50 kVA Amunawa Electric polu-13.8 / 0.347 kV|Canada 2025
Agbara: 50kVA
Foliteji: 13.8 / 0.347kV
Ẹya: Ga foliteji ė bushing

Agbara ti o gbẹkẹle fun awọn nẹtiwọọki ori oke ti Canada - CSA{1}} ni ibamu ati ita gbangba{2}} ṣetan
01 Gbogbogbo
1.1 Project abẹlẹ
Lati pade awọn ibeere ti pinpin ohun elo agbegbe ni Ilu Kanada, awọn ẹya mẹta ti 50 kVA, 13.8 kV ẹyọkan -pase opo-awọn transformer ti a gbe soke ni a fi jiṣẹ. Ti a ṣe apẹrẹ ati ti a ṣe ni ibamu pẹlu awọn iṣedede CSA C2.1 ati C802.1, awọn oluyipada wọnyi ṣe idaniloju iṣẹ ṣiṣe ti o gbẹkẹle ati ifaramọ ni kikun si awọn ibeere itanna Kanada.
Oluyipada kọọkan ṣe ẹya foliteji akọkọ ti 13.8 kV Delta ati foliteji keji ti 347 V, pẹlu iwọn BIL ti 95 kV/30 kV, ikọjujasi ti 2.3% ± 15%, iwọn otutu yikaka apapọ ti iwọn 65, ati polarity aropo. Ti a ṣe apẹrẹ fun itutu agba ONAN ita gbangba, awọn ẹyọ naa pẹlu 5{11}}iyipada ipo tẹ ni kia kia (±2×2.5%) ati pe wọn ni ipese pẹlu ideri{12}}ti a gbe ga{13}}foliteji ati ẹgbẹ{14}}ti a gbe soke{15}}awọn bushing foliteji fun fifi sori ọpa-oke.
Gẹgẹbi ojutu ọpa ina eletiriki aṣoju aṣoju, awọn ẹya wọnyi jẹ iṣẹ-ṣiṣe fun pinpin agbara oke ni awọn agbegbe ita ati pe o jẹ apẹrẹ fun:
• Awọn agbegbe ibugbe ni igberiko tabi awọn agbegbe igberiko
• Awọn ẹru iṣowo fẹẹrẹ pẹlu ipese{{0} alakoso kan
• Imugboroosi nẹtiwọki tabi imuduro atokan ni 13.8 kV
1.2 Imọ pato
50kVA ipele ẹyọkan ti ọpa ina mọnamọna ti a gbe sipesifikesonu ati iwe data
|
Jišẹ si
Canada
|
|
Odun
2025
|
|
Iru
Polu agesin transformer
|
|
Standard
CSA C2.1
|
|
Ti won won Agbara
50 kVA
|
|
Igbohunsafẹfẹ
60HZ
|
|
Polarity
Iyokuro
|
|
Ẹgbẹ Vector
Ii0
|
|
Primary Foliteji
13800 V
|
|
Secondary Foliteji
347 V
|
|
Ohun elo Yiyi
Idẹ
|
|
Ipalara
2.3%
|
|
Ọna Itutu
ONAN
|
|
Tẹ Ayipada
NLTC
|
|
Ibiti titẹ ni kia kia
±2X2.5%
|
|
Iṣẹ ṣiṣe
98.84 %
|
|
Ko si Ipadanu Ẹru
135 W
|
|
Lori Ipadanu Fifuye
705 W
|
|
Awọn ẹya ẹrọ
Standard iṣeto ni
|
1.3 Yiya
50kVA ipele ẹyọkan ti ọpa ina mọnamọna ti o gbe awọn iwọn iyipada ati awọn alaye iwuwo
![]() |
![]() |
02 iṣelọpọ
2.1 mojuto
Òpó iná mànàmáná 50kVA yìí jẹ́ àwòkẹ́kọ̀ọ́ -otútù dídára kan{2}} tí a yípo, irin tí a dá sílẹ̀ nípa yíyí. Ilana iwapọ rẹ ati iyika oofa aṣọkan ni imunadoko dinku pipadanu fifuye - si 160W. Ti ṣe apẹrẹ lati ba awọn iṣedede CSA C2.1 mu, o dara daradara- fun awọn ohun elo pinpin 13.8/0.347kV.

2.2 Yiyi
Yiyi transformer nlo ohun elo bàbà, pẹlu iwọn kekere{0}foliteji ti a ṣe nipasẹ yiyi waya ati giga{1}}foliteji ti a ṣe lati yiyi foil. Ijọpọ yii ṣe idaniloju iṣiṣẹ itanna eletiriki ti o dara julọ ati sisọnu ooru daradara. Polarity iyokuro ati ẹgbẹ fekito Ii0 ni a ṣe ni deede nipasẹ awọn onimọ-ẹrọ ti oye lati mu iṣẹ ṣiṣe ati igbẹkẹle pọ si, ni ipade awọn iṣedede iṣelọpọ to muna.
2.3 ojò

Awọn ojò transformer ti wa ni ṣe ti o tọ ìwọnba irin ati ki o ti a bo pẹlu ina grẹy iposii kun lati jẹki ipata resistance. Ti a ṣe apẹrẹ bi igbekalẹ edidi, o ṣe idiwọ jijo epo ni imunadoko ati ifọle ọrinrin. Ẹka kọọkan n gba afẹfẹ ti o muna{2}}idanwo wiwọ lati rii daju iṣẹ edidi to dara julọ, pese aabo igbẹkẹle fun awọn paati inu ni awọn agbegbe ita gbangba lile
2.4 ik Apejọ
Lakoko apejọ, awọn bushings HV ni a gbe sori oke ojò, pẹlu ebute H1 nipa lilo dimole 4- ati H2 ti a so sinu inu nipasẹ awọn boluti. LV spade ebute oko ti fi sori ẹrọ lori ojò ẹgbẹ fun rorun onirin. Ipilẹ mojuto, ilẹ ojò, ati awọn okun ilẹ ti wa ni ti fi sori ẹrọ, pẹlu irin alagbara, irin ọkan-iho spade grounding ebute ni idaniloju ailewu ati iṣẹ igbẹkẹle.

03 Idanwo
Idanwo baraku
1. Resistance wiwọn
2. Awọn idanwo ipin
3. Polarity igbeyewo
4. Ko si Awọn ipadanu fifuye ati Ko si fifuye lọwọlọwọ
5. Fifuye adanu ati Impedance Foliteji
6. Applied Foliteji Igbeyewo
7. Induced Foliteji withstand Igbeyewo
8. Idiwọn Resistance Insulation
9. Idanwo Leak pẹlu Ipa fun Liquid Immersed Transformers
10. Epo Idanwo

Awọn abajade idanwo
|
Rara. |
Nkan Idanwo |
Ẹyọ |
Gbigba Awọn iye |
Awọn iye Diwọn |
Ipari |
|
1 |
Awọn wiwọn Resistance |
/ |
/ |
/ |
Kọja |
|
2 |
Awọn idanwo ipin |
/ |
Iyapa ti ipin foliteji lori titẹ ni akọkọ: Kere ju tabi dọgba si ± 0.5% Aami asopọ: Ii6 |
0.05~0.08 |
Kọja |
|
3 |
Awọn idanwo polarity |
/ |
Àfikún |
Àfikún |
Kọja |
|
4 |
Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun |
% |
I0 :: pese iye iwọn (100%) |
0.24 |
Kọja |
|
kW |
P0: pese iye iwọn (100%) |
0.1089 |
|||
|
% |
I0 :: pese iye iwọn (105%) |
0.27 |
|||
|
kW |
P0: pese iye diwọn (105%) |
0.123 |
|||
|
/ |
Ifarada fun ko si pipadanu ẹru jẹ +15% |
/ |
|||
|
5 |
Awọn adanu fifuye, foliteji impedance, awọn adanu lapapọ ati ṣiṣe |
/ |
t:85 iwọn ifarada fun ikọjujasi jẹ ± 15% ifarada fun pipadanu fifuye lapapọ jẹ +8% |
/ |
Kọja |
|
% |
Z%: iye iwọn |
2.27 |
|||
|
kW |
Pk: iye iwọn |
0.636 |
|||
|
kW |
Pt: iye iwọn |
0.7449 |
|||
|
% |
Ṣiṣe ko kere ju 98.84% |
99.00 |
|||
|
6 |
Applied Foliteji Igbeyewo |
/ |
LV: 10kV 60s HV: 34kV 60s |
Ko si iparun ti foliteji idanwo waye |
Kọja |
|
7 |
Induced Foliteji withstand Igbeyewo |
/ |
Applied foliteji (KV): 0.694 |
Ko si iparun ti foliteji idanwo waye |
Kọja |
|
Iye akoko:40 |
|||||
|
Igbohunsafẹfẹ (HZ): 180 |
|||||
|
8 |
Idiwon Resistance idabobo |
GΩ |
HV-LV·to·Ilẹ |
26.3 |
Kọja |
|
LV-HV si Ilẹ |
32.2 |
||||
|
HV&LV si Ilẹ |
28.7 |
||||
|
9 |
Idanwo jijo |
/ |
Ipa titẹ: 20kPA |
Ko si jijo ati ki o ko Bibajẹ |
Kọja |
|
Iye akoko: 12h |
|||||
|
10 |
Idanwo epo |
kV |
Dielectric Agbara |
60.9 |
Kọja |
|
mg/kg |
Ọrinrin akoonu |
10.5 |
|||
|
% |
Okunfa ifasilẹ |
0.138 |
|||
|
mg/kg |
Furan Analysis |
Kere ju tabi dogba si 0.1 |
|||
|
/ |
Gaasi Chromatography Analysis |
/ |
04 Iṣakojọpọ ati Sowo


05 Ojula ati Lakotan
Ayipada yi fun awọn ohun elo ọpá ina jẹ 50 kVA ẹyọkan -ọpa ipele{2}} ti a gbe soke ni pataki ti a ṣe apẹrẹ fun awọn eto pinpin agbegbe ni Ilu Kanada, ti o ni ibamu pẹlu awọn iṣedede agbara North America pataki. O jẹ apẹrẹ fun awọn oju iṣẹlẹ ipese agbara oke ita ni 13.8 kV, pataki ni pataki fun awọn agbegbe ibugbe igberiko, awọn ohun elo iṣowo kekere, ati awọn iṣẹ akanṣe imugboroja ti o nilo ailewu, igbẹkẹle, ati kekere{{5} ohun elo agbara itọju.
Pẹlu iduroṣinṣin igbekalẹ to lagbara ati iṣẹ iduroṣinṣin, a ti kọ ẹrọ iyipada lati koju oju ojo lile ati awọn ipo ayika. O ṣe ifidimọ to dara julọ ati awọn agbara itutu agbaiye, pẹlu giga -ṣiṣe ṣiṣe, agbara - apẹrẹ fifipamọ lati pade awọn ibeere Kanada ti o muna fun itọju agbara ati igbẹkẹle. Olumulo rẹ - fifi sori ore ati igba pipẹ - jẹ ki o jẹ yiyan ti o dara julọ fun awọn ile-iṣẹ iwUlO ati awọn iṣẹ akanṣe idagbasoke ti o nii ṣe pẹlu ọpá ina mọnamọna{6}} awọn oluyipada.

Awọn afiwe Gbona: ọpá ina transformer, olupese, olupese, owo, iye owo
You Might Also Like
167 kVA Cooper Paadi Amunawa-13.8 / 0.24 kV|Guyana 2024
167 kVA Power polu Amunawa-13.8 / 0.347 kV|Canada 2025
37,5 kVA ọpá Amunawa-2.4 / 0,12 kV|Canada 2025
50 kVA Amunawa IwUlO polu-13.8 / 0,24 kV|Guyana 2025
500 kVA ọpá Amunawa-24.94 / 0,6 kV|Canada 2025
167 kVA Ọpa Agbekale Pipin Amunawa-24.94 / 0.12 / 0....
Fi ibere ranṣẹ