1500 KVA Ayirapada Electrical Box-4.16 / 0.48 KV|AMẸRIKA 2025

1500 KVA Ayirapada Electrical Box-4.16 / 0.48 KV|AMẸRIKA 2025

Orilẹ-ede: USA 2024
Agbara: 1500 kVA
Foliteji: 4.16D-0.48Y / 0.277 kV
Ẹya: pẹlu Schrader àtọwọdá
Fi ibere ranṣẹ

 

image001

Paadi- Awọn Ayirapada ti a gbe soke: Ipele ode oni fun Agbara Pipin.

 

 

01 Gbogbogbo

1.1 Project Apejuwe

1000 kVA mẹta alakoso pad agesin transformer ti a jišẹ si America ni 2024. Awọn won won agbara ti awọn transformer jẹ 1500 kVA pẹlu ONAN itutu. Iwọn giga giga jẹ 4.16D kV pẹlu ± 2 * 2.5% ibiti o tẹ (NLTC), foliteji kekere jẹ 0.48Y / 0.277 kV, wọn ṣẹda ẹgbẹ fekito ti Dyn1.

Ti a ṣe ẹrọ fun igbẹkẹle ati ailewu ni awọn nẹtiwọọki pinpin itanna, Paadi wa {{0}Ayipada Ayipada jẹ okuta igun-ile ti awọn ọna ṣiṣe agbara ipamo ti ode oni. Ti a ṣe apẹrẹ fun isọpọ ailopin sinu ibugbe, iṣowo, ati awọn ala-ilẹ ile-iṣẹ, o pese iṣẹ ṣiṣe to lagbara lakoko ti o ṣaju aabo gbogbo eniyan ati lakaye ẹwa.

Ẹya bọtini kan ti n ṣe idasiran si agbara ailagbara rẹ ati igbẹkẹle igba pipẹ - ni lilo awọn igbo giga ti tanganran foliteji{1}. Olokiki fun agbara ẹrọ ti o ga julọ, awọn ohun-ini dielectric ti o dara julọ, ati imudari atako si ibajẹ ayika, awọn bushings tanganran wọnyi ṣe idaniloju aaye asopọ to ni aabo ati iduroṣinṣin fun alabọde{3}} awọn kebulu foliteji. Itumọ ti o lagbara wọn n pese iṣẹ ṣiṣe to dayato labẹ iwọn otutu ati awọn aapọn itanna, ni idaniloju iduroṣinṣin lori awọn ewadun ti iṣẹ.

Ti a fi sinu ibi-ifọwọyi{0}}, apade irin titiipa, transformer yii ṣopọpọ didara iṣẹ-ṣiṣe ti akoko{1}}awọn ohun elo idanwo bii tanganran pẹlu koko to ti ni ilọsiwaju ati imọ-ẹrọ okun. O duro bi aabo, profaili kekere{{3}, ati ojuutu ti o gbẹkẹle gaan fun sisọ agbara mu lọna ti o dara lati akoj ohun elo si olumulo-opin.

 

 

 

1.2 Imọ pato

1500 kVA paadi agesin transformer ni pato iru ati data dì

Jišẹ si
USA
Odun
2024
Iru
Paadi agesin transformer
Standard
IEEE Std C57.12.34-2022
Ti won won Agbara
1500 kVA
Igbohunsafẹfẹ
60HZ
Ipele
3
Ifunni
Loop
Iwaju
Òkú
Itutu agbaiye
ONAN
Primary Foliteji
4.16D kV
Secondary Foliteji
0.48Y / 0.277 kV
Ohun elo Yiyi
Aluminiomu
Ẹgbẹ Vector
Dyn1
Ipalara
5.75%
Iṣẹ ṣiṣe
99.48%
Tẹ Ayipada
NLTC
Ibiti titẹ ni kia kia
±2*2.5%
Ko si Ipadanu Ẹru
1.545 kW
Lori Ipadanu Fifuye
10.54 kW

 

1.3 Yiya

1500 kVA paadi agesin transformer aworan atọka yiya ati iwọn.

image003 image005

 

 

02 iṣelọpọ

2.1 mojuto

image007

Kokoro wa ko dinku - adanu fifuye nipasẹ 70%, fifipamọ agbara ti o pọju ati awọn idiyele igbesi aye kekere fun ROI ti o ga julọ. Ti a ṣe fun igbẹkẹle ati iṣẹ idakẹjẹ, o jẹ ijafafa ti o gun julọ{3}} idoko-owo igba.

 

2.2 Yiyi

Wa paadi agesin Ayirapada ẹya-ara gbẹkẹle aluminiomu bankanje HV ati waya LV windings. Apẹrẹ yii ṣe idaniloju agbara kukuru ti o lagbara{1} ati iṣẹ igbona, fifun ọ ni akoko ti o pọ julọ ni idiyele kekere ju awọn omiiran bàbà lọ.

image009

 

2.3 ojò

image011

Apo wa jẹ ti ailabo, irin ipata -, ti a ṣe idanwo lile lati ṣe ẹri idalẹnu jijo{1}} fun igbesi aye. Eyi yọkuro awọn aniyan itọju ati mimọ ayika ti o ni iye owo, pese igbẹkẹle lapapọ ati awọn idiyele igba pipẹ kekere-.

 

2.4 ik Apejọ

Ipejọ ikẹhin ti paadi wa{0} awọn oluyipada ti a gbe soke ṣepọ mojuto, coils, ati ojò pẹlu titete deede ati awọn ilana ti a fihan. Eyi ṣe idaniloju iṣẹ ṣiṣe to dara julọ, ariwo ti o dinku ati gbigbọn, ati iduroṣinṣin igbekalẹ igba pipẹ{{2}. O gba ẹrọ oluyipada ti o nṣiṣẹ ni idakẹjẹ ati ni igbẹkẹle lati ọjọ kini, ṣe atilẹyin nipasẹ awọn iṣakoso didara wa ati iriri aaye lọpọlọpọ.

image013

 

 

03 Idanwo

Fun 1500kVA mẹta wa -paadi alakoso{2}} transformer (4160Δ{12}}480Y/277V), idanwo dojukọ awọn ohun pataki rẹ: idiyele kekere, ko si akoko idaduro. A pin data ti o han gbangba: 2.83% aiṣedeede yikaka (yago fun igbona pupọ), -0.23% ~ 0.15% awọn ipin titan (agbara iduroṣinṣin), 18.2-18.6GΩ idabobo (awọn aṣiṣe diẹ), 12h jo-free (ko si awọn idiyele epo), 56.4kV agbara epo (isẹ ailewu), ati agbara agbara 99). Gbogbo awọn metiriki pade awọn iṣeduro.

Rara.

Nkan Idanwo

Ẹyọ

Gbigba

Awọn iye

Iwọn Iwọn

Ipari

1

Awọn wiwọn Resistance

%

Iwọn aidogba resistance ti o pọju

2.83

Kọja

2

Awọn idanwo ipin

%

Iyapa ti ipin foliteji lori titẹ ni akọkọ: Kere tabi dọgba si 0.5%

-0.12

Kọja

3

Ipele{0}} igbeyewo ibatan

/

Dyn1

Dyn1

Kọja

4

Ko si - awọn adanu fifuye ati lọwọlọwọ igbadun

%

I0 :: pese iye iwọn

0.26

Kọja

kW

P0: pese iye iwọn (iwọn 20)

1.567

/

Ifarada fun ko si pipadanu fifuye jẹ ± 10%

/

5

Awọn adanu fifuye, foliteji ikọlu, awọn adanu lapapọ ati ṣiṣe

/

t:85 iwọn

ifarada fun ikọjujasi jẹ ± 7.5%

Ifarada fun pipadanu fifuye lapapọ jẹ ± 6%

/

Kọja

%

Z%: iye iwọn

5.67

kW

Pk: iye iwọn

10.475

kW

Pt: iye iwọn

12.042

%

Ṣiṣe ko kere ju 99.48%

99.48

6

Applied Foliteji Igbeyewo

/

HV: 19kV 60s

LV: 10kV 60s

Ko si iparun ti foliteji idanwo waye

Kọja

7

Induced Foliteji withstand Igbeyewo

/

Foliteji ti a lo (KV): 0.96

Ko si iparun ti foliteji idanwo waye

Kọja

Duration(s):48

Igbohunsafẹfẹ (HZ): 150

8

Idiwon Resistance idabobo

GΩ

HV{0}LV si Ilẹ:

18.2

/

LV-HV si Ilẹ:

18.6

HV&LV si Ilẹ:

18.5

9

Idanwo jijo

/

Ipa titẹ: 20kPA

Ko si jijo ati ki o ko

Bibajẹ

Kọja

Iye akoko: 12h

10

Idanwo epo

kV

Dielectric Agbara

56.4

Kọja

mg/kg

Ọrinrin akoonu

9.9

%

Okunfa ifasilẹ

0.00247

mg/kg

Furan Analysis

/

/

Gaasi Chromatography Analysis

/

 

image015
image017

 

04 Iṣakojọpọ ati Sowo

4.1 Iṣakojọpọ

image019

Awọn paadi alakoso{{0}mẹta{1} ti a gbe sori ẹrọ ti nmu idabobo meji: igbale akọkọ{2}} ti a fi sinu awọn baagi aluminiomu pẹlu awọn ohun mimu mimu (idaduro ipata, ọrọ ti o wọpọ ti awọn oludije foju kọju si), lẹhinna ti a we pẹlu awọn oludabobo igun ati ti kojọpọ sinu awọn apoti igi ti o lagbara. Ko dabi awọn apoti ti a ko samisi awọn miiran, tiwa ni forklift/aarin-ti{5}}awọn aami walẹ fun mimuurọrun- ni idaniloju pe ẹrọ oluyipada rẹ de ni pipe, ṣetan lati lo.

 

4.2 Gbigbe

Labẹ awọn ofin CIF wa si Port of Los Angeles, a gba ojuse ni kikun fun idiyele, iṣeduro, ati ẹru gbigbe rẹ. Ìbáṣepọ̀ pẹ̀lú - àwọn tí ń gbé ìpele òkè àti ètò àwọn ẹ̀rọ iṣẹ́-ìsọ̀rọ̀ dídánilójú pé ẹ̀rọ àyípadà rẹ dé lásìkò àti ní ipò pípé. Eyi yọkuro idiju ati awọn eewu ti gbigbe ilu okeere fun ọ, pese idaniloju idiyele ati alaafia ti ọkan.

image021

 

 

05 Ojula ati Lakotan

Nigbati o ba sọ pato awọn oluyipada paadi mẹta wa{0}, o n yan diẹ sii ju ọja kan lọ – o n nawo ni awọn ọdun mẹwa ti iṣẹ ṣiṣe igbẹkẹle. Lati awọn yiyi aluminiomu ti o lagbara ati jijo - ojò ẹri si iṣakojọpọ to ni aabo ati ifijiṣẹ iṣakoso, gbogbo alaye ni a ṣe lati dinku awọn idiyele igbesi aye rẹ ati awọn eewu iṣẹ ṣiṣe. A ṣe afihan igbẹkẹle ti o jẹ ki awọn iṣẹ akanṣe rẹ wa lori iṣeto ati agbara agbegbe rẹ, ni ọdun lẹhin ọdun.

image023

 

Awọn afiwe Gbona: Apoti itanna transformers, olupese, olupese, owo, iye owo

Fi ibere ranṣẹ