50 Kva Amunawa Ọpa Oke-13.8 / 0.12 * 0.24 KV|AMẸRIKA 2025

50 Kva Amunawa Ọpa Oke-13.8 / 0.12 * 0.24 KV|AMẸRIKA 2025

Orilẹ-ede Ifijiṣẹ: USA 2025
Agbara: 50 kVA
Foliteji: 13.8-0.12 / 0.24kV
Ẹya: HV yikaka: Ejò, LV yikaka: Aluminiomu
Fi ibere ranṣẹ

 

50 kva transformer pole mount

Gbẹkẹle ati lilo daradara 50 kVA ọpá- ẹrọ oluyipada, ti a ṣe fun awọn nẹtiwọọki pinpin North America pẹlu iṣẹ ṣiṣe to gaju

 

 

01 Gbogbogbo

1.1 Project Apejuwe

50 kVA ẹyọkan -ọpa ipele{2}} ti a gbe sori ẹrọ transformer ni alakọbẹrẹ 13.8 kV ati 120/240 V keji. Ti ṣe apẹrẹ si IEEE C57.12.20 fun awọn oluyipada pinpin oke. O dara fun 13.8 kV mẹta{10}}apakan, awọn nẹtiwọki pinpin waya mẹta{11} ni Ariwa America. Awọn ẹya ara ẹrọ transformer ONAN adayeba epo itutu pẹlu erupe epo idabobo. Pẹlu idojukọ lori ṣiṣe ati iṣapeye aaye, Scotech lo mejeeji aluminiomu ati yikaka Ejò. Polarity jẹ iyokuro, ati pe ẹgbẹ fekito jẹ Ii0, aridaju ilana ti o pe ni nẹtiwọọki pinpin. Awọn ifojusi iṣẹ ṣiṣe pẹlu ko si - pipadanu fifuye ti 0.14 kW, ipadanu ẹru ti 0.527 kW, adanu lapapọ ti 0.667 kW, ati - imunadoko fifuye ti 98.97%. Impedance jẹ 2.86%, laarin awọn sakani oniyipada pinpin aṣoju. Ni afikun, transformer naa ni ipese pẹlu ko si -ayipada titẹ fifuye (NLTC) gbigba gbigba giga{27}} atunṣe foliteji lati 14, 400 V si 12, 540 V lati gba awọn iyipada foliteji ninu netiwọki.

 

1.2 Imọ pato

50kVA ọpá alakoso ẹyọkan ti o gbe sipesifikesonu transformer ati iwe data

Jišẹ si
USA
Odun
2025
Iru
Polu agesin Amunawa
Standard
IEEE C57.12.20
Ti won won Agbara
50 kVA
Igbohunsafẹfẹ
60HZ
Ipele
Nikan
Itutu agbaiye
ONAN
Insulant olomi
Epo Eruku
Primary Foliteji
13.8kV
Secondary Foliteji
0,12 / 0,24 kV
Ẹgbẹ Vector
Ii0
Polarity
Iyokuro
Ohun elo Yiyi
HV: Ejò, LV:Aluminiomu
Iṣẹ ṣiṣe
98.97 %
Ipalara
2.86%
Tẹ Ayipada
NLTC
Ibiti titẹ ni kia kia
14400,13800,13200,12870,12540
Ko si Ipadanu Ẹru
0.14 kW
Lori Ipadanu Fifuye
0,527 kW
Awọn ẹya ẹrọ
Standard iṣeto ni

 

1.3 yiya

50kVA paadi alakoso ẹyọkan ti a gbe sori aworan apẹrẹ ati iwọn.

50 kva transformer pole mount drawing 50 kva transformer pole mount nameplate

 

 

02 iṣelọpọ

2.1 mojuto

Lilo ọkà -irin silikoni ti o da, mojuto ọgbẹ n pese iṣẹ oofa to dara julọ nipa didin ipalọkuro ni ọna ṣiṣan. Apẹrẹ yago fun itẹlọrun oofa, ni idaniloju iṣẹ iduroṣinṣin labẹ awọn iyatọ fifuye. Ti a fiwera si awọn ohun kohun ti aṣa, eto ọgbẹ ko dinku - pipadanu fifuye ati pe ko si{4}} fifuye lọwọlọwọ, lakoko ti o tun dinku gbigbọn ati ariwo. Awọn anfani wọnyi jẹ ki mojuto ọgbẹ ni agbara gaan-daradara ati igbẹkẹle ninu awọn eto pinpin.

 

2.2 Yiyi

Yiyi foliteji giga n gba ikole concentric pẹlu okun waya Ejò elekitiroti ti 99.9% ti nw, enamel ti ya sọtọ, aridaju iṣe adaṣe ko kere ju 100% IACS. Idabobo igbona duro de iwọn 105. Yiyi LV nlo bankanje aluminiomu, eyiti o dinku awọn adanu lọwọlọwọ eddy, ṣe idaniloju iduroṣinṣin ẹrọ ti o lagbara, ati pade awọn ibeere pinpin ohun elo.

50 kva transformer pole mount winding

 

2.3 ojò

50 kva transformer pole mount oil tank

Ojò oluyipada jẹ ọna iyipo iyipo ti o ni edidi ti a ṣe ti irin ìwọnba pẹlu ibora dada ni awọ RAL7035. O jẹ apẹrẹ laisi ayewo tabi awọn iho itọju lati rii daju pe iduroṣinṣin. Ideri domed yiyọ kuro ni a lo fun iraye si. Awọn biraketi iṣagbesori jẹ irin pẹlu sisanra ti o kere ju ti 3.4 mm. Awọn opin ti wa ni marun ati welded si awọn ojò body. Eyi jẹ ki eto naa lagbara ati ti o tọ.

 

2.4 ik Apejọ

1. Apejọ Yiyi:Rọra awọn iyipo HV/LV sori mojuto laminated, aridaju titete to dara ati iduroṣinṣin idabobo.
2. Awọn Isopọ Itanna:Sopọ yikaka nyorisi tẹ ni kia kia oluyipada, bushings, ati awọn miiran irinše, ki o si ni aabo ati ki o idabobo awọn isẹpo.
3. Kokoro -Gbigbe okun:Gbe apakan ti nṣiṣe lọwọ ti o pejọ (mojuto + windings) sinu adiro gbigbe fun alapapo igbale lati yọ ọrinrin kuro.
4. Fifi sori ojò:Gbe apakan ti nṣiṣe lọwọ ti o gbẹ sinu ojò, gbe si ni aabo, ati rii daju idabobo to dara lati awọn odi ojò.
5. Iṣagbesori Ẹya ẹrọ:Fi bushings sori ẹrọ, àtọwọdá iderun titẹ ati awọn ẹya ẹrọ miiran, lẹhinna ṣayẹwo fun awọn n jo.
6. Nkún Epo & Ṣiṣeto:Igbale-kun pẹlu epo idabobo, degas, ati gba laaye lati yanju ṣaaju ṣiṣe ayẹwo awọn ipele epo ati agbara dielectric.

50 kva transformer pole mount active part

 

 

03 Idanwo

Igbeyewo Standard ati baraku Igbeyewo

IEEE C57.12.20 -2017: IEEE Standard for Overhead-Iru Distribution Transformers 500 kVA ati Kere; Foliteji giga, 34500 V ati Ni isalẹ; Foliteji Kekere,7970/13 800YV ati Ni isalẹ
IEEE C57.12.90-2021: IEEE Standard Code Testing fun Distrbud-Immersed Liquid, Power, ati Awọn Ayirapada ti n ṣakoso
CSA C802.1-13 (R2022): Awọn iye ṣiṣe to kere julọ fun awọn oluyipada pinpin olomi
 

1. Resistance wiwọn
2. Awọn idanwo ipin
3. Polarity igbeyewo
4. Ko si Awọn ipadanu fifuye ati Ko si fifuye lọwọlọwọ
5. Fifuye adanu ati Impedance Foliteji
6. Applied Foliteji Igbeyewo
7. Induced Foliteji withstand Igbeyewo
8. Idiwọn Resistance Insulation
9. Idanwo Leak pẹlu Ipa fun Liquid Immersed Transformers
10. Oil Dielectric igbeyewo
 

Awọn abajade Idanwo

Rara.

Nkan Idanwo

Ẹyọ

Gbigba

Awọn iye

Awọn iye Diwọn

Ipari

1

Awọn wiwọn Resistance

/

/

/

Kọja

2

Awọn Idanwo Ipin

/

Iyapa ti ipin foliteji lori titẹ ni akọkọ: Kere tabi dọgba si 0.5%

Aami asopọ: Ii0

-0.02

Kọja

3

Awọn idanwo polarity

/

Iyokuro

Iyokuro

Kọja

4

Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun

%

kW

I0 :: pese iye iwọn

P0: pese iye iwọn

Ifarada fun ko si pipadanu ẹru jẹ +10%

0.22

0.107

Kọja

5

Awọn adanu fifuye, foliteji impedance, awọn adanu lapapọ ati ṣiṣe

/

kW

kW

t:85 iwọn

Z%: iye iwọn

Pk: iye iwọn

Pt: iye iwọn

ifarada fun ikọjujasi jẹ ± 10%

ifarada fun pipadanu fifuye lapapọ jẹ +6%

2.93

0.557

0.664

99.07

Kọja

6

Applied Foliteji Igbeyewo

/

HV: 30KV 60s

LV: 10kV 60s

Ko si iparun ti foliteji idanwo waye

Kọja

7

Induced Foliteji withstand Igbeyewo

/

Foliteji ti a lo (KV):

2 Úrì

Iye akoko: 48

Igbohunsafẹfẹ (HZ): 150

Ko si iparun ti foliteji idanwo waye

Kọja

8

Idiwon Resistance idabobo

HV{0}LV si Ilẹ

LV-HV si Ilẹ

HV&LV si Ilẹ

96.9

49.1

55.8

Kọja

9

Idanwo jijo

/

Ipa titẹ: 20kPA

Iye akoko: 12h

Ko si jijo ati ko si

Bibajẹ

Kọja

10

Idanwo Dielectric Epo

kV

Ti o tobi ju tabi dọgba si 45

59.1

Kọja

 

 

04 Iṣakojọpọ ati Sowo

50 kVA single-phase pole-mounted transformer packing

 
 

05 Ojula ati Lakotan

50 kVA ẹyọkan -ọpa ipele{2}} ti a gbe sori ẹrọ ti n ṣiṣẹ fun awọn nẹtiwọọki pinpin oke ni Ariwa Amerika. O nlo itutu agba epo ONAN ati ṣiṣe daradara. Awọn mojuto ti wa ni ṣe ti egbo silikoni, irin. Awọn windings lo dara Ejò ati aluminiomu. Eyi yoo fun foliteji iduroṣinṣin, awọn adanu kekere, ati iṣẹ idakẹjẹ. Ko ni - oluyipada tẹ ni kia kia fun atunṣe foliteji. Ojò jẹ lagbara ati ki o kü. O ṣiṣẹ daradara fun awọn ile ati awọn iṣowo. Scotech ṣe kọọkan transformer fara. Ẹka kọọkan ni ibamu pẹlu awọn ajohunše agbaye.

50 kVA single-phase pole-mounted transformer

 

Awọn afiwe Gbona: 50 kva òke ọpá transformer, olupese, olupese, owo, iye owo

Fi ibere ranṣẹ