50 KVA polu Ayirapada-14.4 / 0.12 * 0,24 KV|Canada 2025

50 KVA polu Ayirapada-14.4 / 0.12 * 0,24 KV|Canada 2025

Orilẹ-ede Ifijiṣẹ: Canada2025
Agbara: 50kVA
Foliteji: 14.4-0.12 / 0.24kV
Ẹya: Foliteji Meji & Idaabobo IFD
Fi ibere ranṣẹ

Jiangshan Scotech Electrical Co., Ltd jẹ ọkan ninu awọn olupese ti o gbẹkẹle julọ ati awọn olupese ti 50 kva polu transformers-14.4/0.12*0.24 kv|Canada 2025 ni China. Jọwọ lero ọfẹ lati ra awọn ọja to munadoko fun tita nibi ati gba awọn aworan atọka lati ile-iṣẹ wa. Kan si wa fun alaye sii.

 

50 kVA pole transformers

50 kVA pole transformers pẹlu Meji Voltage & Idaabobo IFD - daradara, gbaradi{2}}agbara setan fun etikun ati awọn nẹtiwọki pinpin igberiko

 

 

01 Gbogbogbo

1.1 Project Apejuwe

50 kVA ẹyọkan -ọpa alafojusi{2}} ti a gbe sori ẹrọ transformer jẹ apẹrẹ fun pinpin oke ti o gbẹkẹle ni awọn agbegbe eti okun ati igberiko. O ṣiṣẹ ni 60 Hz ati atilẹyin awọn foliteji akọkọ meji (24,940 GRDY tabi 14,400 V), gbigba fifi sori ẹrọ lori ọpọlọpọ awọn ifunni lakoko ti o pese iṣelọpọ 120/240 V lori ile-ẹkọ giga. Ẹyọ naa nlo awọn yiyi aluminiomu ati ipilẹ irin ti a fi lami, pẹlu itutu agbaiye ONAN ati erupẹ erupẹ{12}}epo ninu ojò edidi fun igbesi aye ita gbangba pipẹ. O ṣaṣeyọri Ti o tobi ju tabi dọgba si iṣẹ ṣiṣe 99.04%, laisi pipadanu fifuye 130 W, pipadanu ẹru 492 W, ati ikọlu 2.16% (± 10%). Ti kii ṣe - Oluyipada Fifọwọ ba (NLTC) ± 2 × 2.5% jẹ ki foliteji duro iduroṣinṣin labẹ awọn ẹru iyipada.

Transformer tun gbe imunina foliteji giga 9 kV{1} lati di monomono ati yiyi pada si ilẹ ṣaaju ki wọn le tẹnumọ idabobo tabi ibajẹ awọn afẹfẹ - gbọdọ fun awọn ifunni ti o farahan si iji ãra, sokiri iyọ, ati afẹfẹ igba otutu. Ẹya meji{4} foliteji ngbanilaaye awọn ohun elo lati tọju awọn iru ẹrọ oluyipada diẹ ninu iṣura ati fi awọn ẹyọ sii ni iyara lakoko ijade tabi awọn iṣagbega. Pẹlu iwọn 50 kVA, o le ṣe iranṣẹ awọn ile ati awọn iṣowo diẹ sii ju 25 kVA transformer, ṣiṣe ni igbẹkẹle, kekere{8}ojutu itọju fun awọn nẹtiwọọki pinpin okun ati igberiko.

 

 

 

1.2 Imọ pato

50kVA polu Ayirapada sipesifikesonu ati data dì

Jišẹ si
Canada
Odun
2025
Iru
Polu agesin transformer
Standard
CSA C2.2-06 / C802.1-23
Ti won won Agbara
50KVA
Igbohunsafẹfẹ
60HZ
Ipele
Nikan
Itutu agbaiye
ONAN
Insulant olomi
Epo Eruku
Primary Foliteji
24940GRDY/14400 V
Secondary Foliteji
120 / 240 V
Ẹgbẹ Vector
Ii6
Polarity
Àfikún
Ohun elo Yiyi
Aluminiomu
Ipalara
2.16%(±10%)
Iṣẹ ṣiṣe
Ti o tobi ju tabi dọgba si 99.04%
Tẹ Ayipada
NLTC
Ibiti titẹ ni kia kia
±2*2.5%
Ko si Ipadanu Ẹru
130 W
Ipadanu fifuye ni Foliteji ti a Ti wọn
492 W
Awọn ẹya ẹrọ
9kV HV Arrester

 

1.3 yiya

50kVA polu Ayirapada iyaworan ati nameplate

50 kVA pole transformers drawing 50 kVA pole transformers nameplate

 

 

Apẹrẹ ti a ṣe adani fun Awọn ipo oju-ọjọ eti okun

Niwọn bi aaye fifi sori ẹrọ wa ni agbegbe eti okun {{0} pẹlu afẹfẹ ọririn, ojo loorekoore, ati iyọ diẹ ninu afẹfẹ{1}}a kọja iṣeto ipilẹ kan a si ṣe awọn iṣagbega ifọkansi diẹ:

 

1. Giga{{1}Foliteji Awọn Ideri Aabo

 

A lọ siwaju ti a si fi awọn ideri aabo sori giga -awọn igbona foliteji{1} ni pataki lati jẹ ki idabobo yẹn dun ati iduroṣinṣin. O mọ, ni ọririn, ti ojo, nigbamiran agbegbe ti o tutu, idabobo ti o farahan jẹ iru ibeere fun wahala. Awọn ideri wọnyi? Wọn ṣe aabo ni ipilẹ lati ọrinrin, lati afẹfẹ eti okun iyọ, lati gbogbo awọn ohun kekere ti o le jẹ ki igbesi aye le fun oluyipada.

High-Voltage Bushing Protective Covers
 
High-Voltage Bushing Protective Covers drawing

2. 9 kV HV Agbofinro

Ki o si nibẹ ni 9 kV HV arrester. Kekere, bẹẹni, ṣugbọn o jẹ ohun nla nigbati awọn ifaworanhan iyalẹnu wọnyẹn kọlu- iji, yi pada, tabi awọn airotẹlẹ oju-ọjọ eti okun nikan. O wa nibẹ lati mu wọn, da awọn filasi duro, ati pe o jẹ ki eto naa jẹ ki o ja ni ọjọ buburu kan.

9 KV HV Arrester

 

 

02 iṣelọpọ

2.1 mojuto

50 kVA pole transformers iron core

A ṣe ipilẹ ọgbẹ fun lilo ita gbangba. Apẹrẹ tolera rẹ koju gbigbọn ati ki o jẹ ki ẹrọ oluyipada duro lori awọn ọpa. Ko dinku - pipadanu fifuye, ṣiṣẹ daradara lori awọn ifunni gigun, ati pe o le mu afẹfẹ, yinyin, ati oju ojo miiran, fifun awọn ile ati awọn iṣowo kekere ina ti o gbẹkẹle.

 

2.2 Yiyi

50 kVA pole transformers copper winding
50 kVA pole transformers iron and coil

Òpó yìí -Típadàrọ́pọ̀ tí a fi ń lò ń lo yíyíká fóìlì kékeré{{1}voltage àti - yíyí waya voltaji kan tó ga, bàbà àti àlùmọ́nì ní àpapọ̀. The LV bankanje ntọju impedance kekere. Ooru ti ntan boṣeyẹ. Waya HV jẹ rọ, mu awọn iyipada fifuye. Ejò -Idapọ aluminiomu{8}} ṣe iwọntunwọnsi ṣiṣe ati idiyele. Gbẹkẹle, ti o tọ, ni ibamu awọn grids kekere, ibugbe tabi iṣowo ina, lojoojumọ.

 

 

03 Idanwo

50 kVA pole transformers testing-1
50 kVA pole transformers testing-2

 

 

04 Iṣakojọpọ ati gbigbe

4.1 Iṣakojọpọ

50 kVA pole transformers waiting for packing
50 kVA pole transformers in box

 

4.2 Gbigbe

50 kVA pole transformers shipping-1
50 kVA pole transformers shipping-2

 

 

05 FAQ

50 kVA pole transformers on the pole line

Q1: Ṣe o jẹ ailewu lati fi sori ẹrọ ẹrọ iyipada ni ọrinrin tabi awọn agbegbe eti okun?

Bẹẹni, ni gbogbogbo o jẹ ailewu. Ṣugbọn, awọn agbegbe eti okun -ọriniinitutu, iyọ ninu afẹfẹ, nigbami o kan tutu ati ọririn -le jẹ lile lori transformer. Ìdí nìyí tí a fi dámọ̀ràn ọ̀rinrin - àwọn ọ̀nà tí kò lè sọ̀rọ̀, bíi gíga-àwọn ìdìbò fífẹ́lítì, àwọn ohun èlò ìpata-, àti ìpìlẹ̀ líle. Ṣe iranlọwọ idilọwọ awọn ọran idabobo. Ntọju ohun nṣiṣẹ gun. Ayẹwo iyara ni bayi ati lẹhinna mu awọn iṣoro ni kutukutu.

Q2: Le a transformer overheat?

O le. Paapa ti awọn ẹru ba ga, tabi ti o nṣiṣẹ nigbagbogbo, tabi fentilesonu ko pe. O nilo iwọn to dara ni akọkọ. Itutu? Pataki pupo. Òtútù epo tàbí ìwọ̀ntúnwọ̀nsì -Ṣàkíyèsí wọn. Ki o si mu ẹrọ oluyipada kan pẹlu iwọn iwọn otutu ti o tọ fun ẹru ti o nireti. Overheat gun ju, idabobo ogoro yiyara, ṣiṣe silẹ, eewu ikuna dide.

Q3: Ṣe imudani monomono pataki?

Bẹẹni, ni agbara. Paapaa awọn ṣiṣan kekere, manamana, yiyi awọn spikes{1} wọn ṣẹlẹ. Laisi imuni iṣẹ-abẹ, idabobo le kuna, awọn filasi le waye, igbesi aye transformer dinku. Ẹrọ ti o rọrun, ṣugbọn o ṣe iyatọ nla. Awọn iji ti eti okun tabi awọn grids ti ko duro{5}} imudani jẹ ifọkanbalẹ ti ọkan.

Q4: Igba melo ni o yẹ ki a ṣe itọju transformer?

O kere ju lẹẹkan lọdun. Awọn idanwo itanna - idabobo idabobo, idiwọ yiyi, awọn sọwedowo ipin. Ilẹ-ilẹ- rii daju pe o lagbara, aabo kekere. Idabobo - wa awọn dojuijako, ipata, ọrinrin. Epo - awọn ẹya ti a fibọmi bi? Ayẹwo didara epo, DGA, ọrinrin, acidity. Nigbakugba diẹ sii nigbagbogbo, ti ẹru ba wuwo tabi ayika ti o le. Ntọju o nṣiṣẹ, yago fun awọn iyanilẹnu.

 

 

Awọn afiwe Gbona: opopo transformers, olupese, olupese, owo, iye owo