75 kVA polu Mount Ayirapada-14.4 / 0.277 kV|Canada 2025

75 kVA polu Mount Ayirapada-14.4 / 0.277 kV|Canada 2025

Orilẹ-ede: Canada 2025
Agbara: 75 kVA
Foliteji: 24.94GrdY/14.4-0.48/0.277kV
Ẹya ara ẹrọ: pẹlu pipa-oluyipada tẹ ni kia kia
Fi ibere ranṣẹ

 

 

image001

Polu agesin Ayirapada: Ifijiṣẹ Power Ibi ti o ti Nlo.

 

01 Gbogbogbo

1.1 Project abẹlẹ

A 75 kVA nikan ipele opo igi agesin transformer ti a jišẹ si Canada ni 2025. Awọn won won agbara ti awọn transformer jẹ 75 kVA pẹlu ONAN itutu. Awọn ga foliteji ni 24.94GrdY/14.4 kV pẹlu ± 2 * 2.5% kia kia ibiti (NLTC), awọn kekere foliteji ni 0.48 / 0.277 kV, nwọn si akoso kan fekito ẹgbẹ ti Ii6.

Gẹgẹbi ọna asopọ to ṣe pataki ti o n so pọ giga -apapọ agbara foliteji lati pari{1} awọn olumulo, opopo ti o wa ni ipele ẹyọkan ṣe ipa ti ko ṣe pataki ninu ipese ina mọnamọna lojoojumọ fun ibugbe, igberiko, ati kekere{2} awọn oju iṣẹlẹ iṣowo iwọn. Ko dabi awọn oluyipada ipapopada nla{{4}, o ti fi sori ẹrọ taara lori awọn ọpá ohun elo, ngbanilaaye imuṣiṣẹ rọ ni awọn agbegbe ti o ni aaye to lopin- gẹgẹbi awọn opopona ibugbe, awọn opopona igberiko, tabi nitosi awọn ile itaja kekere ati awọn ile oko. Nípa lílọ lọ́wọ́lọ́wọ́ pẹ̀lú iná mànàmáná gíga - sí àìléwu, ìwọ̀nba foliteji kékeré tí a lè lò, ó ń fún àwọn ohun èlò ilé, ẹ̀rọ iṣẹ́ àgbẹ̀, àti àwọn ohun èlò ìṣòwò kékeré, ní àtìlẹ́yìn tààràtà ní ìgbésí ayé ojoojúmọ́ àti àwọn ìgbòkègbodò ọrọ̀ ajé agbègbè. Pẹlu awọn anfani ti itọju irọrun, ariwo iṣiṣẹ kekere, ati resistance to lagbara si oju ojo lile (fun apẹẹrẹ, ojo, eruku, ati awọn iwọn otutu), ẹrọ oluyipada yii ṣe idaniloju ipese agbara lemọlemọ paapaa ni awọn agbegbe eka, ti o jẹ ki o jẹ okuta igun-ile ti igbẹkẹle ati wiwọle pinpin ina mọnamọna fun awọn agbegbe agbaye.

 

1.2 Imọ pato

75 kVA polu agesin transformer ni pato iru ati data dì

Jišẹ si
Canada
Odun
2025
Iru
Polu agesin transformer
Standard
CSA C2.2-06
Ti won won Agbara
75 kVA
Igbohunsafẹfẹ
60HZ
Ipele
1
Polarity
Àfikún
Itutu agbaiye
ONAN
Primary Foliteji
24,94GrdY / 14,4 kV
Secondary Foliteji
0,48 / 0,277 kV
Ohun elo Yiyi
Ejò
Angular nipo
Ii6
Ipalara
Ti o tobi ju tabi dọgba si 1.5%
Tẹ Ayipada
NLTC
Ibiti titẹ ni kia kia
±2*2.5%
Ko si Ipadanu Ẹru
0,165 kW
Lori Ipadanu Fifuye
1.05 kW

 

1.3 Yiya

75 kVA òpó agesin transformer iyaworan ati iwọn.

image003 20251029145305473177

 

 

02 polu òke Ayirapada Parts

2.1 LV Bushing - BIL: 30 kV; LV Ilẹ Ipese

 

L.V. Bushing – BIL: 30 kV

Iwọn kekere{0}foliteji bushings jẹ oṣuwọn fun 30 kV BIL, eyiti o jẹ diẹ sii ju to fun ẹgbẹ LV ti ẹyọ kVA 75 kan ti o si pese ala idabobo itunu. Ipese ilẹ LV ti wa ni apa ọtun lẹgbẹẹ rẹ, ṣiṣe didoju didoju taara ati ifaramọ. Awọn oniṣẹ le wọle si ni irọrun lakoko fifi sori ẹrọ.

 

 

2,2 HV Bushing - BIL: 125 kV

Ni ẹgbẹ giga - foliteji, awọn igbo ti pade 125 kV BIL. Iwọnwọn yii jẹ boṣewa fun awọn ipele pinpin Ilu Kanada ati pe o fun oluyipada ni aabo to lagbara lodi si awọn imun ina. O jẹ paati ti o rọrun, ṣugbọn o gbe ojuṣe pataki ni awọn ipo akoj gidi.

H.V. Bushing – BIL: 125 kV

 

 

2.3 Ideri Okun Ilẹ

Cover Ground Strap

Okùn ilẹ ti wa ni ibamu kọja ideri ojò. Iṣẹ rẹ ni lati tọju gbogbo awọn ẹya irin ni agbara kanna, paapaa ti awọn agbeka diẹ ba wa tabi awọn iṣẹ itọju. O jẹ alaye kekere, ṣugbọn o ṣe idaniloju ideri ati ojò wa ni asopọ itanna ni gbogbo igba.

2.4 Asopọ ilẹ

Awọn asopo ilẹ ti wa ni agesin nitosi ipilẹ. O pese aaye iduroṣinṣin fun adaorin ilẹ ibudo, ati awọn ohun elo nigbagbogbo fẹran ifilelẹ yii fun fifi sori iyara. Ni kete ti a ti sopọ, o ṣe iranlọwọ lati ṣetọju ọna ilẹ iduroṣinṣin lakoko awọn aṣiṣe.

Grounding Connector

 

2.5 Igbesoke Lugs; Tapchanger; Titẹ Relief àtọwọdá

 

6

Awọn ọpa gbigbe ti wa ni welded sori ojò ati ni iwọn daradara fun iwuwo transformer, nitorinaa mimu ẹyọ naa pẹlu Kireni jẹ taara taara. Ko si - tapchanger fifuye nfunni ni atunṣe ± 2 × 2.5% lori yiyi HV; ohunkohun idiju, o kan to ni irọrun lati baramu foliteji ila. Awọn titẹ iderun àtọwọdá jẹ tun bayi lori awọn ojò oke. Ni awọn ipo titẹ aiṣedeede, o ṣii laifọwọyi lati tọju ojò ailewu.

 

03 Idanwo

Idanwo fun 75kVA -14.4/0.277kV olupilẹṣẹ opo ti o ti gbe transformer ni a ṣe ni 2025-04-25 (iwọn otutu: 23.9 iwọn , RH: 36%) ni ila pẹlu CSA C2.2-06(R2022) ati CSA C122(R2022) Awọn idanwo igbagbogbo pẹlu resistance yikaka (HV: 9.747-10.786Ω, LV: 5.875mΩ), idanwo ipin (iyapa +0.02~+0.06%, ẹgbẹ fekito Ii6), polarity (Afikun), ipadanu ko si/lọwọlọwọ (128.9W/010% 148.6W/0.23% ni 105%), fifuye pipadanu / impedance (912W ni 85 iwọn, ikọjujasi 2.21%, ṣiṣe 99.11% Tobi ju tabi dogba si 98.94%), foliteji withstand (LV 10kV / 60s, induced 0.554kV/240Hz/30s,5) resistance, 7GB resistance 20kPa / 12h idanwo jo (ko si jijo), ati idanwo epo (dielectric agbara 53.9kV). Gbogbo koja; Iroyin naa ko le ṣe daakọ laisi igbanilaaye SCOTECH, awọn atako gbọdọ wa ni dide laarin awọn ọjọ 7, ati pe ko wulo laisi awọn ibuwọlu oluyẹwo / oludaniloju / alakosile.

Rara.

Nkan Idanwo

Ipari

1

Awọn wiwọn Resistance

Kọja

2

Awọn idanwo ipin

Kọja

3

Awọn idanwo polarity

Kọja

4 Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun

Kọja

5 Awọn adanu fifuye, foliteji impedance, awọn adanu lapapọ ati ṣiṣe

Kọja

6 Applied Foliteji Igbeyewo

Kọja

7 Induced Foliteji withstand Igbeyewo

Kọja

8 Idiwon Resistance idabobo

Kọja

9 Idanwo jijo

Kọja

10 Idanwo epo Kọja

 

04 Iṣakojọpọ ati Sowo

4.1 Iṣakojọpọ

Oluyipada ti a gbe sori opo alakoso ẹyọkan ti wa ni akopọ ninu apoti igi ti o lagbara kan. Ẹran naa jẹ ti aṣa{1} lati baamu awọn iwọn transformer, pese aabo igbẹkẹle si awọn ipaya ita, awọn ipa kekere, ati ọrinrin lakoko gbigbe ati ibi ipamọ. O ṣe idaniloju pe transformer naa wa ni iduroṣinṣin ati mule titi ti - fifi sori aaye.

image013

 

4.2 Gbigbe

image015

Fun opopo ipele kan ṣoṣo ti o gbe transformer, gbigbe ni atẹle ọrọ CIF pẹlu EDMONTON gẹgẹbi ibudo opin irin ajo. Olutaja naa ni iduro fun gbigbe aaye gbigbe okun, jiṣẹ onigi -ọla{2}} transformer ti a kojọpọ si Port EDMONTON, ati gbigbe awọn idiyele ẹru ati ẹru lati bo awọn ewu irekọja ti o pọju. Nigbati transformer ba de ni Port EDMONTON, olura yoo gba awọn ọja naa, lakoko ti ewu ti transformer ti kọja si ẹniti o ra nigba ti o kuro ni ọkọ oju-irin ti ibudo ikojọpọ.

 

 

05 FAQ

 

image017

01.Kí Ni -Opa Ipele Ipele Kan -Ayipada Ti A gbe soke ati Kini A Nlo Fun?

Ayipada -opa ipele kan-kan ti a gbe sori transformer jẹ oluyipada pinpin ti a fi sori ẹrọ taara sori ọpá ohun elo. Iṣẹ rẹ jẹ taara: o sọkalẹ alabọde{3}}laini foliteji si kekere{4}}ipele foliteji ti o yẹ fun awọn ile, awọn iṣowo kekere, tabi ina miiran-awọn olumulo iṣẹ. Nitoripe o jẹ iwapọ ati pe ko nilo aaye aaye -, o ṣiṣẹ daradara ni awọn agbegbe nibiti awọn paadi ohun elo ti nira lati kọ-tabi ko ṣe pataki. Iwọ yoo rii nigbagbogbo ni awọn nẹtiwọọki igberiko, awọn opopona igberiko, tabi awọn agbegbe agbegbe ti o dapọ nibiti o nilo igbẹkẹle ṣugbọn aaye ni opin.

02.Kini Ibiti Agbara Aṣoju ti Ẹyọkan-Ọpa Alakoso{1}}Arapada ti a gbe soke?

Pupọ julọ -ọpa alafojusi- awọn transformers ti a gbe soke ṣubu ni ibikan laarin 10 kVA ati 167 kVA. Iwọn yii ni wiwa pupọ julọ ti ibugbe ati awọn ohun elo iṣowo kekere, ati fun ọpọlọpọ awọn ohun elo, o pọ ju deedee lọ.
Diẹ ninu awọn olupese le funni ni titobi nla ti o ba nilo, botilẹjẹpe ni kete ti idiyele naa ba ga to, awọn olumulo ṣọ lati lọ si -ipele tabi paadi{1} awọn apẹrẹ ti a gbe soke dipo. O rọrun diẹ sii wulo ni aaye yẹn.

03.Kini Awọn Anfani Ti a Fiwera Pẹlu Ayipada Ipele Ipele Mẹta?

Ọpọlọpọ wa, ati pe wọn jẹ idanimọ daradara ni adaṣe pinpin:

Kukuru kekere {{0} awọn ifunni foliteji, eyiti o tumọ si awọn adanu kekere.
Nipa gbigbe transformer sunmo ẹru naa, awọn ohun elo le dinku idinku foliteji ati ilọsiwaju iṣẹ ṣiṣe ni ọjọ-si{1}} ọjọ.

A iwapọ be ti o nbeere fere ko si ilẹ.
Ko si paadi nja, ko si adaṣe, ko si si apade. Ọpa funrararẹ di eto atilẹyin, eyiti o jẹ ki fifi sori ẹrọ rọrun.

Rọrun fifi sori ẹrọ ati itọju.
Awọn onimọ-ẹrọ le wọle ati rọpo awọn ẹya wọnyi ni yarayara ju ipamo tabi paadi -awọn ohun elo ti a gbe soke, eyiti o fi akoko pamọ-paapaa lakoko imularada aṣiṣe.

Iwoye, o jẹ yiyan ti o wulo nigbati ẹru ba jẹ iwọntunwọnsi ati agbegbe fifi sori ẹrọ ti ṣoki tabi tan kaakiri.

04. Kini fifi sori ẹrọ tabi Awọn aaye Itọju yẹ ki o ṣe akiyesi?

Awọn nkan diẹ ṣe pataki nibi, ati pe ko si ọkan ninu wọn ti o ni idiju, wọn ṣe pataki fun igbẹkẹle igba pipẹ{{0}.

Lo ọpa kan pẹlu agbara to. O gbọdọ ṣe atilẹyin ẹrọ iyipada lailewu ati duro ni iduroṣinṣin ni afẹfẹ ati oju ojo.

Jeki gbogbo awọn ebute ati awọn asopọ mọ ki o si mura daradara{{0}. Idọti, epo, tabi olubasọrọ ti ko dara le fa awọn iṣoro nigbamii. Awọn oludari tun nilo irọrun to lati koju pẹlu awọn iyipada iwọn otutu tabi gbigbọn.

Ṣayẹwo ipele epo, ipo epo, ati awọn igbo nigbagbogbo ti ẹyọ naa ba jẹ epo{0}}. Eyikeyi ami ti jijo tabi ibajẹ idabobo yẹ ki o ṣe pẹlu ni kutukutu.

Rii daju pe didasilẹ jẹ to lagbara. Ti o dara, kekere {{1} ipa ọna ilẹ resistance ṣe pataki fun aabo.

Ṣe ayewo wiwo lododun. Wa ipata, abuku, awọn abawọn epo, tabi idoti igbo.

Ṣe idanwo epo ati mimọ igbo ni gbogbo ọdun 2-3, tabi diẹ sii nigbagbogbo ni awọn iwọn otutu lile gẹgẹbi awọn agbegbe eti okun tabi awọn agbegbe ile-iṣẹ.

 

Awọn afiwe Gbona: Awọn olupilẹṣẹ òke igi, olupilẹṣẹ, olupese, idiyele, idiyele