yiyi
Aluminiomu
|
|
Ipalara
2.8%
|
|
Iṣẹ ṣiṣe
98.63%
|
|
Tẹ Ayipada
NLTC
|
|
Ibiti titẹ ni kia kia
±2*2.5%
|
|
Ko si Ipadanu Ẹru
83 kV
|
|
Lori Ipadanu Fifuye
404 kV
|
|
Awọn ẹya ẹrọ
Agbofinro
|
1.3 Yiya
25 kVA nikan alakoso polu transformer iyaworan ati nameplate
![]() |
![]() |
02 iṣelọpọ
2.1 mojuto
Kokoro transformer jẹ paati bọtini kan ti o n ṣe Circuit oofa ati muu gbigbe agbara ṣiṣẹ laarin awọn iyipo akọkọ ati Atẹle. O nlo ọkà ti o ga{1}}-awọn ohun elo irin silikoni ti o ni itosona ti o tolera ati idayatọ lati dinku awọn adanu lọwọlọwọ eddy. Ipilẹ ṣe ẹya apẹrẹ pataki - iru oniru pẹlu awọn ọwọn onigun, iṣapeye fun ṣiṣan oofa ti o pọju ati ṣiṣe giga ni iṣẹ ṣiṣe ti nlọsiwaju.
2.2 Yiyi
Aluminiomu windings ti wa ni iṣelọpọ labẹ iṣakoso ti o muna ti itọsọna, polarity, ati ẹdọfu. Okun LV naa jẹ egbo ni akọkọ, atẹle pẹlu okun HV, pẹlu idabobo Layer ti a lo ni wiwọ ko si awọn wrinkles. Awọn išedede titan wa laarin ± 0.3%. Awọn ọna epo radial Ti o tobi ju tabi dọgba si 3 mm ati funmorawon duro ṣetọju itutu agbaiye ti o munadoko ati agbara ẹrọ, idilọwọ abuku lakoko iṣẹ.

2.3 ojò

Ojò epo ti wa ni itumọ ti lati pade ti o muna arrester fifi sori awọn ajohunše. O ni awọn flange ti o lagbara ati awọn atilẹyin, o le gbe iwuwo ati gbigbọn, ati awọn ẹya awọn iho fifin to ni aabo. Ohun elo ojò duro ni iwọn otutu giga ati titẹ. Gasket rii daju pe ko si awọn n jo epo. Awọn dada ti wa ni itọju lodi si ipata. Oke pese aaye ti o to fun yiyọkuro irọrun ati rirọpo ti awọn ti o mu lai ṣe adehun lilẹ.
2.4 ik Apejọ
Mojuto ati Yika Apejọ
Fi sori ẹrọ giga -foliteji ati kekere{1}} awọn afẹfẹ foliteji sori koko, ni idaniloju idabobo ati ifọkansi.
Fifi sori ara
Gbe awọn mojuto ati yikaka ijọ sinu epo ojò.
Fi awọn idari sori ẹrọ ati awọn igbo idabobo, ni idaniloju lilẹ to dara.
Àgbáye Amunawa Epo
Abẹrẹ epo oluyipada ti a yan, ni idaniloju pe o mọ ati laisi awọn aimọ.
Fi Ita Awọn ẹya ẹrọ
So awọn falifu ailewu, awọn iwọn ipele epo, ati awọn asopọ ebute.

03 Idanwo
Igbeyewo Standard ati baraku Igbeyewo
CSA C2.2-06(R2022) Ẹyọkan-ilana ati mẹta{4}}awọn ayirapada pinpin olomi-alakoso
CSA C802.1-13(R2022) Awọn iye ṣiṣe to kere julọ fun awọn oluyipada pinpin olomi
1. Resistance wiwọn
2. Awọn idanwo ipin
3. Polarity igbeyewo
4. Ko si Awọn ipadanu fifuye ati Ko si fifuye lọwọlọwọ
5. Fifuye adanu ati Impedance Foliteji
6. Applied Foliteji Igbeyewo
7. Induced Foliteji withstand Igbeyewo
8. Idiwọn Resistance Insulation
9. Idanwo Leak pẹlu Ipa fun Liquid Immersed Transformers
10. Epo Idanwo
Awọn abajade Idanwo
|
Rara. |
Nkan Idanwo |
Ẹyọ |
Gbigba Awọn iye |
Awọn iye Diwọn |
Ipari |
|
1 |
Awọn wiwọn Resistance |
/ |
/ |
/ |
Kọja |
|
2 |
Awọn idanwo ipin |
/ |
Iyapa ti ipin foliteji lori titẹ ni akọkọ: Kere tabi dọgba si 0.5% Aami asopọ: Ii6 |
0.11~0.12 |
Kọja |
|
3 |
Awọn idanwo polarity |
/ |
Àfikún |
Àfikún |
Kọja |
|
4 |
Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun |
% |
I0 :: pese iye iwọn (100%) |
0.38 |
Kọja |
|
kW |
P0: pese iye iwọn (100%) |
0.0681 |
|||
|
% |
I0 :: pese iye iwọn (105%) |
0.40 |
|||
|
kW |
P0: pese iye diwọn (105%) |
0.0766 |
|||
|
/ |
Ifarada fun ko si pipadanu ẹru jẹ +10% |
/ |
|||
|
5 |
Awọn adanu fifuye, foliteji impedance, awọn adanu lapapọ ati ṣiṣe |
/ |
t:85 iwọn ifarada fun ikọjujasi jẹ ± 7.5% ifarada fun pipadanu fifuye lapapọ jẹ +6% |
/ |
Kọja |
|
% |
Z%: iye iwọn |
2.60 |
|||
|
kW |
Pk: iye iwọn |
0.366 |
|||
|
kW |
Pt: iye iwọn |
0.4341 |
|||
|
% |
Ṣiṣe ko kere ju 98.63% |
98.81 |
|||
|
6 |
Applied Foliteji Igbeyewo |
/ |
LV: 10kV 60s HV: 40kV 60s |
Ko si iparun ti foliteji idanwo waye |
Kọja |
|
7 |
Induced Foliteji withstand Igbeyewo |
/ |
Foliteji ti a lo (KV):2Ur |
Ko si iparun ti foliteji idanwo waye |
Kọja |
|
Iye akoko:40 |
|||||
|
Igbohunsafẹfẹ (HZ): 180 |
|||||
|
8 |
Idiwon Resistance idabobo |
GΩ |
HV-LV·to·Ilẹ |
306 |
Kọja |
|
LV-HV si Ilẹ |
422 |
||||
|
HV&LV si Ilẹ |
129 |
||||
|
9 |
Idanwo jijo |
/ |
Ipa titẹ: 20kPA |
Ko si jijo ati ki o ko Bibajẹ |
Kọja |
|
Iye akoko: 12h |
|||||
|
10 |
Idanwo epo |
kV |
Dielectric Agbara |
61.0 |
|
|
mg/kg |
Ọrinrin akoonu |
13.6 |
|||
|
% |
Okunfa ifasilẹ |
0.158 |
|||
|
mg/kg |
Furan Analysis |
Kere ju tabi dogba si 0.1 |
|||
|
/ |
Gaasi Chromatography Analysis |
/ |


04 Iṣakojọpọ ati Sowo


05 Ojula ati Lakotan

Gbẹkẹle ati lilo daradara, oluyipada kVA 25 ni ibamu pẹlu awọn iṣedede CSA C2.2-06 pẹlu iwọn 25 kV/0.347 kV, awọn yiyi aluminiomu, ati itutu ONAN. Ni ipese pẹlu oluyipada tẹ ni kia kia NLTC ati awọn imuni ina 33 kV, o ṣe idaniloju foliteji iduroṣinṣin ati aabo. Apẹrẹ fun igberiko, ibugbe, ati awọn netiwọki iṣowo kekere, o pese ailewu, ti o tọ, ati irọrun-lati fi agbara ita gbangba sori ẹrọ.
Awọn afiwe Gbona: Oluyipada opopo alakoso kan, olupilẹṣẹ, olupese, idiyele, idiyele
You Might Also Like
15 kVA Pole Amunawa-24.94 / 0.12 * 0.24 kV|Canada 2024
50 kVA IwUlO polu Ayirapada-34.5 / 0.12 * 0,24 kV|Ca...
500 kVA polu Amunawa-4.16 / 0,6 kV|Canada 2024
167 kVA Ọpa Agbekale Pipin Amunawa-24.94 / 0.12 / 0....
167 kVA Pole Amunawa-13.8 / 0.12 * 0.24 kV|Guyana 2024
167 KVA Nikan Alakoso Ọpa Ti a gbe Amunawa-2.4 / 0.3...
Fi ibere ranṣẹ